Synchrophasor-Based Wide-Area Backup Protection Scheme with Data Requirement Analysis

被引:72
|
作者
Zare, Javad [1 ]
Aminifar, Farrokh [1 ]
Sanaye-Pasand, Majid [1 ]
机构
[1] Univ Tehran, Sch Elect & Comp Engn, Coll Engn, Tehran 14395515, Iran
关键词
Data requirement analysis; fault detection; phasor measurement unit (PMU); wide-area backup protection; SYSTEM;
D O I
10.1109/TPWRD.2014.2377202
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a fast and robust wide-area backup protection scheme to detect the faulty condition and to identify the faulted line in a large power network. The proposed methodology uses positive-sequence synchrophasor data captured by either digital relays with synchronization capability or phasor measurement units dispersed over the network. The basic idea behind the new protection scheme is the comparison of bus voltage values calculated through dissimilar paths. Upon occurrence of a fault, the faulty condition is first detected and the bus(es) connected to the faulted line is(are) determined. Among transmission lines connected to the suspected bus(es), the faulted one is thereafter identified. In addition to two-terminal transmission lines, multiterminal lines are also incorporated. The performance of the proposed method is validated on the IEEE 57-bus test system in different fault conditions (fault type, fault location, and fault resistance). Discrimination of faulty and normal conditions is simulated by examining various stressed conditions, for example, load encroachment, generator outage, and power swing. The data requirement of the proposed technique is analyzed as well. To do so, a mathematical model for the optimal placement of measurement devices is developed and applied to different IEEE standard test systems.
引用
收藏
页码:1410 / 1419
页数:10
相关论文
共 50 条
  • [1] Communication-Constrained Regionalization of Power Systems for Synchrophasor-Based Wide-Area Backup Protection Scheme
    Zare, Javad
    Aminifar, Farrokh
    Sanaye-Pasand, Majid
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2015, 6 (03) : 1530 - 1538
  • [2] Wide-area backup protection and protection performance analysis scheme using PMU data
    Yu, Fangzhu
    Booth, Campbell
    Dysko, Adam
    Hong, Qiteng
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2019, 110 : 630 - 641
  • [3] Fault identification scheme for wide-area backup protection
    Wang, Yan
    Jin, Jing
    Jiao, Yanjun
    [J]. Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2014, 34 (12): : 70 - 75
  • [4] An adaptive supervised wide-area backup protection scheme for transmission lines protection
    B. Mallikarjuna
    P. V. Vardhan Varma
    S. D. Samir
    M. Jaya Bharata Reddy
    D. K. Mohanta
    [J]. Protection and Control of Modern Power Systems, 2017, 2 (1)
  • [5] A Differential Voltage-Based Wide-Area Backup Protection Scheme for Transmission Network
    Samantaray, Shalini Ranjan
    Samantaray, Subhransu Ranjan
    [J]. IEEE SYSTEMS JOURNAL, 2022, 16 (01): : 520 - 530
  • [6] A wide area synchrophasor-based load shedding scheme to prevent voltage collapse
    Mahari, Arash
    Seyedi, Heresh
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2016, 78 : 248 - 257
  • [7] Audur-A platform for synchrophasor-based power system wide-area control system implementation
    Vanfretti, L.
    Jonsdottir, G. M.
    Almas, M. S.
    Rebello, E.
    Firouzi, S. R.
    Baudette, M.
    [J]. SOFTWAREX, 2018, 7 : 294 - 301
  • [8] A Wide-Area Backup Protection Algorithm Based on Distance Protection Fitting Factor
    Ma, Jing
    Liu, Chang
    Thorp, James S.
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2016, 31 (05) : 2196 - 2205
  • [9] Tripping strategy based on directional weight for wide-area backup protection
    Ma, Jing
    Pei, Xun
    Ma, Wei
    Wang, Zengping
    [J]. Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2015, 35 (10): : 107 - 114
  • [10] Synchrophasor-based backup distance protection of multi-terminal transmission lines
    Al-Emadi, Nasser A.
    Ghorbani, Amir
    Mehrjerdi, Hasan
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2016, 10 (13) : 3304 - 3313