Modeling the dynamic simulation and control of a single effect LiBr-H2O absorption chiller

被引:48
|
作者
Xu, Yu-jie [1 ,2 ,3 ]
Zhang, Shi-jie [1 ,2 ]
Xiao, Yun-han [1 ,2 ]
机构
[1] Chinese Acad Sci, Inst Engn Thermophys, Key Lab Adv Energy & Power, Beijing 100190, Peoples R China
[2] Chinese Acad Sci, Res Ctr Clean Energy & Power, Lianyungang 222069, Jiangsu, Peoples R China
[3] Univ Chinese Acad Sci, Beijing 100049, Peoples R China
基金
中国国家自然科学基金;
关键词
Absorption chiller; Dynamic performance; Control strategy; PERFORMANCE ANALYSIS; FALLING-FILM; HEAT; DESIGN; TEMPERATURE;
D O I
10.1016/j.applthermaleng.2016.06.043
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this study, a dynamic model of a single-effect LiBr-H2O absorption chiller with improved accuracy is built to explore the dynamic performance and the control strategy. Holman correlation is applied to the calculation of heat transfer coefficients of the evaporator, condenser, solution heat exchanger, and generator. The heat and mass transfer in the absorber, chiefly controlled by the mass transfer resistance on the liquid side, are described according to a lumped but accurate physical model based on Nusselt's film theory. The dynamic performance of the absorption chiller is evaluated under the disturbance of the cooling water inlet temperature and heat source temperature. The effect of the thermal mass of the main components on the dynamic performance is explored. Two control strategies are implemented in the model of the absorption chiller: one is setting the chilled water outlet temperature as the manipulated variable, and the other is setting the generator solution temperature as the manipulated variable. The control performances of the two strategies are compared in detail. Results show that either increasing the heat source temperature or decreasing the cooling water inlet temperature increases the risk of crystallization in the dynamic process. The time to reach steady state is highly dependent on the thermal mass of the generator, rather than the thermal masses of the condenser, evaporator, and absorber. The single-effect chiller has better control performance in off-design condition when the generator solution temperature rather than the chilled water outlet temperature is selected as the manipulated variable. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1183 / 1191
页数:9
相关论文
共 50 条
  • [1] Modeling and Active Disturbance Rejection Control of a Single Effect LiBr-H2O Absorption Chiller
    He, Ting
    Li, Donghai
    Wu, Zhenlong
    Xue, Yali
    Yang, Yuxin
    [J]. 2017 11TH ASIAN CONTROL CONFERENCE (ASCC), 2017, : 2726 - 2731
  • [2] Simulation of dynamics and control of a double-effect LiBr-H2O absorption chiller
    Shin, Younggy
    Seo, Jung Ah
    Cho, Hyun Wook
    Nam, Sang Chul
    Jeong, Jin Hee
    [J]. APPLIED THERMAL ENGINEERING, 2009, 29 (13) : 2718 - 2725
  • [3] A DYNAMIC MODEL OF A SINGLE-STAGE LiBr-H2O ABSORPTION CHILLER
    Samutr, Prangtip
    Al Alili, Ali
    [J]. PROCEEDINGS OF THE ASME 10TH INTERNATIONAL CONFERENCE ON ENERGY SUSTAINABILITY, 2016, VOL 1, 2016,
  • [4] Thermodynamic and economic performance of the LiBr-H2O single stage absorption water chiller
    Mroz, Tomasz M.
    [J]. APPLIED THERMAL ENGINEERING, 2006, 26 (17-18) : 2103 - 2109
  • [5] Thermodynamic Modeling and Optimization of Double Effect Series flow LiBr-H2O Vapor Absorption Chiller
    Ghani, Muhammad Usman
    Zaman, Muhammad
    Khan, Imran
    [J]. 2016 INTERNATIONAL CONFERENCE ON EMERGING TECHNOLOGIES (ICET), 2016,
  • [6] Performance Test of a Small Size LiBr-H2O Absorption Chiller
    Prasartkaew, Boonrit
    [J]. 11TH ECO-ENERGY AND MATERIALS SCIENCE AND ENGINEERING (11TH EMSES), 2014, 56 : 487 - 497
  • [7] Solar Driven LiBr-H2O Absorption Chiller Simulation to Analyze Two Backup Options
    Ibrahim, Furugaan
    Chirarattananon, Surapong
    Rakkwamsuk, Pattana
    Chaiwiwatworakul, Pipat
    Chuangchote, Surawut
    Hien, Vu Duc
    [J]. INTERNATIONAL ENERGY JOURNAL, 2021, 21 (03): : 361 - 374
  • [8] Solar driven LiBr-H2O absorption chiller simulation to analyze two backup options
    Ibrahim, Furugaan
    Chirarattananon, Surapong
    Rakkwamsuk, Pattana
    Chaiwiwatworakul, Pipat
    Chuangchote, Surawut
    Hien, Vu Duc
    [J]. International Energy Journal, 2021, 21 (03): : 361 - 374
  • [9] Solution Crystallization Detection for double-effect LiBr-H2O steam absorption chiller
    Gilani, Syed Ihtsham-ul-Haq
    Ahmed, Mojahid Sidahmed Mohammed Salih
    [J]. CLEAN, EFFICIENT AND AFFORDABLE ENERGY FOR A SUSTAINABLE FUTURE, 2015, 75 : 1522 - 1528
  • [10] Dynamic study of a single effect absorption chiller using the pair LiBr/H2O
    Ochoa, A. A. V.
    Dutra, J. C. C.
    Henriquez, J. R. G.
    dos Santos, C. A. C.
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2016, 108 : 30 - 42