Novel Sensor for Determining the Aging Condition of Insulation Paper in a Transformer

被引:0
|
作者
Muenster, T. [1 ]
Kinkeldey, T. [1 ]
Werle, P. [1 ]
Haemel, K. [2 ]
Preusel, J. [2 ]
机构
[1] Leibniz Univ Hannover, Inst Elect Power Syst, Schering Inst, Div High Voltage Engn & Asset Management, Callinstr 25A, D-30167 Hannover, Germany
[2] GRIDINSPECT GmbH, Mulhof 3a, D-36325 Feldatal, Germany
关键词
CELLULOSIC INSULATION; POWER TRANSFORMERS; DEGRADATION;
D O I
10.1109/CEIDP49254.2020.9437480
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The online monitoring is becoming increasingly important for operators of high voltage assets. One of the most important assets are transformers, especially power transformers, which are mainly insulated with paper together with an insulating liquid for impregnation. An important parameter is the aging condition of the insulating paper, which allows an estimation of the operational safety. This variable is determined by the degree of polymerization (DP-value) and provides information about the mechanical stability of the paper. However, paper samples are currently required for the measurement, which is carried out in a laboratory in accordance with IEC 60450, whereby the paper is destroyed. This study is conducted to determine the DP-value of a paper insulation using a novel, patented optical sensor. The investigation shows that oil-free paper samples have very strong linear correlation between the value measured with the sensor and the DP-value. Therefore, a condition assessment is possible within seconds, as the measurement by means of the optical method is significantly faster and more precise than the conventional viscometric method. It also shows that the assessment is independent of the insulating oil, in which the paper is aged. The sensor could be used for an improved condition assessment of transformers to increase the operational safety.
引用
收藏
页码:520 / 523
页数:4
相关论文
共 50 条
  • [1] Determining Water in Transformer Paper Insulation: Analyzing Aging Transformers
    Martin, Daniel
    Saha, Tapan
    Dee, Richard
    Buckley, Gary
    Chinnarajan, Srinivasan
    Caldwell, Greg
    Bin Zhou, Jian
    Russell, Gary
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2015, 31 (05) : 23 - 32
  • [2] Aging of transformer insulation paper
    Le, TT
    Hill, DJT
    Darveniza, M
    [J]. JOURNAL OF MACROMOLECULAR SCIENCE-PURE AND APPLIED CHEMISTRY, 1996, A33 (12): : 1885 - 1895
  • [3] Using Polarization/Depolarization Current characteristics to Estimate Oil Paper Insulation aging condition of the Transformer
    Zhou, Yuanhua
    Zhang, Tao
    Zhang, Dongfang
    Zhang, Xiaolin
    [J]. 2016 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2016,
  • [4] A Novel Methanol-detection-method for the Aging Prediction of Paper Insulation in Power Transformer
    Peng, Lei
    Fu, Qiang
    Lin, Musong
    Qian, Yihua
    Zhao, Yaohong
    [J]. 2018 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2018,
  • [5] A Novel Furfural-detection-method for the Aging Prediction of Paper Insulation in Power Transformer
    Peng, Lei
    Fu, Qiang
    Lin, Musong
    Zhao, Yaohong
    Qian, Yihua
    Li, Shengli
    [J]. 2018 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (IEEE CEIDP), 2018, : 630 - 633
  • [6] Aging Condition Assessment of Transformer Oil-paper Insulation Model based on Partial Discharge Analysis
    Liao, Rui-jin
    Yang, Li-jun
    Li, Jian
    Grzybowski, Stanislaw
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2011, 18 (01) : 303 - 311
  • [7] Thermal aging test for transformer oil-paper insulation under over-load condition temperature
    Yang, Li Jun
    Sun, Weidong
    Gao, Sihang
    Hao, Jian
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (12) : 2846 - 2853
  • [8] Research of Insulation Aging of Transformer Insulation Paper by Multi-parameter Regression Analysis
    Yang, Daowu
    Han, Huihui
    Wang, Su
    Tong, Haixia
    Ren, Zhuo
    [J]. FUNDAMENTAL OF CHEMICAL ENGINEERING, PTS 1-3, 2011, 233-235 : 1345 - +
  • [9] A Novel Nanomodified Cellulose Insulation Paper for Power Transformer
    Yuan, Yuan
    Liao, Ruijin
    [J]. JOURNAL OF NANOMATERIALS, 2014, 2014
  • [10] Life evaluation of insulation paper used in transformer by determining the activation energy
    Shi, J.
    Wu, C.N.
    Wang, X.J.
    [J]. Materials Research Innovations, 2015, 19 : 164 - 167