Analysis of the Ionized Field Under HVDC Transmission Lines in the Presence of Wind Based on Upstream Finite Element Method

被引:60
|
作者
Lu, Tiebing [1 ]
Feng, Han [2 ]
Cui, Xiang [1 ]
Zhao, Zhinbin [1 ]
Li, Lin [1 ]
机构
[1] N China Elect Power Univ, Sch Elect & Elect Engn, Baoding 071003, Hebei, Peoples R China
[2] Zhengzhou Power Supply Co, Zhengzhou 450006, Henan, Peoples R China
基金
中国国家自然科学基金;
关键词
Corona; electric fields; finite element methods; HVDC transmission lines; ION CURRENT-DENSITY; ELECTRIC-FIELD;
D O I
10.1109/TMAG.2010.2044149
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Corona phenomenon generated from high voltage direct current (HVDC) transmission lines can affect the environment nearby. Based on the upstream finite element method, an iterative algorithm is used to analyze the ionized electric field and the ion current density at the ground level with the wind velocity taken into consideration. The algorithm is efficiently convergent. The proposed method is testified by measurement results of a unipolar line in the presence of wind and a bipolar test line. Finally some examples are analyzed to predict the effect of the wind and to determine the transmission corridor of +/- 800 kV HVDC transmission line.
引用
收藏
页码:2939 / 2942
页数:4
相关论文
共 50 条
  • [1] Analysis of Ionized Field under HVDC Transmission Lines with Buildings Nearby
    Luo, Zhaonan
    Cui, Xiang
    Lu, Jiayu
    2010 ASIA-PACIFIC INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY & TECHNICAL EXHIBITION ON EMC RF/MICROWAVE MEASUREMENTS & INSTRUMENTATION, 2010, : 277 - 280
  • [2] Analysis of ionized field under ±800kV HVDC transmission lines
    Lu, Tiebing
    Zhao, Jie
    Cui, Xiang
    Feng, Han
    2006 17TH INTERNATIONAL ZURICH SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY, VOLS 1 AND 2, 2006, : 416 - +
  • [3] Calculation of Ionized Field of HVDC Transmission Lines by the Meshless Method
    Yang, Fan
    Liu, Zehui
    Luo, Hanwu
    Liu, Xinghua
    He, Wei
    IEEE TRANSACTIONS ON MAGNETICS, 2014, 50 (07)
  • [4] A calculation method for 3-D ionized field under HVDC transmission lines
    Luo, Zhaonan
    Cui, Xiang
    Zhen, Yongzan
    Lu, Jiayu
    Han, Hui
    Liu, Yuanqing
    Yang, Yong
    Ju, Yong
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2010, 30 (27): : 102 - 107
  • [5] Contrast and analysis on total electric field at ground level under HVDC transmission lines by Deutsch assumption-based method and finite element method
    Yang, Yong
    Lu, Jiayu
    Ju, Yong
    Dianwang Jishu/Power System Technology, 2013, 37 (02): : 526 - 532
  • [6] Calculation of Ion-Flow Field of HVdc Transmission Lines in the Presence of Wind Using Finite Element-Finite Difference Combined Method With Domain Decomposition
    Qiao, Ji
    Zou, Jun
    Yuan, Jiansheng
    Lee, J. B.
    Ju, Munno
    IEEE TRANSACTIONS ON MAGNETICS, 2016, 52 (03)
  • [7] Analysis of Ionized Field under HVDC Transmission Lines within the Influences of Suspended Particles
    Li, Yan
    Yuan, Shun
    Yang, Fan
    Gao, Bing
    He, Tingting
    Ran, Jia
    PROGRESS IN ELECTROMAGNETICS RESEARCH M, 2019, 83 : 29 - 40
  • [8] A probabilistic model of exposure to ionized fields under HVDC lines in presence of wind
    Abouelsaad, MM
    11TH IEEE MEDITERRANEAN ELECTROTECHNICAL CONFERENCE, PROCEEDINGS, 2002, : 419 - 423
  • [9] Computation Method for Ionized Field on Buildings Near HVDC Transmission Lines
    He, Kun
    Xie, Li
    Chen, Bo
    Wang, Yifan
    Ju, Yong
    Lu, Jiayu
    2024 10TH INTERNATIONAL CONFERENCE ON ELECTRICAL ENGINEERING, CONTROL AND ROBOTICS, EECR 2024, 2024, : 425 - 429
  • [10] Calculation of Electric Field Under High Voltage Direct Current Transmission Lines by the Upstream Finite Element Method
    Liang, Zhenguang
    Jiang, Yuze
    2020 IEEE 8TH INTERNATIONAL CONFERENCE ON COMPUTER SCIENCE AND NETWORK TECHNOLOGY (ICCSNT), 2020, : 46 - 49