Design and performance of a constant temperature and humidity air-conditioning system driven by ground source heat pumps in winter

被引:26
|
作者
Yu, X. [1 ]
Zhai, X. Q. [1 ]
Wang, R. Z. [1 ]
机构
[1] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, Shanghai 200240, Peoples R China
关键词
Ground source heat pump; Constant temperature and humidity system; Performance analysis; Archives house; ENERGY;
D O I
10.1016/j.enconman.2010.03.009
中图分类号
O414.1 [热力学];
学科分类号
摘要
A constant temperature and humidity air-conditioning system driven by ground source heat pumps was designed and constructed in an archives building in Shanghai, China. The system consists of two water-to-water heat pumps and 280 boreholes with 80 m in depth. In order to keep the temperature and humidity constant, the operation mode that one heat pump ran in heating mode and the other one ran in cooling mode was deployed. According to the experimental results under typical winter weather condition of Shanghai, the average COP of the heat pump in heating mode was 5.2. The average temperature and relative humidity of the archives house were 22.8 degrees C and 52.5%, respectively. It was found that the operation mode we deployed could reduce the heat absorbed from the soil by 20%. Theoretical analysis showed that it was helpful for the earth energy conservation with one heat pump operated in cooling mode in winter. It was also shown that the decrease range of temperature of the soil in the middle of two boreholes would reduce with the increase of the distance between two boreholes. The distance between two boreholes is suggested to be 4-5 m in Shanghai. (C) 2010 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2162 / 2168
页数:7
相关论文
共 50 条
  • [1] Year round experimental study on a constant temperature and humidity air-conditioning system driven by ground source heat pump
    Yu, X.
    Wang, R. Z.
    Zhai, X. Q.
    [J]. ENERGY, 2011, 36 (02) : 1309 - 1318
  • [2] In situ performance of independent humidity control air-conditioning system driven by heat pumps
    Zhu, Weifeng
    Li, Zhongjian
    Liu, Sheng
    Liu, Shuanqiang
    Jiang, Yi
    [J]. ENERGY AND BUILDINGS, 2010, 42 (10) : 1747 - 1752
  • [3] Control System Design in Constant-Temperature and Constant-Humidity Air-Conditioning System
    Wang Jiangjiang
    Jing Youyin
    Zhang Chunfa
    Shi Guohua
    [J]. PROCEEDINGS OF THE 27TH CHINESE CONTROL CONFERENCE, VOL 4, 2008, : 632 - 636
  • [4] The Application of Temperature & Humidity Independent Control Air-conditioning System based on the Ground Source Heat Pump
    Liu, Jianlong
    Xia, Xiaoqian
    Wang, Hanqing
    Liu, Peng
    [J]. SENSORS, MECHATRONICS AND AUTOMATION, 2014, 511-512 : 1053 - 1057
  • [5] Performance study of a constant temperature and humidity air-conditioning system with temperature and humidity independent control device
    Zhang, X. J.
    Xiao, F.
    Li, S.
    [J]. ENERGY AND BUILDINGS, 2012, 49 : 640 - 646
  • [6] Air-conditioning of a typical house in moderate climates with Ground Source Heat Pumps and cost comparison with Air Source Heat Pumps
    Christodoulides, Paul
    Aresti, Lazaros
    Florides, Georgios
    [J]. APPLIED THERMAL ENGINEERING, 2019, 158
  • [7] A Study on Fuzzy Control Technology of Constant Temperature and Constant Humidity Air-Conditioning System
    Kan, Ankang
    Han, Houde
    Ji, Jun
    Liu, Houmin
    [J]. 6TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS I-III, PROCEEDINGS, 2009, : 278 - 285
  • [8] Fuzzy PID Controller Design of Air Handling Unit for Constant Temperature and Humidity Air-conditioning
    Liu, Shuai
    Wang, Xiangdong
    Li, Shujiang
    [J]. 2016 8TH INTERNATIONAL CONFERENCE ON INTELLIGENT HUMAN-MACHINE SYSTEMS AND CYBERNETICS (IHMSC), VOL. 2, 2016, : 410 - 414
  • [9] Air-conditioning system and control design for advanced ceramics workshop of constant temperature and humidity with high precision
    Wu, XZ
    Li, ML
    [J]. ENERGY CONVERSION AND APPLICATION, VOL I AND II, 2001, : 1022 - 1025
  • [10] Temperature and Humidity Independent Control Research on Ground Source Heat Pump Air Conditioning System
    Chen, G.
    Wang, L. L.
    [J]. PROCEEDINGS OF THE 2015 INTERNATIONAL CONFERENCE ON MECHANICAL ENGINEERING AND CONTROL SYSTEMS (MECS2015), 2016, : 214 - 217