Improvement of the Standard Ampacity Calculations for Power Cables Installed in Trefoil Formations in Ventilated Tunnels

被引:6
|
作者
Colef, John-Michael [1 ]
de Leon, Francisco [1 ]
机构
[1] New York Univ, Metrotech Ctr 5, Dept Elect & Comp Engn, Brooklyn, NY 11201 USA
关键词
Mathematical model; Power cables; Standards; Convection; IEC Standards; Ventilation; Finite element analysis; Cable rating; computational fluid dynamics (CFD); forced convection; turbulent flow; ventilated tunnel;
D O I
10.1109/TPWRD.2021.3068111
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Forced ventilated underground installations are challenging to design due to the complex mathematics of turbulent fluid flow. Previous methods have tackled this problem, but only recently, the effect of confinement on a single cable has been considered. In this paper, the effect of cable confinement on the practical case of ventilated trefoil installations is investigated. The complete Computational Fluid Dynamics (CFD) problem is solved using Finite Element Method (FEM) simulations and then validated by laboratory experiments using pipes. FEM simulations are then used to vary the current, the wind velocity, and the distance of the trefoil from the tunnel wall to get a comprehensive picture of the phenomena. This data is used to create a new empirical equation for the Nusselt number for a wide range of operating conditions. The principle of similitude is validated for a scaled-down model of a large tunnel and then used to analyze the thermal rating of tunnels. The new equation improves the IEC standard equations by accounting for the effect of cable confinement on trefoil installations. An important finding of this paper is that a lower maximum permissible current rating is obtained, which if ignored can present a serious risk for thermal damage. It was also found that the cables must be installed three cable diameters away from the wall to prevent the derating effect of confinement.
引用
收藏
页码:627 / 637
页数:11
相关论文
共 10 条
  • [1] Ampacity Calculations for Deeply Installed Cables
    Dorison, Eric
    Anders, George J.
    Lesur, Frederic
    IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (02) : 524 - 533
  • [2] Enhanced Thermal Model of Power Cables Installed in Ducts for Ampacity Calculations
    Sedaghat, Ali
    Lu, Haowei
    Bokhari, Abdullah
    de Leon, Francisco
    IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (05) : 2404 - 2411
  • [3] Thermal Analysis of Power Cables in Free Air: Evaluation and Improvement of the IEC Standard Ampacity Calculations
    Sedaghat, Ali
    de Leon, Francisco
    IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (05) : 2306 - 2314
  • [4] Ampacity Calculations of Underground Power Cables With End Effects
    Brakelmann, Heiner
    Anders, George J.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2023, 38 (03) : 1968 - 1976
  • [5] Ampacity Estimation for HV Submarine Power Cables Installed in Saturated Seabed
    Duraisamy, Nishanthi
    Gooi, H. B.
    Ukil, Abhisck
    2018 IEEE INTERNATIONAL CONFERENCE ON POWER ELECTRONICS, DRIVES AND ENERGY SYSTEMS (PEDES), 2018,
  • [6] Ampacity improvement of high voltage submarine cables installed in J-tubes
    Zhang, Ruisong
    Zhang, Shihao
    Wang, Maozhou
    Peng, Jia
    Chang, Zhengshi
    Deng, Junbo
    Wang, Shaohua
    Yang, Yong
    Ma, Yu
    ELECTRIC POWER SYSTEMS RESEARCH, 2025, 244
  • [7] Dynamic Thermal Model for Different Size Trefoil Power Cables With Various Loads in Non-Forced-Ventilated Tunnels
    Giglio, David A. A.
    de Leon, Francisco
    IEEE TRANSACTIONS ON POWER DELIVERY, 2023, 38 (02) : 1286 - 1296
  • [8] Ampacity Estimation for Submarine Power Cables Installed in Saturated Seabed-Experimental Studies
    Duraisamy, Nishanthi
    Gooi, Hoay Beng
    Ukil, Abhisek
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2020, 56 (06) : 6229 - 6237
  • [9] Improvement in power cables ampacity in ducts by using low thermal resistivity backfill material
    Zhang M.
    Fan Y.
    Liu S.
    Zhang Q.
    Fan, Youbing, 1600, Science Press (42): : 2548 - 2552
  • [10] Mock-Up Study of the Effect of Wall Distance on the Thermal Rating of Power Cables in Ventilated Tunnels
    Boukrouche, Fahd
    Moreau, Christophe
    Pelle, Julien
    Beaubert, Francois
    Harmand, Souad
    Moreau, Olivier
    IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (06) : 2453 - 2461