Review of time-domain polarization measurements for assessing insulation condition in aged transformers

被引:70
|
作者
Saha, TK [1 ]
机构
[1] Univ Queensland, Sch Informat Technol & Elect Engn, Brisbane, Qld 4072, Australia
关键词
polarization and depolarization currents; polarization measurements; return voltage measurement transformers insulation;
D O I
10.1109/TPWRD.2003.817741
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a review of the time-domain polarization measurement techniques for the condition assessment of aged transformer insulation. The polarization process is first described with appropriate dielectric response theories and then commonly used polarization methods are described with special emphasis on the most widely used "return voltage"(rv) measurement. Most recent emphasis has been directed to techniques of determining moisture content of insulation indirectly by measuring rv parameters. The major difficulty still lies with the accurate interpretation of return voltage results. This paper investigates different thoughts regarding the interpretation of rv results for different moisture and ageing conditions. Other time domain polarization measurement techniques and their results are also presented in this paper.
引用
收藏
页码:1293 / 1301
页数:9
相关论文
共 50 条
  • [1] Review of modern diagnostic techniques for assessing insulation condition in aged transformers
    Saha, TK
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2003, 10 (05) : 903 - 917
  • [2] Review of Physicochemical-Based Diagnostic Techniques for Assessing Insulation Condition in Aged Transformers
    N'cho, Janvier Sylvestre
    Fofana, Issouf
    Hadjadj, Yazid
    Beroual, Abderrahmane
    [J]. ENERGIES, 2016, 9 (05):
  • [3] Investigations into effective methods for assessing the condition of insulation in aged power transformers
    Darveniza, M
    Saha, TK
    Hill, DJT
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (04) : 1214 - 1223
  • [4] Electrical-Based Diagnostic Techniques for Assessing Insulation Condition in Aged Transformers
    Fofana, Issouf
    Hadjadj, Yazid
    [J]. ENERGIES, 2016, 9 (09)
  • [5] Experience with return voltage measurements for assessing insulation conditions in service aged transformers
    Saha, TK
    Yao, ZT
    [J]. 2003 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-4, CONFERENCE PROCEEDINGS, 2003, : 2370 - 2370
  • [6] Experience with return voltage measurements for assessing insulation conditions in service-aged transformers
    Saha, TK
    Yao, ZT
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (01) : 128 - 135
  • [7] Polarization State Measurements of Terahertz Time-Domain Pulses
    Neshat, M.
    Armitage, N. P.
    [J]. 2012 CONFERENCE ON LASERS AND ELECTRO-OPTICS (CLEO), 2012,
  • [8] Terahertz Time-Domain Spectroscopy Characterization of Aged XLPE Cable Insulation
    Zhang, Yuanyuan
    Lian, Ze
    Li, Jianying
    Li, Shengtao
    [J]. PROCEEDINGS OF THE 21ST INTERNATIONAL SYMPOSIUM ON HIGH VOLTAGE ENGINEERING, VOL 1, 2020, 598 : 878 - 886
  • [9] Investigation of polarization and depolarization current measurements for the assessment of oil-paper insulation of aged transformers
    Saha, TK
    Purkait, P
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2004, 11 (01) : 144 - 154
  • [10] Understanding Frequency & Time Domain Polarisation Methods for the Insulation Condition Assessment of Power Transformers
    Saha, T. K.
    Middleton, R.
    Thomas, A.
    [J]. 2009 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, VOLS 1-8, 2009, : 1456 - +