Sensitivity of Low-voltage Variable-Frequency Devices to voltage Sags

被引:17
|
作者
Xu, Yonghai [1 ]
Lu, Wenqing [1 ]
Wang, Kun [1 ]
Li, Chenyi [2 ]
Aslam, Waseem [1 ]
机构
[1] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewabl, Beijing 102206, Peoples R China
[2] Chengdu Power Supply Co, State Grid Sichuan Elect Power Corp, Chengdu 610011, Sichuan, Peoples R China
基金
中国国家自然科学基金;
关键词
Variable frequency drive; voltage sag; tolerance curve; PMSM;
D O I
10.1109/ACCESS.2018.2885402
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Variable frequency drives (VFDs) are the types of power electronic device commonly used to drive motors with a wide range of industrial and practical applications, especially in power systems. VFDs are sensitive to voltage sag, thereby limiting their application. However, the difficulty in determining the detailed voltage sag tolerance characteristics of VFDs is due to various influencing factors, and the tolerance curve obtained from test results is updated as mainstream low-voltage VFDs change. This paper is the first to perform an in-depth analysis on the influence and operation mechanism of voltage sags on VFDs. Voltage sag types, which are regarded as the important influencing factors, are explored for their different impacts on VFDs from the perspective of energy. Then, eight commonly used low-voltage VFDs with small and medium powers (7.5 and 18.5 kW) are selected as the test objects. The influence of voltage sags on VFDs is tested, and the equipment parameters (protection modes and control modes of VFDs, and load torque and speed) and voltage sag characteristics factors (sag types, voltage magnitude before voltage sag, and harmonics) are considered. Finally, the general tolerance curves of the low-voltage VFDs under different sag types are extracted via comprehensive analyses and processing of more than 13 000 sets of test data. Based on the test data, this paper further explores the influence of voltage sag on the motor by using the permanent magnet synchronous motor (PMSM) as an example, which is used as the load during the tolerance test. Operation performance of the PMSM driven by different VFDs is also discussed.
引用
收藏
页码:2068 / 2079
页数:12
相关论文
共 50 条
  • [1] Applying low-voltage variable-frequency drives
    Marrano, Steven
    2000, Putman Publ Co, Itasca, IL, United States (13):
  • [2] Compatibility between Low Voltage Variable-Frequency Drives and Voltage Sags in Distribution Systems
    Xu Y.
    Li C.
    Wang K.
    Lu W.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2019, 34 (10): : 2216 - 2229
  • [3] Test and analysis on sensitivity of low-voltage releases to voltage sags
    Ouyang, Sen
    Liu, Ping
    Liu, Liyuan
    Li, Xiang
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2015, 9 (16) : 2664 - 2671
  • [4] A three-dimensional model for sensitivity of low-voltage releases to voltage sags
    Ouyang, Sen
    Liu, Ping
    Liang, Weibin
    Li, Xiang
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2015, 39 (22): : 157 - 163
  • [5] Test and study on sensitivity of electronic circuit in low-voltage release to voltage sags
    Ouyang, Sen
    Liu, Liyuan
    IET CIRCUITS DEVICES & SYSTEMS, 2017, 11 (06) : 529 - 534
  • [6] Quantitative evaluation of the impact of repetitive voltage sags on low-voltage loads
    Moon, Jong-Fil
    Yun, Sang-Yun
    Kim, Jae-Chul
    IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (04) : 2395 - 2400
  • [7] Research on the Influence of Voltage sags on Performance of Variable-Frequency Adjustable-Speed Permanent Magnet Synchronous Motor
    Wang, Kun
    Li, Chenyi
    Lu, Wenqing
    Xu, Yonghai
    PROCEEDINGS OF THE 2018 13TH IEEE CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS (ICIEA 2018), 2018, : 1147 - 1152
  • [8] Low-Voltage Electronic Diagnostic Devices
    不详
    MEDICAL LETTER ON DRUGS AND THERAPEUTICS, 2008, 50 (1300): : 95 - 96
  • [9] Design of low-voltage variable-frequency electrical motors. I: Analysis of the magnetic-thermal-electric coupled problem
    Biedinger, JM
    Vilain, JP
    EUROPEAN PHYSICAL JOURNAL-APPLIED PHYSICS, 1998, 3 (01): : 101 - 118
  • [10] Low-voltage PV power integration for variable frequency drives application
    Shetty, Akshatha
    Fernandes, B. G.
    Ojo, Olorunfemi
    Ferreira, J. A.
    2017 19TH EUROPEAN CONFERENCE ON POWER ELECTRONICS AND APPLICATIONS (EPE'17 ECCE EUROPE), 2017,