Fault diagnosis of circuit breakers based on time-frequency and chaotic vibration analysis

被引:16
|
作者
Yang, Qiuyu [1 ]
Ruan, Jiangjun [1 ]
Zhuang, Zhijian [2 ]
机构
[1] Wuhan Univ, Sch Elect Engn & Automat, Wuhan, Peoples R China
[2] ABB China Co Ltd, Power Prod Medium Voltage Technol Ctr, Xiamen, Peoples R China
关键词
circuit breakers; machinery; fault diagnosis; mechanical engineering computing; time-frequency analysis; vibrations; chaotic vibration analysis; mechanical malfunction; main failure mode; high-voltage circuit breakers; opening operations; highly time-varying; nonstationary; machinery fault diagnosis; CB vibration characteristics; chaotic analysis; called adaptive chirp mode decomposition; ACMD; fast fluctuating instantaneous frequency; signal component; CB's vibration signal; high resolution adaptive time-frequency spectrum; mechanical condition alteration; significant time-frequency fluctuation; high-dimensional phase space; dynamic variation characteristics; reconstructed phase space; stability; CB faults; vacuum CB; voltage; 12; 0; kV; current; 1250; A; EMBEDDING DIMENSION;
D O I
10.1049/iet-gtd.2019.0985
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Mechanical malfunction is a main failure mode for circuit breakers (CBs). Vibrations generated from CB switching operations contain rich information of its mechanical condition. However, the vibrations are highly time-varying and non-stationary, which makes it very difficult to precisely extract effective features for machinery fault diagnosis. This study presents a methodology to obtain the CB vibration characteristics based on time-frequency and chaotic analysis. A new method, called adaptive chirp mode decomposition (ACMD), is introduced to extract the fast fluctuating instantaneous frequency and catch each signal component individually from the CB's vibration signal. A high resolution adaptive time-frequency spectrum which can clearly represent the mechanical condition alteration in CB is obtained by the ACMD. The component with the most significant time-frequency fluctuation is reconstructed into a high-dimensional phase space to recover and extract the dynamic variation characteristics of the CB. Based on the reconstructed phase space, a new set of features, namely RST (ratio of major-minor axis, shape complexity and trajectory compactness), is proposed for realising the stability and accurate diagnosis of CB faults. Experimental study and practical application cases are presented showing the efficiency of the methodology proposed here.
引用
收藏
页码:1214 / 1221
页数:8
相关论文
共 50 条
  • [1] Mechanical fault diagnosis of high voltage circuit breakers utilizing zero-phase filter time-frequency entropy of vibration signal
    [J]. Chang, G. (guang_chang@163.com), 2013, Chinese Society for Electrical Engineering (33):
  • [2] Fault Diagnosis of Medium Voltage Circuit Breakers Based on Vibration Signal Envelope Analysis
    Wu, Yongbin
    Zhang, Jianzhong
    Yuan, Zhengxi
    Chen, Hao
    [J]. SENSORS, 2023, 23 (19)
  • [3] A method of fault detection and diagnosis based on time-frequency analysis
    Liang, YingBo
    Zhang, LiHong
    Li, Jin
    [J]. MECHATRONICS AND INTELLIGENT MATERIALS II, PTS 1-6, 2012, 490-495 : 1407 - 1410
  • [4] Generator Looseness Fault Diagnosis Based on Time-Frequency Analysis
    Li, Ting
    Liu, Chen
    Duan, Chendong
    Qi, Xia
    [J]. PROCEEDINGS OF THE 2016 2ND WORKSHOP ON ADVANCED RESEARCH AND TECHNOLOGY IN INDUSTRY APPLICATIONS, 2016, 81 : 17 - 21
  • [5] Fault Detection for High-Voltage Circuit Breakers Based on Time-Frequency Analysis of Switching Transient E-Fields
    Zhang, Hong-Ye
    Xie, Yan-Zhao
    Yi, Tong-Qiang
    Kong, Xu
    Cheng, Lin
    Liu, Hao-Jun
    [J]. IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2020, 69 (04) : 1620 - 1631
  • [6] Fault Diagnosis of Conventional Circuit Breaker Contact System Based on Time-Frequency Analysis and Improved AlexNet
    Sun, Shuguang
    Zhang, Tingting
    Li, Qin
    Wang, Jingqin
    Zhang, Wei
    Wen, Zhitao
    Tang, Yao
    [J]. IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2021, 70
  • [7] Opening Damper Condition Evaluation Based on Vibration Time-Frequency Images for High-Voltage Circuit Breakers
    Yang, Qiuyu
    Ruan, Jiangjun
    Huang, Daochun
    Zhuang, Zhijian
    [J]. Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2019, 34 (19): : 4048 - 4057
  • [8] CURRENT-AIDED TIME-FREQUENCY ANALYSIS OF VIBRATION SIGNALS FOR GEARBOX FAULT DIAGNOSIS
    Tu, Xiaotong
    Hu, Yue
    Li, Fucai
    [J]. PROCEEDINGS OF THE ASME INTERNATIONAL DESIGN ENGINEERING TECHNICAL CONFERENCES AND COMPUTERS AND INFORMATION IN ENGINEERING CONFERENCE, 2018, VOL 8, 2018,
  • [9] Mechanical Fault Diagnosis of High Voltage Circuit Breakers Based on Wavelet Time-Frequency Entropy and One-Class Support Vector Machine
    Huang, Nantian
    Chen, Huaijin
    Zhang, Shuxin
    Cai, Guowei
    Li, Weiguo
    Xu, Dianguo
    Fang, Lihua
    [J]. ENTROPY, 2016, 18 (01)
  • [10] Fault Identification for Circuit Breakers Based on Vibration Measurements
    Yang, Qiuyu
    Ruan, Jiangjun
    Zhuang, Zhijian
    Huang, Daochun
    [J]. IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2020, 69 (07) : 4154 - 4164