Study on temperature distribution in oil-immersed inverted current transformer

被引:0
|
作者
Yang, Xiaoping [1 ]
Wu, Yiming [2 ]
Li, Jiansheng [2 ]
Wei, Chao [2 ]
Wang, Shengquan [2 ]
Huang, Leifeng [3 ]
Li, Bonan [3 ]
Wang, Youyuan [3 ]
机构
[1] Jiangsu Elect Power Co, Nanjing, Jiangsu, Peoples R China
[2] Jiangsu Elect Power Co, Res Inst, Nanjing, Jiangsu, Peoples R China
[3] Chongqing Univ, Sch Elect Engn, Chongqing, Peoples R China
关键词
Oil-immersed inverted current transformer; Temperature distribution; insulating oil;
D O I
10.1109/icdl.2019.8796597
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Oil-immersed inverted current transformer, as an important electrical equipment in power grid, is mainly used in power plants and substations. Accidents caused by oil-immersed inverted current transformers are generally accompanied by explosions, which not only reduce the amount of electricity delivered, but also damage other nearby equipment in the substation and even cause casualties. Therefore, it is very necessary to detect and evaluate the operation status of oil-immersed inverted current transformer and study the fault prevention technology to reduce the probability of accidents. According to the common faults of oil-immersed inverted current transformer, this paper firstly analyzed the parts and components with high fault rate of current transformer. Combined with the operating condition of current transformer and its internal insulation structure, the internal temperature field simulation model of current transformer and the temperature calculation model of key parts were established. It was found that the temperature near the winding of the oil-immersed inverted current transformer was the highest, while the temperature rise at the lower part far from the heat source was very small. The simulation results were basically consistent with the experimental results, and it was found that the temperature distribution on both sides of the primary conductor in the head region of the current transformer was symmetrical.
引用
收藏
页数:4
相关论文
共 50 条
  • [1] Thermal Modeling of an Inverted-Type Oil-Immersed Current Transformer
    Mahajan, Satish M.
    Robalino, Diego M.
    Sivan, Vinod
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) : 2511 - 2518
  • [2] An analysis of temperature and pressure on loading oil-immersed distribution transformer
    Suechoey, B.
    Tadsuan, S.
    Thammarat, C.
    Leelajindakrairerk, M.
    [J]. IPEC: 2005 International Power Engineering Conference, Vols 1 and 2, 2005, : 634 - 638
  • [3] Study on Gas Diffusion Distribution Law of Inverted Oil Immersed Current Transformer
    Li, Bonan
    Wang, Youyuan
    Gu, Hongrui
    [J]. PROCEEDINGS OF THE 2020 3RD IEEE INTERNATIONAL CONFERENCE ON DIELECTRICS (ICD 2020), 2020, : 724 - 727
  • [4] Effect of loads on temperature distribution characteristics of oil-immersed transformer winding
    Zhao Z.
    Jiang Z.
    Li Y.
    Li C.
    Zhang D.
    [J]. Distributed Generation and Alternative Energy Journal, 2022, 37 (02): : 237 - 254
  • [5] Research on hydrogen diffusion characteristics under typical defects of inverted oil-immersed current transformer
    Xiong, Tianyu
    Wang, Youyuan
    Wu, Peng
    Li, Xiaohan
    Li, Jiansheng
    Li, Bonan
    [J]. ENERGY REPORTS, 2022, 8 : 467 - 474
  • [6] A Probabilistic Approach for Dynamic Oil-Immersed Transformer Rating Accounting for Current and Temperature Limits
    Bracale, Antonio
    Caramia, Pierluigi
    Carpinelli, Guido
    De Falco, Pasquale
    Russo, Angela
    [J]. 2022 17TH INTERNATIONAL CONFERENCE ON PROBABILISTIC METHODS APPLIED TO POWER SYSTEMS (PMAPS), 2022,
  • [7] Numerical study on temperature rise and mechanical properties of winding in oil-immersed transformer
    Jia, Xiaoyu
    Lin, Mei
    Su, Shiwei
    Wang, Qiuwang
    Yang, Jian
    [J]. ENERGY, 2022, 239
  • [8] Design of Intelligent Monitoring System for Oil-immersed Distribution Transformer
    Sun, Jin
    Fan, Jialong
    Ji, Yingdong
    Wang, Yongxing
    Shi, Zhentang
    Liu, Weigong
    [J]. 2020 5TH INTERNATIONAL CONFERENCE ON MECHANICAL, CONTROL AND COMPUTER ENGINEERING (ICMCCE 2020), 2020, : 802 - 805
  • [9] Study on the deformation of the oil-immersed transformer tank by FEA
    Zhang, Jianhua
    Sun, Lingyu
    Zhang, Xiaojun
    Li, Jiapeng
    [J]. EQUIPMENT MANUFACTURING TECHNOLOGY, 2012, 422 : 51 - +
  • [10] Research on Overload Capability of Oil-immersed Distribution Transformer Based on Hot Spot Temperature Model
    Wang, Haifei
    Xue, Manyu
    Wang, Tingkang
    Hou, Yuning
    Chen, Jianchun
    Sun, Jianming
    [J]. 2019 22ND INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS (ICEMS 2019), 2019, : 4478 - 4482