Energy and exergy analysis of a geothermal heat pump air conditioning system

被引:29
|
作者
Baccoli, Roberto [1 ]
Mastino, Costantino [1 ]
Rodriguez, Giuseppe [2 ]
机构
[1] Univ Cagliari, Inst Tech Phys, I-09123 Cagliari, Italy
[2] Univ Cagliari, Dept Math & Comp Sci, I-09123 Cagliari, Italy
关键词
Geothermal heat pump; Energy analysis; Exergy analysis; Laplace transform; GROUTING MATERIALS; BOREHOLE; PERFORMANCE; EXCHANGERS; OPERATION; TEMPERATURE; EXTRACTION; SIMULATION;
D O I
10.1016/j.applthermaleng.2015.03.046
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper considers the energy analysis of a heat pump system coupled to the ground by means of vertical exchangers, to verify which thermodynamic boundary conditions, in terms of thermal conductivity and diffusivity of the ground and the grout, make it competitive in comparison with other technologies harnessing atmospheric air as the heat source. The comparison is based on the maximum theoretical efficiency available in correspondence to the temperature effectively assumed by the thermal energy reservoirs in contact with the evaporator and the condenser during the operating conditions. The comparison of the two sources/sinks of heat, i.e. the ground and atmospheric air, represents the comparison between the time trend of the exergy of the two reservoirs required by an ideal GSHP and ASHP respectively. A fully transient heat transfer model able to handle on a time scale of a year or more and with a refinement of less than an hour is considered, since short term variations have significant effects on the overall performance of GSHP. In this paper the borehole heat transfer problem in the Laplace domain is solved for any trend and duration of thermal loads, taking into account an existing analytical approximation model of the full solution proposed by Lamarche and Beauchamp. A numerical inversion using the Inverse Discrete Fourier Transform is then applied to obtain the time domain solution. The method combines the flexibility and accuracy of the analytical model with the superior efficiency of the computational time offered by the numerical inversion if compared with that of methods based on the convolution scheme. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:333 / 347
页数:15
相关论文
共 50 条
  • [1] Energy and exergy analysis of a ground source (geothermal) heat pump system
    Hepbasli, A
    Akdemir, O
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2004, 45 (05) : 737 - 753
  • [2] Modeling of an Air Conditioning System with Geothermal Heat Pump for a Residential Building
    Cocchi, Silvia
    Castellucci, Sonia
    Tucci, Andrea
    [J]. MATHEMATICAL PROBLEMS IN ENGINEERING, 2013, 2013
  • [3] Exergy Analysis of Electric Vehicle Heat Pump Air Conditioning System with Battery Thermal Management System
    Zhang Kexin
    Li Ming
    Yang Changhai
    Shao Zhiyuan
    Wang Lihong
    [J]. JOURNAL OF THERMAL SCIENCE, 2020, 29 (02) : 408 - 422
  • [4] Exergy Analysis of Electric Vehicle Heat Pump Air Conditioning System with Battery Thermal Management System
    ZHANG Kexin
    LI Ming
    YANG Changhai
    SHAO Zhiyuan
    WANG Lihong
    [J]. Journal of Thermal Science, 2020, 29 (02) : 408 - 422
  • [5] Exergy Analysis of Electric Vehicle Heat Pump Air Conditioning System with Battery Thermal Management System
    Kexin Zhang
    Ming Li
    Changhai Yang
    Zhiyuan Shao
    Lihong Wang
    [J]. Journal of Thermal Science, 2020, 29 : 408 - 422
  • [6] ANALYSIS OF SOIL TEMPERATURE DISTRIBUTIONS IN A GEOTHERMAL HEAT-PUMP AIR-CONDITIONING SYSTEM
    Endoh, Noboru
    Sasaki, Masafumi
    Tsuchiya, Takayuki
    Satoh, Kenji
    [J]. PROCEEDINGS OF THE INTERNATIONAL CONFERENCE ON POWER ENGINEERING 2009 (ICOPE-09), VOL 3, 2009, : 179 - 183
  • [7] Energy and exergy analysis of an Automobile Heat Pump system
    Direk, Mehmet
    Hosoz, Murat
    [J]. INTERNATIONAL JOURNAL OF EXERGY, 2008, 5 (5-6) : 556 - 566
  • [8] Energy and exergy analysis of thermoelectric heat pump system
    Kaushik, S. C.
    Manikandan, S.
    Hans, Ranjana
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2015, 86 : 843 - 852
  • [9] Heating Performance Characteristics of an Electric Vehicle Heat Pump Air Conditioning System Based on Exergy Analysis
    Tang, Xingwang
    Guo, Qin
    Li, Ming
    Jiang, Mingzhe
    [J]. ENERGIES, 2020, 13 (11)
  • [10] Exergy Analysis of Energy Consumption for Central Air Conditioning System
    Xia, Xiaoxia
    Zhou, Naijun
    Wang, Zhiqi
    [J]. MATERIALS SCIENCE, MECHANICAL ENGINEERING AND APPLIED RESEARCH, 2014, 628 : 332 - 337