Determinants of low energy performance in a multi-chiller system serving an educational premise

被引:2
|
作者
Ho, W. T. [1 ]
Yu, F. W. [1 ]
机构
[1] Hong Kong Polytech Univ, Coll Profess & Continuing Educ, Div Sci Engn & Hlth Studies, Hong Kong, Peoples R China
关键词
Coefficient of performance; Logistic regression; Odds ratio; Water-cooled chiller; OPERATION STRATEGY; SEQUENCING CONTROL; OPTIMIZATION; DEMAND; EFFICIENT; PLANT;
D O I
10.1016/j.ijrefrig.2020.02.019
中图分类号
O414.1 [热力学];
学科分类号
摘要
This study analyses an association between operating variables and low energy performance in terms of the coefficient of performance (COP) of a chiller system in daily operation. Year-round operating data were collected at 15-min intervals from a trend logging device for a system with five chillers of two different capacities. Two-step cluster analysis was applied to group operating data with high and low COP ratings. The odds ratio analysis ascertained that the key deficient control was operating extra chillers with one at particularly light loads. The optimal trade-off between the chiller power and condenser water pump power was not achieved due to the surplus operation of condenser water pumps. The low COP rating was also due to an imprecise control in the chilled water supply temperature and the condenser water entering temperature from their fixed set points. The significance of this study is to prioritize COP improvement opportunities by ranking the impact of deficient controls based on the actual configuration and operating practice of any given chiller system. (C) 2020 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:47 / 53
页数:7
相关论文
共 50 条
  • [1] The energy saving operation design for large multi-chiller system
    Lu, Yanyue
    Liao, Anping
    RENEWABLE AND SUSTAINABLE ENERGY, PTS 1-7, 2012, 347-353 : 3064 - 3067
  • [2] Evaluation of operation performance of a multi-chiller system using a data-based chiller model
    Wang, Yijun
    Jin, Xinqiao
    Du, Zhimin
    Zhu, Xu
    ENERGY AND BUILDINGS, 2018, 172 : 1 - 9
  • [3] Design and operation optimization of multi-chiller plants based on energy performance simulation
    Chen, Yixing
    Yang, Chuhao
    Pan, Xiao
    Yan, Da
    ENERGY AND BUILDINGS, 2020, 222
  • [4] Study on operation and control of large multi-chiller system
    Lu, Yanyue
    Liao, Anping
    ADVANCED MATERIALS AND STRUCTURES, PTS 1 AND 2, 2011, 335-336 : 1273 - 1278
  • [5] Energy optimization methodology of multi-chiller plant in commercial buildings
    Thangavelu, Sundar Raj
    Myat, Aung
    Khambadkone, Ashwin
    ENERGY, 2017, 123 : 64 - 76
  • [6] Rapid evaluation of operation performance of multi-chiller system based on history data analysis
    Wang, Yijun
    Jin, Xinqiao
    Fang, Xing
    ENERGY AND BUILDINGS, 2017, 134 : 162 - 170
  • [7] A model predictive control for a multi-chiller system in data center considering whole system energy conservation
    Zhao, Jing
    Chen, Ziyi
    Li, Haonan
    Liu, Dehan
    ENERGY AND BUILDINGS, 2024, 324
  • [8] A decentralized algorithm to optimize multi-chiller systems in the HVAC system
    Yu, Hao
    Zhao, Tianyi
    Zhang, Jili
    Li, Xiuming
    2017 CHINESE AUTOMATION CONGRESS (CAC), 2017, : 4099 - 4102
  • [9] Application of new optimisation model for multi-chiller system consumption
    Tian, Erlin
    Ebadi, Abdol Ghaffar
    Mavaluru, Dinesh
    Kadyrov, Marsel
    Ponomarev, Andrei
    Druzhinin, Zumrat
    INTERNATIONAL JOURNAL OF AMBIENT ENERGY, 2021, 42 (16) : 1851 - 1863
  • [10] Easy-to-Use Methods for Multi-Chiller Plant Energy and Cost Evaluation
    Duda, Stephen W.
    ASHRAE TRANSACTIONS 2012, VOL 118, PT 1, 2012, 118 : 325 - 332