ESTIMATION FOR DEGRADATION CHARACTERISTICS OF CELLULOSE PAPER USED IN OIL-FILLED TRANSFORMER AND ANALYSIS FOR CORRELATIONSHIP USING STATISTICAL TREATMENT

被引:0
|
作者
Kim, Jae Hoon [1 ]
Park, Doo Ki [1 ]
Han, Sang Ok [1 ]
机构
[1] Chungnam Natl Univ, Taejon 305764, South Korea
来源
2010 CONFERENCE ON PRECISION ELECTROMAGNETIC MEASUREMENTS CPEM | 2010年
关键词
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper is aimed at evaluation about aging properties of cellulose paper used for insulating of oil-filled transformer and analysis on correlation between mechanical characteristic such as tensile strength and chemical characteristics such as CO, CO(2) gas and furfural when cellulose paper is aged by thermal. For experiment the accelerated aging cell has been manufactured, it has been aged during 60 hours at 100, 150, 180 and 200[degrees C], respectively. It has been used DGA(dissolved gas analysis) and HPLC(high performance liquid chromatography) for degradation diagnosis. Also it has been established correlation between them using multiple regression analysis.
引用
收藏
页码:692 / 693
页数:2
相关论文
共 8 条
  • [1] Estimation of Degradation Indices of Oil-Filled Transformer Based on the Color Data of Insulating Oil
    Oshima, Seiichirou
    Nakamura, Hisahide
    Kobayashi, Hiroshi
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2021, 16 (06) : 882 - 887
  • [2] DIELECTRIC RESPONSE ANALYSIS AND DIAGNOSIS OF OIL-FILLED POWER TRANSFORMERS Calculation of paper moisture in power transformer
    Singh, Shrikant
    Kumar, Ambuj
    Singh, Sunil Kumar
    Jarial, R. K.
    2015 INTERNATIONAL CONFERENCE ON ENERGY, POWER AND ENVIRONMENT: TOWARDS SUSTAINABLE GROWTH (ICEPE), 2015,
  • [3] Statistical Estimation Oil-filled Cable Using Health and Risk Index by the Monte Carlo Simulation
    Park, Keonhee
    Park, Sehee
    Im, Jeaseong
    Lim, Jangseob
    2022 9TH INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD), 2022, : 301 - 304
  • [4] Analysis for insulating degradation characteristics with aging time for oil-filled transformers and/or correlation between using linear regression method
    Lee, Seung-Min
    Transactions of the Korean Institute of Electrical Engineers, 2010, 59 (04): : 693 - 699
  • [5] Comparison of Empty and Oil-Filled Transformer Tank Mode Shapes Using Experimental and FEM Modal Analysis
    Petrovic, Karlo
    Dobric, Danilo
    Gotic, Ivan
    Zupan, Tomislav
    ENERGIES, 2024, 17 (03)
  • [6] Inhibition method for the degradation of oil-paper insulation and corrosive sulphur in a transformer using adsorption treatment
    Yang, Lijun
    Gao, Sihang
    Deng, Bangfei
    Zhang, Jiang
    Sun, Weidong
    Hu, Ende
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2016, 10 (08) : 1893 - 1900
  • [7] Transformer Paper Expected Life Estimation Using ANFIS Based on Oil Characteristics and Dissolved Gases (Case Study: Indonesian Transformers)
    Prasojo, Rahman Azis
    Diwyacitta, Karunika
    Suwarno
    Gumilang, Harry
    ENERGIES, 2017, 10 (08):
  • [8] Analysis of Physical and Electrical Characteristics of Transformer Oil Insulation During Accelerated Thermal Aging Experiment and Its Lifetime Estimation Using Arrhenius Law and Breakdown Voltage Test
    Negara, I. Made Yulistya
    Aryani, Ni Ketut
    Asfani, Dimas Anton
    Fahmi, Daniar
    Jauhari, Rifqi
    Wahyudi, Mochammad
    2017 INTERNATIONAL SEMINAR ON INTELLIGENT TECHNOLOGY AND ITS APPLICATIONS (ISITIA), 2017, : 139 - 143