Transfer of transient surge voltage through XLPE cable winding transformer (Dryformer) circuits

被引:0
|
作者
Manyahi, MJ
Thottappillil, R
Leijon, M
机构
[1] Univ Dar Es Salaam, Fac Elect & Comp Syst Engn, Dar Es Salaam, Tanzania
[2] Uppsala Univ, Angstrom Lab, SE-75121 Uppsala, Sweden
关键词
transient surge voltage; Dryformer; gas insulated switchgear;
D O I
10.1016/j.ijepes.2005.06.007
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Experiment and simulation results of conventional transformer design have shown that there are considerable differences in the characteristics of the surge voltages that are important in deciding the transferred voltages, depending on whether it is from primary to secondary or vice versa. Dryformer is a new technological advance of dry power transformer, which is constructed from XLPE insulated high voltage cables as its winding, and is designed to provide a direct link between ultimate customers and transmission systems in one step transformation [Leijon M, Andersson T. High and dry-dryformer, an innovative high-voltage transformer design that, eliminates the need for oil, promises a host of performance and environmental benefits. IEE Rev 2000:9-14. [1]; Leijon M, Dahlgren M, Walfridsson L, Ming L, Jaksts A. A recent development in the electrical insulation systems of generators and transformers. IEEE Electr Insular Mag 2001;17(3):10-15. [2]]. It is important therefore to have a better understanding of Dryformer behaviour in regard to transient surge voltage transfer between its circuits. This paper presents the application of a high frequency model for the study of transient surge voltage transfer between the Dryformer circuits due to surges having various steepness, amplitude and duration characteristics, which are expected in practise. The model is based on the creation of an RLCG network that gives the same admittance function as that obtained experimentally at the transformer terminals [Manyahi MJ, Leijon M, Thottappillil R. Transient response of transformer with XLPE insulation cable winding design (Dryformer). ELSEVIER Electr Power Energy Syst 2005;27(l):69-80.]. The validity of the formulated model has been verified by comparing the model predictions with experimentally obtained voltage transfer function. The model is successfully applied in estimating the threat levels posed to Dryformer winding and customer connected equipment due to transient overvoltages. (c) 2005 Elsevier Ltd. All rights reserved.
引用
收藏
页码:602 / 609
页数:8
相关论文
共 36 条
  • [1] Transient response of transformer with XLPE insulation cable winding design
    Manyahi, MJ
    Leijon, M
    Thottappillil, R
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2005, 27 (01) : 69 - 80
  • [2] A new type of dry power transformer based on XLPE cable winding
    Gao, YN
    Wang, SS
    Gao, H
    ICEMS 2005: PROCEEDINGS OF THE EIGHTH INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS, VOLS 1-3, 2005, : 1771 - 1774
  • [3] Voltage Distribution in Power Transformer Winding under Transient Impulse
    Ye, Haifeng
    Gao, Ya
    Wu, Hao
    Li, Yabo
    Wu, Zhen
    Ma, Guoming
    PROCEEDINGS OF THE 2017 2ND INTERNATIONAL SYMPOSIUM ON ADVANCES IN ELECTRICAL, ELECTRONICS AND COMPUTER ENGINEERING (ISAEECE 2017), 2017, 124 : 375 - 378
  • [4] NONLINEAR TRANSFORMER-WINDING SYNTHESIS FOR IMPROVED SURGE-VOLTAGE DISTRIBUTION
    ADAMSON, C
    MANSOUR, EAA
    PROCEEDINGS OF THE INSTITUTION OF ELECTRICAL ENGINEERS-LONDON, 1968, 115 (12): : 1821 - &
  • [5] Surge voltage stresses across power transformer winding sections provided with metal oxide surge absorber blocks
    Gurumurthy, G. R.
    Ansari, Mohd. Z. A.
    Amarnath, J.
    Kishore, N. K.
    2006 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2006, : 229 - 232
  • [6] SURGE TRANSFER THROUGH TRANSFORMER-GENERATOR UNITS
    HICKLING, GH
    WINDER, AI
    PROCEEDINGS OF THE INSTITUTION OF ELECTRICAL ENGINEERS-LONDON, 1969, 116 (05): : 788 - &
  • [7] Prediction of transient transfer functions at cable-transformer interfaces
    Zhou, Joe Y.
    Boggs, Steven A.
    2005/2006 IEEE/PES TRANSMISSION & DISTRIBUTION CONFERENCE & EXPOSITION, VOLS 1-3, 2006, : 52 - +
  • [8] Numerical calculation of the lightning transient voltage distribution on converter transformer winding based a dual winding model
    Jia, Hongrui
    Liu, Xuezhong
    Tian, Shijin
    Wang, Lin
    Gao, Fei
    JOURNAL OF ENGINEERING-JOE, 2019, (16): : 3012 - 3016
  • [9] Numerical Analysis of Lightning Transient Voltage Distributions in HV Converter Transformer Winding
    Tian, Shijin
    Liu, Xuezhong
    Liu, Hao
    Wang, Lin
    Gao, Fei
    2016 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD), 2016, : 444 - 447
  • [10] Surge voltage performance of power transformer winding sections provided with metal oxide surge absorber blocks with faults in portion of sections
    Gurumurthy, G. R.
    Ansari, Mohd. Z. A.
    Amarnath, J.
    2007 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2007, : 655 - +