On-line Voltage Stability Monitoring and Control (VSMC) system in Fujian power grid

被引:0
|
作者
Zhao, Jinquan [1 ]
Huang, Wenying [2 ]
Fang, Zhaoxiong [2 ]
Chen, Feng [2 ]
Li, Kewen [2 ]
Deng, Yong [2 ]
机构
[1] Hohai Univ, Dept Elect Engn, Nanjing 210098, Peoples R China
[2] Fujian Power Co, Fuzhou 350000, Peoples R China
关键词
voltage stability assessment; stability margin monitoring; preventive control; sensitivity; successive linear programming;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The main functions and implementations of Fujian on-fine Voltage Stability Monitoring & Control (VSMC) system is presented in this paper. The salient feature of VSMC is that the on-line voltage stability close-loop control is realized partly by interfacing with the existing Automatic Voltage Control (AVC) system. Within the scan period of 5 minutes, the load margins of current operational state and about 260 credible contingencies are computed at totally 10 different predefined load directions. Once the unstable or severe contingencies are identified, the preventive control module is activated to produce the preventive control actions and the new voltage lower limits of all pivot buses are given to AVC system. A sensitivity-based successive linear programming method is used to obtain the control solution robustly. Fujian on-line VSMC system helps operators to monitor the voltage stability margins and automatically take actions to mitigate the voltage collapses.
引用
收藏
页码:3127 / 3132
页数:6
相关论文
共 50 条
  • [1] Real-time dynamic equivalence of East China power grid for on-line stability control system of Fujian power system
    Zhao, Yong
    Su, Yi
    Chen, Feng
    Teng, Lin
    Bi, Zhao-Dong
    Zhang, Jian-Ping
    Sun, Guang-Hui
    [J]. Power System Technology, 2005, 29 (04) : 18 - 22
  • [2] On-line Voltage Stability Monitoring and Control in Smart Grid- A Survey
    Sahu, Pankaj
    Verma, M. K.
    [J]. 2015 IEEE UP SECTION CONFERENCE ON ELECTRICAL COMPUTER AND ELECTRONICS (UPCON), 2015,
  • [3] Preventive control method of electric power system based on on-line voltage stability monitoring index
    College of Electrical and Information Engineering, Hunan University, Changsha
    Hunan Province
    410082, China
    [J]. Zhongguo Dianji Gongcheng Xuebao, 18 (4598-4606):
  • [4] On-Line Voltage Stability Monitoring of Large Power Systems
    Chiang, Hsiao-Dong
    Li, Hua
    Tong, Jianzhong
    Causgrove, Patrick
    [J]. 2011 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING, 2011,
  • [5] On-line voltage stability monitoring for electric power system Part 1: On-line voltage stability index considering load static characteristics
    [J]. Fu, X. (fuxu@mailst.xjtu.edu.cn), 2005, Electric Power Automation Equipment, 38 New Mofan Malu, Nanjing, 210003, China (25):
  • [6] On-Line Voltage Stability Monitoring
    Vournas, Costas
    Mandoulidis, Panagiotis
    [J]. 2018 IEEE INTERNATIONAL SYMPOSIUM ON CIRCUITS AND SYSTEMS (ISCAS), 2018,
  • [7] On-line voltage stability monitoring
    de Souza, AC
    de Souza, JC
    da Silva, AM
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2000, 15 (04) : 1300 - 1305
  • [8] AVC System Based on On-line Voltage Stability Monitoring System
    Ding Xiaoqun
    Zhou Ling
    Liu Hongliang
    [J]. 2008 PROCEEDINGS OF THE 43RD INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE, VOLS 1-3, 2008, : 70 - 74
  • [9] Development and on-line application of voltage control and security assessment system for Guangdong power grid
    School of Electric Power, South China University of Technology, Guangzhou 510640, Guangdong Province, China
    不详
    [J]. Lin, S. (linshj@scut.edu.cn), 1600, Power System Technology Press (37):
  • [10] Upgrade of Fujian grid on-Line Stability Control System for the Transformer Operating of 500kV Ningde Substation
    Wang Yunmao
    Su Yi
    Huang Jianhong
    [J]. 2009 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), VOLS 1-7, 2009, : 1387 - +