Non-Unit Ultra-High-Speed Line Protection for Multi-Terminal Hybrid LCC/MMC HVDC System and Its Application Research

被引:21
|
作者
Zhang, Chenhao [1 ]
Huang, Jinhai [2 ]
Song, Guobing [1 ]
Dong, Xinzhou [3 ]
机构
[1] Xi An Jiao Tong Univ, Dept Elect Engn, Xian 710049, Shaanxi, Peoples R China
[2] XJ Elect Co Ltd, Xuchang 461000, Henan, Peoples R China
[3] Tsinghua Univ, Dept Elect Engn, State Key Lab Control & Simulat Power Syst & Gene, Beijing 100084, Peoples R China
关键词
HVDC transmission; Circuit faults; Impedance; Reflection; Inductors; Equivalent circuits; Hybrid power systems; First peak time of line-mode fault component voltage; high sensitivity; multi-terminal hybrid LCC; MMC HVDC; ultra-high-speed line protection; DC FAULT-DETECTION; CONVERTER; TOPOLOGY;
D O I
10.1109/TPWRD.2020.3027723
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The multi-terminal hybrid LCC/MMC HVDC has been applied to overcome the simultaneous commutation failure problem caused by the multi-infeed LCC-HVDCs in the East China. The high-speed and selectivity line protection method is required for the multi-terminal hybrid HVDC system. In this paper, the reflection and refraction of the fault traveling waves at different kinds of line terminals are characterized by transfer functions. Then the fault voltage as well as its first peak time at different line terminals when different internal and external faults occur are derived respectively. The conclusion proves that the first peak time of line-mode fault component voltage (FPTV) for internal faults is smaller than that for external faults, which is independent of fault impedance and fault type as well. Therefore, a FPTV-based non-unit ultra-high-speed dc line protection method is proposed. The algorithm is implemented in the developed protection prototype and validated in the Kun-Liu-Long three-terminal hybrid HVDC RTDS test system. The test results show that the proposed method can fast and correctly identify line faults in the multi-terminal hybrid HVDC system, even with 500 omega fault impedance. Comparing with the traveling wave protection method of ABB, the proposed method improves the sensitivity when high-impedance faults occur.
引用
收藏
页码:2825 / 2838
页数:14
相关论文
共 20 条
  • [1] A non-unit line protection scheme for MMC-based multi-terminal HVDC grid
    Huang, Qiang
    Zou, Guibin
    Wei, Xiuyan
    Sun, Chenjun
    Gao, Houlei
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2019, 107 : 1 - 9
  • [2] Non-unit ROCOV scheme for protection of multi-terminal HVDC
    Jose Perez-Molina, Maria
    Eguia, Pablo
    Larruskain, Marene
    Buigues, Garikoitz
    Torres, Esther
    [J]. 2020 22ND EUROPEAN CONFERENCE ON POWER ELECTRONICS AND APPLICATIONS (EPE'20 ECCE EUROPE), 2020,
  • [3] Ultra-high-speed non-unit non-differential protection scheme for buses of MMC-HVDC grids
    Farshad, Mohammad
    [J]. IET RENEWABLE POWER GENERATION, 2020, 14 (09) : 1541 - 1549
  • [4] Application Research on Fast Line Protection and Adaptive Restarting Methods for Multi-terminal Hybrid LCC/MMC HVDC Transmission Lines
    Zhang C.
    Song G.
    Dong X.
    Huang J.
    [J]. Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2021, 41 (11): : 3873 - 3884
  • [5] A Non-unit transient travelling wave protection scheme for multi-terminal HVDC system
    Li, Botong
    Li, Yuqi
    Li, Bin
    Chen, Xiaolong
    Ji, Liang
    Hong, Qiteng
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2023, 152
  • [6] A Novel Protection Scheme for LCC-MMC Hybrid Multi-terminal HVDC Transmission Lines
    Zhou, Yi
    Cao, Junzheng
    Zhao, Jing
    Li, Yang
    Zhang, Chenhao
    Song, Guobing
    [J]. 2022 4TH INTERNATIONAL CONFERENCE ON SMART POWER & INTERNET ENERGY SYSTEMS, SPIES, 2022, : 638 - 642
  • [7] Non-Unit Ultra-High-Speed DC Line Protection Method for HVDC Grids Using First Peak Time of Voltage
    Zhang, Chenhao
    Song, Guobing
    Dong, Xinzhou
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (03) : 1683 - 1693
  • [8] Research on Line Protection Configuration Scheme of Hybrid Multi-terminal HVDC Transmission System
    Zhan, Qingqing
    Hao, Liangliang
    Chen, Zhengguang
    Wang, Xingguo
    [J]. PROCEEDINGS OF 2019 IEEE 3RD INTERNATIONAL ELECTRICAL AND ENERGY CONFERENCE (CIEEC), 2019, : 176 - 181
  • [9] Non-unit ultra-high-speed DC line protection method for HVDC grids using dynamic fitting algorithm with data reconstruction
    Yu, D. C.
    Zhou, N. C.
    Liao, J. Q.
    Wang, Q. G.
    Wei, N. Q.
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2023, 154
  • [10] Non-unit protection method for multi-terminal MMC-HVDC systems based on fault severity analysis and coordinated relay operation
    Marvasti, Farzad Dehghan
    Mirzaei, Ahmad
    Kavousi-Fard, Abdollah
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2023, 220