Model-based commissioning for filters in room air-conditioners

被引:3
|
作者
Wang, FL [1 ]
Yoshida, H
Kitagawa, H
Matsumoto, K
Goto, K
机构
[1] Kyoto Univ, Dept Urban & Environm Engn, Sakyo Ku, Kyoto 6068501, Japan
[2] YANMAR Co Ltd, Res & Dev Ctr, Elect Dev Ctr, Shiga, Japan
关键词
automated commissioning; filter resistance; modeling; room air-conditioner;
D O I
10.1016/j.enbuild.2005.01.004
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper proposes a model that can estimate filter resistance using estimated air-conditioner indoor unit air flow rate, which is tightly related to filter fouling conditions. Two sorts of value are used as inputs to estimate air flow rate. One is the power consumed by the fan in the indoor unit of a room air-conditioner and the other is the thermal performance of a room air-conditioner. For the room air-conditioners that the real-time indoor unit fan power consumption is available, fan power consumptions are used as inputs to estimate filter resistance. For the room air-conditioners that are equipped with refrigerant pressure and temperature sensors, this model estimates filter resistance using refrigerant pressure and temperature, air temperature or enthalpy difference between supply and indoor air. This model was validated using a really running multi-evaporator Gas-engine Heat Pump (GHP) system. The maximum and average difference between estimated and measured filter resistance are 12.72% and 5.89% when using the fan power consumption as inputs. When using the air-conditioner thermal performance data, the maximum and average estimation errors are 13.12% and 5.96%. The validation results show that this model is accurate enough for estimating filter resistance. Based on this model, the method for commissioning filters in air-conditioner is discussed. This method is useful for automatically estimating filter resistance and reminding users timely to clean or replace a filter to prevent wasting energy and to maintain desirable indoor environment. (c) 2005 Elsevier B.V. All rights reserved.
引用
收藏
页码:1225 / 1233
页数:9
相关论文
共 50 条
  • [1] A NEW CONTROL FOR ROOM AIR-CONDITIONERS
    ALLEN, JB
    HANCOCK, JT
    [J]. IEEE TRANSACTIONS ON INDUSTRY AND GENERAL APPLICATIONS, 1968, IGA4 (06): : 625 - &
  • [2] Experiments for actual performance evaluation of room air-conditioners in an experimental house: Research on performance evaluation of room air-conditioners part 1
    Sumiyoshi, Daisuke
    Ogino, Takashi
    Miura, Hisashi
    Hosoi, Akinori
    Sawachi, Takao
    [J]. Journal of Environmental Engineering (Japan), 2013, 78 (688): : 497 - 505
  • [3] Future environmental impacts of room air-conditioners in Europe
    Pout, C.
    Hitchin, E. R.
    [J]. BUILDING RESEARCH AND INFORMATION, 2009, 37 (04): : 358 - 368
  • [4] TECHNOLOGY OF ROOM AIR-CONDITIONERS - MARKET POSSIBILITIES IN 1979
    不详
    [J]. KALTE UND KLIMATECHNIK, 1979, 32 (05): : 269 - 270
  • [5] OPERATION AND SERVICE OF AIR-CONDITIONERS WITH SPECIAL EMPHASIS ON AIR-FILTERS
    BOTZENHART, K
    RUDEN, H
    [J]. SOZIAL-UND PRAVENTIVMEDIZIN, 1974, 19 (5-6): : 343 - 349
  • [6] CONSERVED ENERGY FROM ROOM AIR-CONDITIONERS FOR WATER HEATING
    MONERASINGHE, NJ
    RATNALINGAM, R
    LEE, BS
    [J]. ENERGY CONVERSION AND MANAGEMENT, 1982, 22 (02) : 171 - 173
  • [7] Comparative investigation of thermoelectric air-conditioners versus vapour compression and absorption air-conditioners
    Riffat, SB
    Qiu, GQ
    [J]. APPLIED THERMAL ENGINEERING, 2004, 24 (14-15) : 1979 - 1993
  • [8] MOLDS IN AUTOMOBILE AIR-CONDITIONERS
    KUMAR, P
    MARIER, R
    LOPEZ, M
    FAN, W
    SIAK, J
    LEECH, SH
    [J]. ANNALS OF ALLERGY, 1987, 58 (04): : 280 - 280
  • [9] Performance metrics for room air-conditioners: energy, comfort and environmental impacts
    Jain, Nidhi Rai
    Rawal, Rajan
    Vardhan, Vishnu
    Dey, Shubhashis
    [J]. BUILDINGS & CITIES, 2021, 2 (01): : 666 - 687
  • [10] The electricity savings by using probabilistic neural network for room air-conditioners
    Chen, SL
    Tsay, MT
    [J]. TENCON 2004 - 2004 IEEE REGION 10 CONFERENCE, VOLS A-D, PROCEEDINGS: ANALOG AND DIGITAL TECHNIQUES IN ELECTRICAL ENGINEERING, 2004, : C516 - C519