Insulation Diagnosis for 220kV Oil-Immersed Current Transformer by Frequency Dielectric Spectroscopy

被引:0
|
作者
Peng, Hua-dong [1 ]
Dong, Ming [1 ]
Ren, Ming [1 ]
Miao, Jin [1 ]
Zhang, Zhi [2 ]
机构
[1] Xi An Jiao Tong Univ, State Key Lab Elect Insulat & Power Equipment, Sch Elect Engn Org, Xian 710049, Shaanxi, Peoples R China
[2] Hubei Elect Power Test Res Inst, High Voltage Div, Wuhan 430077, Hubei, Peoples R China
基金
中国国家自然科学基金;
关键词
component; current transformer; frequency dielectric spectroscopy; dissipation factor; aging and moisture; MOISTURE; DOMAIN;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Current transformer (CT) is used for protection of major components and to provide continuity of operation in power system. Failure of CT may lead to an energy explosion and result in phase to ground fault that will hinder the operation of a substation. Therefore insulation diagnosis is of great importance for evaluation of CT. As a non-destructive dielectric testing tool, Frequency Dielectric Spectroscopy (FDS) is widely used by power utility for assessments of the condition of electrical equipments such as transformer and cable, but seldom used on CT. Due to the similarity of transformer's insulation, the insulation condition of oil-paper insulation CT may be evaluated by FDS. In this paper, with the frequency range from 10(-2)similar to 10(3)Hz, FDS has been investigated on insulation condition assessment for several 220kV oil-immersed CTs. Complex permittivity and dissipation factor data are obtained as a function of frequency for each CT. To verify the validity of FDS, high voltage dissipation factors from 10kV to 145kV have been measured by Schering Bridge and compared with the FDS result at power frequency. Results indicate that FDS evaluation is a reliable tool for determination of moisture content in papers and of oil conductivities.
引用
收藏
页码:69 / 73
页数:5
相关论文
共 50 条
  • [1] Case Analysis of 220 kV Oil-immersed Current Transformer Defect
    Li Pei
    Li Hongbo
    Niu Lin
    Gao Nannan
    Zhang Yan
    Zhang Yanyan
    Pei Ying
    Yin Qinghua
    [J]. 2020 5TH ASIA CONFERENCE ON POWER AND ELECTRICAL ENGINEERING (ACPEE 2020), 2020, : 2178 - 2182
  • [2] Moisture Diagnosis of Transformer Oil-Immersed Insulation With Intelligent Technique and Frequency-Domain Spectroscopy
    Liu, Jiefeng
    Fan, Xianhao
    Zhang, Chaohai
    Lai, Chun Sing
    Zhang, Yiyi
    Zheng, Hanbo
    Lai, Loi Lei
    Zhang, Enze
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, 2021, 17 (07) : 4624 - 4634
  • [3] Analysis of 220kV Oil Immersed Inverted Current Transformer Fault and Precautions during Operation
    Zhu, Yi
    Zhang, Hong
    Wang, Xinming
    Liu, Xu
    Rong, Hua
    Guan, Yunlin
    Zheng, Wanyi
    Zhang, Su
    Jin, Xin
    [J]. PROCEEDINGS OF THE 2017 2ND INTERNATIONAL CONFERENCE ON AUTOMATION, MECHANICAL CONTROL AND COMPUTATIONAL ENGINEERING (AMCCE 2017), 2017, 118 : 761 - 764
  • [4] Aging evaluation for transformer oil-immersed cellulose insulation by using frequency dependent dielectric modulus technique
    Liu, Jiefeng
    Zhang, Heng
    Fan, Xianhao
    Zhang, Yiyi
    Zhang, Chaohai
    [J]. CELLULOSE, 2021, 28 (04) : 2387 - 2401
  • [5] Aging evaluation for transformer oil-immersed cellulose insulation by using frequency dependent dielectric modulus technique
    Jiefeng Liu
    Heng Zhang
    Xianhao Fan
    Yiyi Zhang
    Chaohai Zhang
    [J]. Cellulose, 2021, 28 : 2387 - 2401
  • [6] Aging Evaluation of Transformer Oil-Immersed Insulation Combining Frequency Domain Spectroscopy and Support Vector Machine
    Fan, Xianhao
    Liu, Jiefeng
    Zhang, Yiyi
    Wang, Zixiao
    [J]. Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2021, 36 (10): : 2161 - 2168
  • [7] Application of Dielectric Response for Oil-immersed Transformer
    Yang, Shuangsuo
    Dong, Ming
    Zhang, Guanjun
    Zhang, Zhi
    [J]. ICPADM 2009: PROCEEDINGS OF THE 9TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1-3, 2009, : 370 - +
  • [8] DIELECTRIC STRENGTH OF OIL-IMMERSED TRANSFORMER INSULATION WITH SUPERIMPOSED AC AND LIGHTNING IMPULSE VOLTAGE
    KAMATA, Y
    ENDOH, K
    FURUKAWA, S
    ENDOH, F
    NONOMURA, K
    IWATA, Y
    HORIUCHI, S
    TAKASU, N
    [J]. IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1990, 25 (04): : 683 - 687
  • [9] Polarization loss analysis and ageing characterisation of transformer oil-immersed insulation by using decoupled frequency domain spectroscopy
    Fan, Xianhao
    Liu, Jiefeng
    Zhang, Yiyi
    Ding, Zheshi
    Wang, Qingyin
    [J]. HIGH VOLTAGE, 2022, 7 (03) : 575 - 585
  • [10] Insulation Condition Diagnosis of Oil-Immersed Paper Insulation Based on Non-linear Frequency-Domain Dielectric Response
    Zhang, Daning
    Yun, Hao
    Zhan, Jiangyang
    Sun, Xiang
    He, Wenlin
    Niu, Chaobin
    Mu, Haibao
    Zhang, Guan-jun
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2018, 25 (05) : 1980 - 1988