Electromagnetic Field Analysis and Shielding Method of Underground Variable Frequency Power Cable

被引:0
|
作者
Zhang, Jianwei [1 ]
Yang, Zhuojing [1 ]
机构
[1] China Geol Survey, Ctr Hydrogeol & Environm Geol, Baoding 071051, Hebei, Peoples R China
关键词
D O I
10.1155/2022/3271806
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The transmission and radiation of underground variable frequency electromagnetic waves will seriously interfere with the operation of the power cable and its surrounding environment. At present, the test methods for power cables basically require the impedance of the test system to match the characteristic impedance of the cable. The defect is that the process of designing and making the impedance matching impedance network is relatively complex and requires high manufacturing accuracy. In order to solve these problems, this paper puts forward the electromagnetic field fast detection formula and electromagnetic field shielding method of underground variable frequency power cable. The research method of this paper is the principle of shielding electromagnetic field materials and the suppression principle of shielding layer for electromagnetic coupling. The function of the two principles is to study the reflection, absorption, and multiple reflection of electromagnetic waves and to study the cut-off frequency of the nonmagnetic shielding layer. These two principles guide the experiment. In this paper, the measurement formula of the shielding performance of mismatched cables is derived through experiments. The results show that the error of the measurement formula is no more than 8 dB. Then, through the experiment of restraining the interference of magnetic materials on the electromagnetic field, it is concluded that the magnetic field shielding performance can reach 20 dB. Then, through the performance test of electromagnetic field shielding materials, the shielding efficiency of metal fiber antiradiation materials is the largest, and the average efficiency reaches 76.4 dB.
引用
收藏
页数:13
相关论文
共 50 条
  • [1] Magnetic field shielding optimization in underground power cable duct banks
    Carlos del-Pino-Lopez, Juan
    Cruz-Romero, Pedro
    Serrano-Iribarnegaray, Luis
    Martinez-Roman, Javier
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2014, 114 : 21 - 27
  • [2] SCREEN SELECTION FOR THE POWER FREQUENCY MAGNETIC FIELD SHIELDING OF UNDERGROUND POWER CABLES
    Carlos del Pina-López, Juan
    Cruz-Romero, Pedro
    Bachiller-Soler, Alfonso
    [J]. DYNA, 2013, 88 (01): : 105 - 113
  • [3] Dosimetry analysis of the magnetic field of underground power cables and magnetic field mitigation using an electromagnetic shielding technique
    Ates, Kayhan
    Carlak, H. Feza
    Ozen, Sukru
    [J]. INTERNATIONAL JOURNAL OF OCCUPATIONAL SAFETY AND ERGONOMICS, 2022, 28 (03) : 1672 - 1682
  • [4] MAGNETIC FIELD SHIELDING OF UNDERGROUND CABLE DUCT BANKS
    del Pino-Lopez, Juan C.
    Cruz-Romero, Pedro
    [J]. PROGRESS IN ELECTROMAGNETICS RESEARCH-PIER, 2013, 138 : 1 - 19
  • [5] MAGNETIC FIELD SHIELDING OF UNDERGROUND POWER CABLE LINE BY H-SHAPED SHIELD
    Kucheriava, I.M.
    [J]. Technical Electrodynamics, 2020, 2020 (06): : 1 - 3
  • [6] Application of nano material for shielding power-frequency electromagnetic field
    Li, Hualiang
    Li, Li
    Liu, Jiawen
    [J]. 2015 GLOBAL CONFERENCE ON POLYMER AND COMPOSITE MATERIALS (PCM2015), 2015, 87
  • [7] SHIELDING EFFECT OF POWER CABLE SHEATH ON ELECTROMAGNETIC INTERFERENCE
    SAKAI, H
    IDOGAWA, I
    [J]. ELECTRICAL ENGINEERING IN JAPAN, 1966, 86 (12) : 1 - &
  • [8] Shielding techniques of the low-frequency magnetic field from cable power lines
    D'Amore, M
    Menghi, E
    Sarto, MS
    [J]. 2003 IEEE SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY, SYMPOSIUM RECORD, VOLS 1 AND 2, 2003, : 203 - 208
  • [9] Magnetic Field Mitigation Shielding of Underground Power Cables
    Machado, Vitor Malo
    [J]. IEEE TRANSACTIONS ON MAGNETICS, 2012, 48 (02) : 707 - 710
  • [10] Thermal analysis of underground power cable system
    Monika Rerak
    Paweł Ocłoń
    [J]. Journal of Thermal Science, 2017, 26 : 465 - 471