A Decision Tree-Based Method for Fault Classification in Double-Circuit Transmission Lines

被引:51
|
作者
Jamehbozorg, A. [1 ]
Shahrtash, S. M. [2 ]
机构
[1] Tennessee Technol Univ, Cookeville, TN 38501 USA
[2] Iran Univ Sci & Technol, Dept Elect Engn, Ctr Excellence Power Syst Automat & Operat, Tehran, Iran
关键词
Decision tree; double-circuit transmission line; fault classification; PROTECTION; SCHEME;
D O I
10.1109/TPWRD.2010.2050911
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper, a novel method for fault classification of double-circuit transmission lines is presented. The proposed method needs voltages and currents of only one side of the protected line. After detecting the exact time of fault inception and calculating the odd harmonics of the measured signals, up to the nineteenth, a decision tree algorithm has been employed for recognition of the intercircuit fault type. Also, the proposed method is extended for classification of crossover faults in these transmission lines. Simulation results have shown that the proposed method can classify the faults in less than a quarter of a cycle with the highest possible accuracy.
引用
收藏
页码:2184 / 2189
页数:6
相关论文
共 50 条
  • [1] A decision tree based method for fault classification in transmission lines
    Shahrtash, S. M.
    Jamehbozorg, A.
    [J]. 2008 IEEE/PES TRANSMISSION & DISTRIBUTION CONFERENCE & EXPOSITION, VOLS 1-3, 2008, : 1039 - 1043
  • [2] Counterpropagation network based fault classification for double-circuit lines
    Xuan, QY
    Aggarwal, RK
    Johns, AT
    [J]. MELECON '96 - 8TH MEDITERRANEAN ELECTROTECHNICAL CONFERENCE, PROCEEDINGS, VOLS I-III: INDUSTRIAL APPLICATIONS IN POWER SYSTEMS, COMPUTER SCIENCE AND TELECOMMUNICATIONS, 1996, : 657 - 660
  • [3] A Decision-Tree-Based Method for Fault Classification in Single-Circuit Transmission Lines
    Jamehbozorg, Arash
    Shahrtash, S. Mohammad
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) : 2190 - 2196
  • [4] A precise analytical method for fault location in double-circuit transmission lines
    Gil, Milad
    Abdoos, Ali Akbar
    Sanaye-Pasand, Majid
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2021, 126
  • [5] ON ALLOWING FOR SUSCEPTANCE IN FAULT LOCATION ON DOUBLE-CIRCUIT TRANSMISSION LINES
    MALYI, AS
    [J]. ELECTRICAL TECHNOLOGY, 1968, 3 : 166 - &
  • [6] Online parameter measurement of double-circuit transmission lines based on fault recorder
    Wei, Heng
    Zhou, Di
    Wang, Yi
    [J]. Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2011, 39 (23): : 138 - 142
  • [7] A Fault Location Method for Double-circuit HVDC Transmission Lines on the Same Tower Based on Mixed Modulus
    Qiu, Yingdan
    Li, Haifeng
    Guo, Lvxing
    Wu, Jiyang
    Liang, Yuansheng
    [J]. 2015 IEEE EINDHOVEN POWERTECH, 2015,
  • [8] A novel single-end fault location method for double-circuit transmission lines
    Arpanahi, Moossa Khodadadi
    Fini, Masoud Hajiakbari
    Nateghi, Abolfazl
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2024, 158
  • [9] New method of fault location on double-circuit two-terminal transmission lines
    Mazon, AJ
    Minambres, JF
    Zorrozua, MA
    Zamora, I
    AlvarezIsasi, R
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 1995, 35 (03) : 213 - 219
  • [10] A Successive Geometric Segmentation Approach Applied to Double-Circuit Transmission Lines Fault Classification and Location
    Gaspar Valente W.A.
    de Mello Honório L.
    de Oliveira E.J.
    de Alcantara Barbosa D.
    Boas E.R.V.
    [J]. Journal of Control, Automation and Electrical Systems, 2016, 27 (4) : 452 - 462