Experimental study of the separation performance of a novel sewage hydrocyclone used in sewage source heat pump

被引:31
|
作者
Ni, Long [1 ]
Tian, Jinyi [1 ]
Shen, Chao [1 ]
Zhao, Jianing [1 ]
机构
[1] Harbin Inst Technol, Sch Municipal & Environm Engn, Harbin 150090, Peoples R China
关键词
Sewage source heat pump; Hydrocyclone; Feed flow rate; Separation efficiency; Foulant; WASTE-WATER; FEED CONCENTRATION; ENHANCED TUBES; FLOW; SYSTEMS; VELOCITY; FIELD; IMPLEMENTATION; BUILDINGS; PARTICLES;
D O I
10.1016/j.applthermaleng.2016.06.093
中图分类号
O414.1 [热力学];
学科分类号
摘要
Sewage source heat pump has the remarkable benefit of energy-saving and is favorable for environment protect. However, one of the main challenges in its application is the blockage issue of heat exchanger triggered by the foulant. The untreated urban sewage contains high-concentration foulant (<4 mm) which is overwhelmingly arduous to be filtered out by the traditional mechanical filtration device. A novel sewage hydrocyclone with reflux function is proposed in this paper with the target of removing the foulant from sewage continuously and in result solving this blockage problem. In order to investigate the performance of this novel device, an experimental set-up was built and a series of research was conducted based on three kinds of sewage: the sand water, high-concentration sewage, and low-concentration sewage. The effects of feed flow rate, feed foulant concentration and feed foulant density on the separation performance were investigated respectively. The experimental results manifested the novel sewage hydrocyclone had an effective separation efficiency of 99.53-99.94% for the sand water, 91-95% for the high-concentration sewage, and 56-72% for low-concentration sewage. The split ratio stayed below 10%. Meanwhile; the pressure drop through the unit kept below 30 kPa. The test data in this study demonstrated clearly that the novel sewage hydrocyclone had a high efficiency to separate foulant (<4 mm) from the sewage continuously so as to prevent the blockage of sewage heat exchanger in the application of heat pump system. Results also can be taken as references for the heat pump designers. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1300 / 1310
页数:11
相关论文
共 50 条
  • [1] Experimental study on performance of a de-foulant hydrocyclone with different reflux devices for sewage source heat pump
    Song, Tao
    Tian, Jinyi
    Ni, Long
    Shen, Chao
    Yao, Yang
    [J]. APPLIED THERMAL ENGINEERING, 2019, 149 : 354 - 365
  • [2] Experimental Study on New Sewage Source Heat Pump Unit
    Wang, Zhiyi
    Li, Jianjiun
    Pan, Zudong
    [J]. ENERGY ENGINEERING AND ENVIRONMENTAL ENGINEERING, PTS 1AND 2, 2013, 316-317 : 49 - +
  • [3] Experimental study on viscosity characteristic of sewage in urban untreated sewage source heat pump system
    吴学慧
    张承虎
    赵明明
    孙德兴
    [J]. Journal of Harbin Institute of Technology(New series), 2010, (01) : 82 - 84
  • [4] PERFORMANCE STUDY OF THE ENGINEERING PRACTICE OF URBAN SEWAGE SOURCE HEAT PUMP SYSTEM
    Fu, L.
    Zhao, X. L.
    Zhu, J. Z.
    Huang, B. M.
    He, T.
    Jiang, Y.
    [J]. ES2009: PROCEEDINGS OF THE ASME 3RD INTERNATIONAL CONFERENCE ON ENERGY SUSTAINABILITY, VOL 1, 2009, : 437 - 443
  • [5] Study on sewage-source heat pump system using in the process of sewage treatment
    Song, Yan
    Yao, Yang
    Na, Wei
    [J]. Journal of Harbin Institute of Technology (New Series), 2007, 14 (SUPPL.) : 385 - 388
  • [6] Performance study and engineering practice of urban original sewage source heat pump system
    Zhao, Xiling
    Fu, Lin
    Zhang, Shigang
    Lai, Zhonglian
    [J]. Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2010, 31 (11): : 1458 - 1463
  • [7] Experimental test on heating performance of backwash falling film sewage source heat pump unit
    Zhang, Qunli
    Yang, Yixiong
    Zhang, Xinchao
    Liu, Fang
    [J]. Huagong Jinzhan/Chemical Industry and Engineering Progress, 2022, 41 (05): : 2698 - 2705
  • [8] Progress of the intaking, defouling and heat transfer in sewage water side of the sewage water source heat pump system Part II: Research on urban sewage source heat pump in China
    Zhang, Jili
    Ma, Liangdong
    Liang, Ruobing
    Zhao, Tianyi
    Ma, Zhixian
    [J]. FIRST INTERNATIONAL CONFERENCE ON BUILDING ENERGY AND ENVIRONMENT, PROCEEDINGS VOLS 1-3, 2008, : 1624 - 1631
  • [9] Study on the Growth Characteristics of Fouling in Sewage Source Heat Pump Systems
    Qu, Yun-xia
    Feng, Yuan
    Liu, Huan
    [J]. SUSTAINABLE DEVELOPMENT OF URBAN ENVIRONMENT AND BUILDING MATERIAL, PTS 1-4, 2012, 374-377 : 86 - 89
  • [10] Analysis of Fouling in Sewage Source Heat Pump Heat Exchanger
    Zhang, Xu
    Zhang, Lingzhe
    [J]. PROCEEDINGS OF THE 5TH INTERNATIONAL CONFERENCE ON CIVIL ENGINEERING AND TRANSPORTATION 2015, 2016, 30 : 804 - 808