Condition based Maintenance for Power Transformers in Service Application of conventional and advanced diagnostic methods

被引:0
|
作者
Fuhr, Jitka [1 ]
机构
[1] BKW FMB Energie AG, Engn Power Lines, CH-3072 Ostermundigen, Switzerland
关键词
condition assessmet of transformers in service; advanced methods; PD-measurement on-site; PD-monitoring system;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The reliability of all HV-apparatus is strongly dependant on the ability of the insulating system to withstand the permanent electrical stress without any damage during the expected lifetime, typically more than 40 years in service. If Dissolved Gas in Oil Analysis (DGA) shows an increasing amount of fault gases the results are analyzed and the risk of the defect is judged by specialists. Due to the fact that DGA is a generic method, the location of the fault inside of the transformer is hopeless. Therefore additional diagnostic methods must be used (conventional and advanced) to identify and localize the source of the fault gases dissolved in the insulating oil. In this contribution it will be shown on practical examples, that it is possible to identify and localize the reason for the alarm or spontaneous outage of the transformer by consequent application of all existing methods (conventional and advanced) and by final "in depth" analysis of all available results.
引用
收藏
页码:271 / 275
页数:5
相关论文
共 50 条
  • [1] A procedure for diagnosis and condition based maintenance for power transformers
    Setayeshmehr, A
    Akbari, A
    Borsi, H
    Gockenbach, E
    [J]. CONFERENCE RECORD OF THE 2004 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2004, : 504 - 507
  • [2] Possibilities and limitations of offline diagnostic methods for the condition assessment of power transformers
    Werle, P.
    Hartje, M.
    [J]. ELEKTROTECHNIK UND INFORMATIONSTECHNIK, 2018, 135 (08): : 514 - 519
  • [3] A review of intelligent diagnostic methods for condition assessment of insulation system in power transformers
    Singh, Amritpal
    Verma, P.
    [J]. PROCEEDINGS OF 2008 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS, 2007, : 1354 - +
  • [4] Review of condition assessment of power transformers in service
    Wang, M
    Vandermaar, AJ
    Srivastava, KD
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2002, 18 (06) : 12 - 25
  • [5] Maintenance Strategies of Power Equipments with a View to Condition Monitoring of Power Transformers
    Spacek, Jaroslav
    Blazekk, Vladimir
    [J]. EPE: PROCEEDINGS OF THE 9TH INTERNATIONAL SCIENTIFIC CONFERENCE ELECTRIC POWER ENGINEERING 2008, 2008, : 371 - 376
  • [6] Diagnostic Application of Moisture Equilibrium for Power Transformers
    Koch, Maik
    Tenbohlen, Stefan
    Stirl, Tobias
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) : 2574 - 2581
  • [7] Modern Methods Of Evaluating The Technical Condition Of Power Transformers
    Aliyev, Tural
    Aliyev, Aydin
    [J]. PRZEGLAD ELEKTROTECHNICZNY, 2024, 100 (07): : 216 - 219
  • [8] MAINTENANCE STRATEGIES OF POWER EQUIPMENTSWITH A BRIEF VIEV TO CONDITION MONITORING OF POWER TRANSFORMERS
    Spacek, J.
    [J]. PROCEEDINGS OF THE 2008 INTERNATIONAL CONFERENCE MODERN TECHNIQUE AND TECHNOLOGIES, 2008, : 16 - 19
  • [9] Experience with diagnostic tools for condition assessment of large power transformers
    Fuhr, J
    Aschwanden, T
    [J]. CONFERENCE RECORD OF THE 2004 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2004, : 508 - 511
  • [10] Vibration of Power Transformers and its Application for Condition Monitoring
    Pan, Jie
    Jin, Ming
    Wang, Yuxing
    [J]. DYNAMICS FOR SUSTAINABLE ENGINEERING, VOL 1, 2011, : 84 - 93