Numerical calculation of transient electric field considering space charge in oil-paper insulation of converter transformers

被引:2
|
作者
Xiu, Liancheng [1 ]
Du, Zhiye [1 ]
Tian, Yu [2 ]
He, Jingxuan [1 ]
Cai, Hongwei [1 ]
Yi, Fan [3 ]
机构
[1] Wuhan Univ, Sch Elect Engn & Automat, Wuhan, Peoples R China
[2] State Grid Suzhou Power Supply Co, Suzhou, Peoples R China
[3] Peoples Liberat Army Air Force Early Warning Acad, Wuhan, Peoples R China
基金
中国国家自然科学基金;
关键词
Space charge; Transient electric field; Oil-paper insulation; Converter transformers; CONSTANT MOBILITY; IONIZED FIELD; FLUID MODEL; VOLTAGE; DC; POLYETHYLENE; TRANSPORT; BEHAVIOR; REVERSAL;
D O I
10.1108/COMPEL-04-2021-0148
中图分类号
TP39 [计算机的应用];
学科分类号
081203 ; 0835 ;
摘要
Purpose The purpose of this paper is to develop a numerical simulation method based on the transient upstream finite element method (FEM) and Schottky emission theory to reveal the distribution characteristics of space charge in oil-paper insulation. Design/methodology/approach The main insulation medium of the converter transformer in high voltage direct current transmission is oil-paper insulation. However, the influence of space charge is difficult to be fully considered in the insulation design and simulation of converter transformers. To reveal the influence characteristics of the space charge, this paper proposes a numerical simulation method based on Schottky emission theory and the transient upstream FEM. This method considers the influence of factors, such as carrier mobility, carrier recombination coefficient, trap capture coefficient and diffusion coefficient on the basis of multi-physics field coupling calculation of the electric field and fluid field. Findings A numerical simulation method considering multiple charge states is proposed for the space charge problem in oil-paper insulation. Meanwhile, a space charge measurement platform based on the electrostatic capacitance probe method for oil-paper insulation structure is built, and the effectiveness and accuracy of the numerical simulation method is verified. Originality/value A variety of models are calculated and analyzed by the numerical simulation method in this paper, and the distribution characteristics of the space charge and total electric field in oil-paper insulation medium with single-layer, polarity reversal of plate voltage and double-layer are obtained. The research results of this paper have the guiding significance for the engineering application of oil-paper insulation and the optimal design of converter transformer insulation.
引用
收藏
页码:155 / 171
页数:17
相关论文
共 50 条
  • [1] The Breakdown Characteristics of Oil-Paper Insulation in Converter Transformers
    Zuo, Kun
    Shen, Wei
    Cui, Huize
    Zhou, Guangming
    Wang, Weiwang
    Li, Shengtao
    PROCEEDINGS OF 2020 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS (ISEIM 2020), 2020, : 537 - 540
  • [2] Influence of Oil Property on the Space Charge Characteristics and Electric Field Distortion in Oil-Paper Insulation
    Hao Jian
    Fu Jin
    Wu Gaolin
    Wang Qian
    Yao Qiang
    2014 IEEE WORKSHOP ON ELECTRONICS, COMPUTER AND APPLICATIONS, 2014, : 1038 - 1041
  • [3] Space Charge Simulation of Oil-paper Insulation in Outlet of Converter Transformer
    Ren, Shuangzan
    Wu, Jingfeng
    Wu, Hao
    Hao, Dongxin
    Wu, Kai
    Wu, Yang
    Gaodianya Jishu/High Voltage Engineering, 2022, 48 (06): : 2292 - 2301
  • [4] Space charge and its effects on oil-paper insulation in power transformers: A review
    Raj, Raymon Antony
    JOURNAL OF ELECTROSTATICS, 2023, 126
  • [5] Numerical Simulation Method of Electric Field in Oil-Paper Insulation
    Lian Q.
    Du Z.
    Yang Z.
    Jin S.
    Ruan J.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2017, 32 (20): : 53 - 61
  • [6] Influence of Oil Property on Space Charge Dynamics in Oil-Paper Insulation under DC and AC Electric Field
    Wu Gaolin
    Jian, Hao
    Qian, Wang
    Jin, Fu
    Qiang, Yao
    2013 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2013, : 218 - 221
  • [7] Influence of Oil-paper Insulation Electric-dynamic Parameters on Calculation Results of Electric Field at the End of Converter Transformer
    Chi M.
    Wang Q.
    Luo Q.
    Zhang C.
    Liu J.
    Guan Y.
    Chen Q.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2022, 42 (05): : 1701 - 1712
  • [8] Effect of Moisture Content on Space Charge Behavior in Oil-paper Insulation Under DC Electric Field
    Che, Lu
    Wu, Jiandong
    Zhou, Guiyue
    Yin, Yi
    Wang, Qiaohua
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2020, 27 (05) : 1570 - 1577
  • [9] DC Electric Field Effect on Conductivity and Interface Charge of Oil-Paper Insulation
    Shi, Shilin
    Hao, Jian
    Jian, Zheng
    Liao, Ruijin
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2023, 30 (04) : 1525 - 1533
  • [10] Space Charge Characteristics of Electrothermally Aged Oil-Paper Insulation Under Slightly Nonuniform Electric Field
    He, Dongxin
    Geng, Pan
    Liu, Hongshun
    Xu, Zhe
    Li, Qingquan
    Xie, Shijie
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2023, 30 (03) : 1125 - 1134