Metal oxide surge arrester condition monitoring based on analysis of leakage current components

被引:40
|
作者
Khodsuz, Masume [1 ]
Mirzaie, Mohammad [1 ]
Seyyedbarzegar, Seyyedmeysam [1 ]
机构
[1] Bobo Noshirvani Univ Technol, Fac Elect & Comp Engn, Babol Sar, Iran
关键词
Metal oxide surge arrester; Condition monitoring; Indicator; Leakage current;
D O I
10.1016/j.ijepes.2014.10.052
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents proper indicators for evaluation of the surge arrester condition based on the leakage current analysis. Maximum amplitude of fundamental harmonic of the resistive leakage current (I-mr1), maximum amplitude of third harmonic of the resistive leakage current (I-mr3) and maximum amplitude of fundamental harmonic of the capacitive leakage current have been used as indicators for surge arrester condition monitoring. The effects of operating voltage fluctuation, third order of voltage harmonic, over-voltage and varistor aging have been investigated to show the ability of introduced indicators for accurate diagnostic of arrester's conditions. In order to have accurate values of stray capacitors, 3D-FEM has been used. Moreover, surge arrester model for calculating leakage current has been performed in ATP-EMTP. In addition, the signal processing has been done using MATLAB software. This study shows that the introduced indicators are proper criteria for surge arrester condition monitoring. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:188 / 193
页数:6
相关论文
共 50 条
  • [1] New criteria for metal oxide surge arrester condition monitoring based on leakage current analysis: Considering non-uniform pollution effect
    Khodsuz, Masume
    Teymourian, Mohammad Hossein
    Seyyedbarzegar, Seyyedmeysam
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2024, 18 (05) : 1072 - 1089
  • [2] Metal-Oxide Surge Arrester's Leakage Current Analysis and Thermography
    Ursine, Wagner A. M.
    Silvino, Jose L.
    Fonseca, Leonardo G.
    de Andrade, Roberto M.
    [J]. 2013 INTERNATIONAL SYMPOSIUM ON LIGHTNING PROTECTION (XII SIPDA), 2013, : 297 - 303
  • [3] A novel technique for condition monitoring of metal oxide surge arrester based on fifth harmonic resistive current
    Munir, Abdullah
    Abdul-Malek, Zulkurnain
    Sultana, Umbrin
    Arshad, Rai Naveed
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2022, 202
  • [4] Condition Monitoring of Metal-oxide Surge Arresters using Leakage Current Signal Analysis
    Doorsamy, W.
    Bokoro, P.
    [J]. 2018 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2018,
  • [5] Study on The Effect of Moisture Ingression into Metal Oxide Surge Arrester Using Leakage Current Analysis
    Das, Sayantan
    Ghosh, Riddhi
    Dalai, Sovan
    Chatterjee, Biswendu
    [J]. 2017 3RD INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS (CATCON), 2017, : 330 - 334
  • [6] Effect of Ambient Temperature on Leakage Current of Gapless Metal Oxide Surge Arrester
    Wooi, C. L.
    Abdul-Malek, Zulkurnain
    Mashak, Saeed Vahabi
    [J]. JURNAL TEKNOLOGI, 2013, 64 (04):
  • [7] Fuzzy expert system for metal-oxide surge arrester condition monitoring
    Goran Dobrić
    Mileta Žarković
    [J]. Electrical Engineering, 2021, 103 : 91 - 101
  • [8] Fuzzy expert system for metal-oxide surge arrester condition monitoring
    Dobric, Goran
    Zarkovic, Mileta
    [J]. ELECTRICAL ENGINEERING, 2021, 103 (01) : 91 - 101
  • [9] Measurement Method for Resistive Current Components of Metal Oxide Surge Arrester in Service
    Fu, Zhongjun
    Wang, Jianyu
    Bretas, Arturo
    Ou, Yun
    Zhou, Genyuan
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (05) : 2246 - 2253
  • [10] Resistive component extraction of leakage current in metal oxide surge arrester: A hybrid method
    Munir, Abdullah
    Abdul-Malek, Zulkurnain
    Arshad, Rai Naveed
    [J]. MEASUREMENT, 2021, 173