Measured and Simulated Energy Use in a Secondary School Building in Sweden-A Case Study of Validation, Airing, and Occupancy Behaviour

被引:20
|
作者
Englund, Jessika Steen [1 ]
Cehlin, Mathias [1 ]
Akander, Jan [1 ]
Moshfegh, Bahram [1 ,2 ]
机构
[1] Univ Gavle, Dept Bldg Engn Energy Syst & Sustainabil Sci, S-80176 Gavle, Sweden
[2] Linkoping Univ, Dept Management & Engn, Div Energy Syst, S-58183 Linkoping, Sweden
关键词
building energy simulation; school building; field measurements; validation; airing; windows and door opening; occupancy behaviour; energy efficiency measures; PERFORMANCE; METHODOLOGIES; GAP;
D O I
10.3390/en13092325
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In this case study, the energy performance of a secondary school building from the 1960s in Gavle, Sweden, was modelled in the building energy simulation (BES) tool IDA ICE version 4.8 prior to major renovation planning. The objectives of the study were to validate the BES model during both occupied and unoccupied periods, investigate how to model airing and varying occupancy behaviour, and finally investigate energy use to identify potential energy-efficiency measures. The BES model was validated by using field measurements and evidence-based input. Thermal bridges, infiltration, mechanical ventilation, domestic hot water circulation losses, and space heating power were calculated and measured. A backcasting method was developed to model heat losses due to airing, opening windows and doors, and other occupancy behaviour through regression analysis between daily heat power and outdoor temperature. Validation results show good agreement: 3.4% discrepancy between space heating measurements and simulations during an unoccupied week. Corresponding monthly discrepancy varied between 5.5% and 10.6% during three months with occupants. Annual simulation indicates that the best potential renovation measures are changing to efficient windows, improved envelope airtightness, new controls of the HVAC system, and increased external wall thermal insulation.
引用
收藏
页数:22
相关论文
共 4 条
  • [1] Simulated and Actual Energy Use of a Green Building: A Case Study on the Magic School of Green Technology
    Su, Tzu-Ching
    Wang, Yu-Chung
    Lin, Hsien-Te
    FRONTIERS OF GREEN BUILDING, MATERIALS AND CIVIL ENGINEERING III, PTS 1-3, 2013, 368-370 : 1174 - 1178
  • [2] The Impact of Occupants' Energy Use Behaviour on Building Performance: a Case Study of a Tower Block in London
    Zahiri, Sahar
    Elsharkawy, Heba
    Shi, Wei
    SMART AND HEALTHY WITHIN THE TWO-DEGREE LIMIT (PLEA 2018), VOL 3, 2018, : 1056 - 1058
  • [3] Development and validation of energy signature method - Case study on a multi-family building in Sweden before and after deep renovation
    Eriksson, Martin
    Akander, Jan
    Moshfegh, Bahram
    ENERGY AND BUILDINGS, 2020, 210
  • [4] Quantification of the energy use due to occupant behaviour collected in surveys: a case study of a green and non-green building
    Almeida, Laura M. M. C. E.
    Tam, Vivian W. Y.
    Le, Khoa N.
    JOURNAL OF BUILDING PERFORMANCE SIMULATION, 2020, 13 (06) : 777 - 803