Correction of current transformer distorted secondary currents due to saturation using artificial neural networks

被引:83
|
作者
Yu, DC [1 ]
Cummins, JC
Wang, ZD
Yoon, HJ
Kojovic, LA
机构
[1] Univ Wisconsin, Dept Elect Engn & Comp Sci, Milwaukee, WI 53201 USA
[2] Cooper Power Syst, Syst Engn, Franksville, WI USA
关键词
artificial neural networks; current transformers; protective equipment; saturation;
D O I
10.1109/61.915481
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Current transformer saturation can cause protective relay misoperation or even prevent tripping, This paper presents the use of artificial neural networks (ANN) to correct current transformer (CT) secondary waveform distortions. The ANN is trained to achieve the inverse transfer function of iron-core toroidal CTs which are widely used in protective systems. The ANN provides a good estimate of the true (primary) current of a saturated transformer. The neural network is developed using MATLAB (R) and trained using data from EMTP simulations and data generated from actual CTs, In order to handle large dynamic ranges of fault currents, a technique of employing two sets of network coefficients is used. Different sets of network coefficients deal with different fault current ranges, The algorithm for running the network was implemented on an Analog De,ices ADSP-2101 digital signal processor. The calculating speed and accuracy proved to be satisfactory in real-time application.
引用
收藏
页码:189 / 194
页数:6
相关论文
共 50 条
  • [1] A Proposal for Detection and Correction of Current Transformer Distorted Secondary Currents Due to Saturation Using Artificial Neural Networks
    Severo, Luana Barcelos
    dos Santos, Eduardo Machado
    da Silva, Chrystian Dalla Lana
    Kilian, Eduardo Davila
    Schons, Fabio Kaspary
    de Oliveira, Fabiano Aguiar
    [J]. 2022 IEEE PES GENERATION, TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION - LATIN AMERICA, IEEE PES GTD LATIN AMERICA, 2022,
  • [2] Correction of capacitive voltage transformer distorted secondary voltages using artificial neural networks
    Khorashadi-Zadeh, H
    [J]. NEUREL 2004: SEVENTH SEMINAR ON NEURAL NETWORK APPLICATIONS IN ELECTRICAL ENGINEERING, PROCEEDINGS, 2004, : 131 - 134
  • [3] Compensation of Distorted Secondary Current Caused by Saturation and Remanence in a Current Transformer
    Hong, Ying-Yi
    Wei, Da-Wei
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (01) : 47 - 54
  • [4] Detection and correction of distorted current transformer current using wavelet transform and artificial intelligence
    Hong, Y. -Y.
    Chang-Chian, P. -C.
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2008, 2 (04) : 566 - 575
  • [5] Neural network for current transformer saturation correction
    Yu, DC
    Cummins, JC
    Kojovic, LA
    Stone, D
    Wang, ZD
    Yoon, HJ
    [J]. 1999 IEEE TRANSMISSION AND DISTRIBUTION CONFERENCE, VOLS 1 & 2, 1999, : 441 - 446
  • [6] Detection and correction of current transformer saturation effects in secondary current signals
    Stachel, Philipp
    Schegner, Peter
    [J]. 2009 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, VOLS 1-8, 2009, : 1369 - 1374
  • [7] Simplified artificial neural network structure with the current transformer saturation detector provides a good estimate of primary currents
    Cummins, JC
    Yu, DC
    Kojovic, LA
    [J]. 2000 IEEE POWER ENGINEERING SOCIETY SUMMER MEETING, CONFERENCE PROCEEDINGS, VOLS 1-4, 2000, : 1373 - 1378
  • [8] Current-transformer saturation detection with genetically optimized neural networks
    Rebizant, Waldemar
    Bejmert, Daniel
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (02) : 820 - 827
  • [10] Method of current transformer metrological properties estimation for transformation of distorted currents
    Kaczmarek, Michal
    [J]. PROCEEDINGS OF THE 2012 IEEE INTERNATIONAL POWER MODULATOR AND HIGH VOLTAGE CONFERENCE, 2012, : 724 - 726