A Study of Composite Insulator Aging Using the Tracking Wheel Test

被引:33
|
作者
Moghadam, Mitra Khiabani [1 ,2 ]
Taheri, Mona [3 ,4 ]
Gharazi, Salimeh
Keramati, Mohsen [5 ]
Bahrami, Mozhgan [6 ]
Riahi, Nastaran [7 ]
机构
[1] Iran Polymer & Petrochem Inst, Tehran, Iran
[2] Niroo Res Inst, Tehran, Iran
[3] Qom Univ Technol, Qom, Qom Province, Iran
[4] Payame Noor Univ, Dept Chem Engn, Tehran, Iran
[5] Iran Polymer & Petrochem Inst, Plast Dept, Tehran, Iran
[6] Univ Michigan, Ann Arbor, MI 48109 USA
[7] Niroo Res Inst, Ceram & Polymer Dept, Tehran, Iran
关键词
High voltage insulation application; tracking wheel; PDMS;
D O I
10.1109/TDEI.2016.005427
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper, silicone rubber (SR) insulators are investigated as to the aging behavior at different aging time in tracking wheel. Sampling was done every 200h till 2000h. Thermo Gravimetric Analysis (TGA), Fourier Transform Inferred Spectroscopy (FTIR), Scanning Electron Microscopy (SEM), contact angle measurement, Energy Dispersive X ray scattering (EDX), mechanical and electrical tests were carried out for these purpose. The correlation coefficient of 0.9 proved an acceptable relation between migration of smaller size low molecular weight molecules (SLMWs) and contact angle. TGA and extraction testes results showed SLMW are almost 15% of total LMWs and responsible for recovery of hydrophobicity. Also TGA results demonstrated that after 2000h accelerated aging, thermal stability (potential thermal-resistant property) of the PDMS polymer decreases about 10%. ATR-FTIR analysis results showed the rate of Si-O-Si peak changes was higher than vSi-C and the vOH peak decreases by the 50%. The surface hardness increased about 20% with increasing aging time to 2000h. An average reduction of 30% and 25% in the tensile strength and strain at break were found with respect to the virgin sample aged. Increasing aging time increases leakage current from 50 to 500 (mu A) that still is lower than 1 mA so means there is no critical degradation.
引用
收藏
页码:1805 / 1811
页数:7
相关论文
共 50 条
  • [1] STUDY OF COMPOSITE INSULATOR SHEDS SUBJECTED TO WHEEL TEST
    Mackiewicz, M.
    Mikulski, J. L.
    Wankowicz, J.
    Kucharski, S.
    Ranachowski, P.
    Ranachowski, Z.
    ARCHIVES OF METALLURGY AND MATERIALS, 2017, 62 (02) : 679 - 686
  • [2] Tracking Wheel Test of Composite Insulator In 22kV Distribution System
    Rupdee, Annop
    Thipprasert, Wichet
    Yachiangkam, Samart
    2020 8TH INTERNATIONAL ELECTRICAL ENGINEERING CONGRESS (IEECON), 2020,
  • [4] Tracking wheel test facilities
    Muncivi, A.
    Sarkar, P.
    Haddad, A.
    UPEC: 2009 44TH INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE, 2009, : 648 - 652
  • [5] Aging Diagnosis of Silicone Rubber Composite Insulator Based on Conduction Current Test
    Li, Yonggang
    Huang, Chengcai
    2014 IEEE TRANSPORTATION ELECTRIFICATION CONFERENCE AND EXPO (ITEC) ASIA-PACIFIC 2014, 2014,
  • [6] Study of tracking wheel test method under DC voltage
    Yu, Y
    Liang, XD
    Zhou, YX
    Li, XS
    PROCEEDINGS OF THE 7TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1-3, 2003, : 439 - 442
  • [7] EFFECT OF WHEEL SPEED ON THE TRACKING TIME IN A ROTATING WHEEL-SPRAY TRACKING TEST
    SALAMA, MMA
    SALLAM, MM
    BARTNIKAS, R
    IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (03) : 1217 - 1221
  • [8] Design and Construction of an Advanced Tracking Wheel for Insulator Materials Testing
    Fletcher, Harrison P.
    Macdonald, Andrew
    Secord, Chris
    Lenckowski, Mark
    Padmawar, Rajkumar
    Hore, Dennis K.
    CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING-REVUE CANADIENNE DE GENIE ELECTRIQUE ET INFORMATIQUE, 2020, 43 (04): : 342 - 349
  • [9] Investigation on Tracking Wheel Test of Large-diameter Composite Insulators under AC Voltage
    Li, Shaohua
    Liang, Xidong
    Liu, Yingyan
    Shen, Hao
    Gao, Yanfeng
    He, Zilan
    Luo, Bing
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (06) : 3522 - 3529
  • [10] The Comprehensive Assessment of Composite Insulator Aging Condition
    Ning, Miaofu
    Liu, Qisheng
    Yu, Xueping
    Chen, Yan
    Wang, Jian
    2015 5TH INTERNATIONAL CONFERENCE ON ELECTRIC UTILITY DEREGULATION AND RESTRUCTURING AND POWER TECHNOLOGIES (DRPT 2015), 2015, : 1472 - 1477