Investigation of Horizontal Ground Electrode&x0027;s Effective Length Under Impulse Current

被引:13
|
作者
Kherif, Omar [1 ]
Chiheb, Sofiane [1 ]
Teguar, Madjid [1 ]
Mekhaldi, Abdelouahab [1 ]
Harid, Noureddine [2 ]
机构
[1] Ecole Natl Polytech, Lab Rech Electrotech, Algiers 16200, Algeria
[2] Khalifa Univ Sci & Technol, Dept Elect & Comp Engn, Abu Dhabi 127788, U Arab Emirates
关键词
Electrodes; Soil; Grounding; Conductivity; Computational modeling; Transient analysis; Electric potential; Effective length; electrodes; grounding; lightning transients; transient analysis; two-layer soil; ELECTRODES; IMPEDANCE; EFFICIENCY; MODEL;
D O I
10.1109/TEMC.2018.2864130
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper discusses the impulse analysis of horizontal ground electrode buried in uniform and two-layer soils, describing applications of a recently developed model based on transmission line approach for the analysis of high frequency and transient behavior of grounding systems. Simulations were carried out to compute the ground electrode' potential and the impulse impedance. A practical method to estimate the effective length of horizontal ground electrodes is presented. The results have been successfully compared with those computed using formulas reported in the literature and only developed for uniform soils. The proposed method is intended for estimation of the effective length of horizontal electrodes buried in soils having a two-layer stratification, which has not yet been considered so far. Based on this method, parametric analysis carried out has shown that the parameters influencing the effective length are mainly the soil resistivity and the rise time of the injected current for uniform soils or associated with the upper layer depth and the refection factor for two-layer soils. Using a genetic algorithm, mathematical expressions for the effective length of horizontal ground electrodes are proposed in terms of these parameters.
引用
收藏
页码:1515 / 1523
页数:9
相关论文
共 5 条
  • [1] Current and Voltage Distribution in a Horizontal Earth Electrode under Impulse Conditions
    Ahmeda, M.
    Ullah, N.
    Harid, N.
    Griffiths, H.
    Haddad, A.
    UPEC: 2009 44TH INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE, 2009, : 707 - +
  • [2] Transmission Line Dynamic Circuit Model for Effective Length of Ground Electrode Under Lightning Transients
    Kumar A, Senthil
    Manickavasagam, Krishnan
    IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2022, 64 (02) : 543 - 550
  • [3] Experimental investigation on ablation characteristics of coated and uncoated steel under 30/80 μs impulse current
    戴明秋
    刘亚坤
    傅正财
    刘娟
    毕晓蕾
    Plasma Science and Technology, 2019, 21 (07) : 123 - 134
  • [4] Experimental investigation on ablation characteristics of coated and uncoated steel under 30/80 μs impulse current
    戴明秋
    刘亚坤
    傅正财
    刘娟
    毕晓蕾
    Plasma Science and Technology, 2019, (07) : 123 - 134
  • [5] Experimental investigation on ablation characteristics of coated and uncoated steel under 30/80 μs impulse current
    Dai, Mingqiu
    Liu, Yakun
    Fu, Zhengcai
    Liu, Juan
    Bi, Xiaolei
    PLASMA SCIENCE & TECHNOLOGY, 2019, 21 (07)