IMPACT OF THERMAL ENERGY STORAGE ON THE SIZING AND ENERGY CONSUMPTION OF A DISTRICT COOLING SYSTEM

被引:0
|
作者
Dufour, T. [1 ]
Hoang, H. M. [1 ]
Osswald, V [1 ]
Clain, P. [1 ,2 ]
Fournaison, L. [1 ]
Delahaye, A. [1 ]
机构
[1] Irstea, UR GPAN, 1 Rue Pierre Gilles de Gennes, F-92761 Antony, France
[2] Leonard de Vinci Pole Univ, Res Ctr, F-92916 Paris, La Defense, France
关键词
Thermal energy storage; District cooling; System modelling; Hydrate; Slurry; BUILDINGS; PCM; CO2;
D O I
10.18462/iir.pcm.2018.0040
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
Thermal energy storage (TES) has been recognized to be a good way to ensure energy security, efficiency and environmental quality. Nevertheless many materials are available with variable thermodynamic properties. The aim of this work is to compare the energy consumption and sizing of a district cooling system with TES device in function of storage materials (water, CO2 hydrate slurry and TBPB hydrate slurry). A system modelling approach was developed by assembling component models: chiller, stirred tank reactor, circulation loop and place of use (house equipped with heat exchanger). The evolution of room and storage temperature, chiller and pumping energy consumption for different materials and various operating conditions is analyzed. Results show that the use of PCM (hydrates) allows an under sizing of the system, limiting the volume of the storage device and improving the system efficiency compared to system with water.
引用
收藏
页码:293 / 300
页数:8
相关论文
共 50 条
  • [1] District Cooling Versus Individual Cooling in Urban Energy Systems: The Impact of District Energy Share in Cities on the Optimal Storage Sizing
    Dominkovic, Dominik Franjo
    Krajacic, Goran
    [J]. ENERGIES, 2019, 12 (03)
  • [2] Sizing and control optimization of thermal energy storage in a solar district heating system
    Saloux, Etienne
    Candanedo, Jose A.
    [J]. ENERGY REPORTS, 2021, 7 : 389 - 400
  • [3] Optimal chiller loading in a district cooling system with thermal energy storage
    Powell, Kody M.
    Cole, Wesley J.
    Ekarika, Udememfon F.
    Edgar, Thomas F.
    [J]. ENERGY, 2013, 50 : 445 - 453
  • [4] Thermal energy storage in district heating and cooling systems: A review
    Guelpa, Elisa
    Verda, Vittorio
    [J]. APPLIED ENERGY, 2019, 252
  • [5] Sizing and Management of an Energy System for a Metropolitan Station with Storage and Related District Energy Community
    Simoiu, Mircea Stefan
    Fagarasan, Ioana
    Ploix, Stephane
    Calofir, Vasile
    [J]. ENERGIES, 2021, 14 (18)
  • [6] Analysis of a Thermal Energy Storage Tank in a Large District Cooling System: A Case Study
    Abd Majid, Mohd Amin
    Muhammad, Masdi
    Hampo, Chima Cyril
    Akmar, Ainul Bt
    [J]. PROCESSES, 2020, 8 (09)
  • [7] Design optimization of a district heating and cooling system with a borehole seasonal thermal energy storage
    Fiorentini, Massimo
    Heer, Philipp
    Baldini, Luca
    [J]. ENERGY, 2023, 262
  • [8] Study on the Performance Analysis of Stratified Thermal Energy Storage System of a District Cooling Plant
    Abd Majid, Mohd Amin
    Yamin, Mohd Fadillah
    [J]. 6TH INTERNATIONAL CONFERENCE ON PRODUCTION, ENERGY AND RELIABILITY 2018: WORLD ENGINEERING SCIENCE & TECHNOLOGY CONGRESS (ESTCON), 2018, 2035
  • [9] Impact of heating and cooling loads on battery energy storage system sizing in extreme cold climates
    Olis, Walker
    Rosewater, David
    Nguyen, Tu
    Byrne, Raymond H.
    [J]. ENERGY, 2023, 278
  • [10] Optimal sizing of battery energy storage system for local multi-energy systems: The impact of the thermal vector
    Gluecker, Philipp
    Pesch, Thiemo
    Benigni, Andrea
    [J]. APPLIED ENERGY, 2024, 372