The possibility for formation of macro-cell corrosion in a liquid with low electrical conductivity

被引:5
|
作者
Matsumura, M.
机构
[1] Saijo-cho, Higashi-Hiroshima 739-0031
来源
关键词
carbon steel pipe; flow accelerated corrosion; macro-cell corrosion; micro-cell corrosion; mihama nuclear power plant; pure water;
D O I
10.1002/maco.200905573
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
The possibility of electrochemical corrosion of carbon steel at the rate of 3.25 x 10(-5) A/cm(2) in water was examined under the conditions present during an accidental pipe rupture at the Mihama nuclear power plant: liquid conductivity, 7.5 mu S/cm; dissolved oxygen concentration, 5 ppb or less; pH 8.6 similar to 9.3; ferrous ion concentration, 20 ppb or less; temperature, 142 degrees C. The corrosion rate of iron in a micro-cell with a dissolved oxygen reduction cathode was estimated to be only 1/400 of the preceding rate. On the other hand, that in a micro-cell with a hydrogen ion reduction cathode was estimated to be as high as 1/10 of the preceding rate, that is, 3.25 x 10(-6) A/cm(2). Two important factors may have influenced the corrosion rate: the remarkable wall thinning, which must have been the direct cause of the rupture of the pipe, was located close to, and downstream from, an orifice; and, the water temperature was in the range at which carbon steel makes a transition from the active to the passive state. Taking these facts into consideration, it appears possible that micro-cells with different corrosion rates might be generated and integrated into a macro-cell, where the iron dissolution rate might be accelerated to as much as 10 times that of the micro-cell.
引用
收藏
页码:449 / 453
页数:5
相关论文
共 50 条
  • [1] FEM simulation of corrosion under macro-cell mechanism
    Attarchi, Mehdi
    Brenna, Andrea
    Ormellese, Marco
    [J]. CORROSION SCIENCE, 2021, 179
  • [2] Proposed FAC mechanism using a macro-cell corrosion model
    Matsumura, Masanobu
    [J]. PROCEEDINGS OF THE ASME PRESSURE VESSELS AND PIPING CONFERENCE 2007, VOL 6: MATERIALS AND FABRICATION, 2007, : 767 - 776
  • [3] Evaluation of the corrosion risk in the mortar by monitoring macro-cell current
    Lu, Shuang
    Ba, Heng-Jing
    [J]. Gongneng Cailiao/Journal of Functional Materials, 2010, 41 (SUPPL. 2): : 235 - 238
  • [4] Effects of phosphates for macro-cell corrosion inhibitors on steel in concrete
    Kobayashi, Izuru
    Ozaki, Takeji
    [J]. Zairyo to Kankyo/ Corrosion Engineering, 2002, 51 (04): : 148 - 152
  • [5] Simulation of steel corrosion in concrete based on the mode of macro-cell corrosion circuit
    Maruya, Tsuyoshi
    Takeda, Hitoshi
    Horiguchi, Kenichi
    Koyama, Satoru
    Hsu, Kai-Lin
    [J]. JOURNAL OF ADVANCED CONCRETE TECHNOLOGY, 2007, 5 (03) : 343 - 362
  • [6] Analysis for macro-cell corrosion phenomena of steels exposed in sea water
    Matsuoka, Kazumi
    Yamamoto, Masahiro
    Goto, Kiyomi
    [J]. Zairyo to Kankyo/ Corrosion Engineering, 2007, 56 (03): : 99 - 105
  • [7] Macro-cell corrosion between crossed steel bars in cracked concrete
    Jin, Zhi-Hao
    Jiang, Chao
    Gu, Xiang-Lin
    Dong, Zheng
    [J]. CONSTRUCTION AND BUILDING MATERIALS, 2022, 350
  • [8] Morphology of corrosion products of steel in concrete under macro-cell and self-corrosion conditions
    Neff, D.
    Harnisch, J.
    Beck, M.
    L'Hostis, V.
    Goebbels, J.
    Meinel, D.
    [J]. MATERIALS AND CORROSION-WERKSTOFFE UND KORROSION, 2011, 62 (09): : 861 - 871
  • [9] On the applicability of the Stern-Geary relationship to determine instantaneous corrosion rates in macro-cell corrosion
    Angst, U.
    Buechler, M.
    [J]. MATERIALS AND CORROSION-WERKSTOFFE UND KORROSION, 2015, 66 (10): : 1017 - 1028
  • [10] Induced macro-cell corrosion phenomenon in the simulated repaired reinforced concrete patch
    Hussain, R.
    Wasim, M.
    Ishida, T.
    [J]. AUSTRALIAN JOURNAL OF CIVIL ENGINEERING, 2010, 8 (01) : 53 - 60