Performance evaluation of a radiant floor cooling system integrated with dehumidified ventilation

被引:111
|
作者
Song, Doosam [2 ]
Kim, Taeyeon [1 ]
Song, Suwon [3 ]
Hwang, Suckho [3 ]
Leigh, Seung-Bok [4 ]
机构
[1] Yonsei Univ, Dept Architectural Engn, Seoul 120749, South Korea
[2] Sungkyunkwan Univ, Dept Architectural Engn, Seoul, South Korea
[3] Yonsei Univ, Ctr Sustainable Bldg, Seoul 120749, South Korea
[4] Yonsei Univ, Dept Architecture, Seoul 120749, South Korea
关键词
radiant floor cooling; dehumidified ventilation; performance evaluation; indoor thermal comfort;
D O I
10.1016/j.applthermaleng.2007.10.020
中图分类号
O414.1 [热力学];
学科分类号
摘要
The radiant floor cooling system can be used as an alternative to all-air cooling systems, using the existing Ondol system (a radiant floor heating system) in Korea to save energy and maintain indoor thermal comfort. Unfortunately, a radiant floor cooling system may cause condensation on the floor surface under hot and humid conditions during the cooling season. In addition, the radiant floor system does not respond quickly to internal load changes due to the thermal storage effect of the concrete mass, which is usually present in radiant floor cooling systems. This study proposes a radiant floor cooling system integrated with dehumidified ventilation, which cools and dehumidifies the outdoor air entering through the cooling coil in the ventilator by lowering the dew-point temperature to prevent condensation on the floor surface. Furthermore, outdoor reset control was used to modulate the temperature of chilled water supplied to the radiant floor, and indoor temperature feedback control was then used to respond to the internal load changes. To evaluate the performance of the radiant floor cooling system integrated with dehumidified ventilation, both a physical experiment in a laboratory setting and TRNSYS simulation for an apartment in Korea have been conducted. As a result, it was found that the proposed system was not only able to solve the problem of condensation on a floor surface but also to control the indoor thermal environment within the acceptable range of comfort. Furthermore, the proposed system improved the responsiveness to internal load changes. (C) 2007 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1299 / 1311
页数:13
相关论文
共 50 条
  • [1] A study for evaluating performance of radiant floor cooling integrated with controlled ventilation
    Leigh, SB
    Song, DS
    Hwang, SH
    Lee, SY
    [J]. ASHRAE Transactions 2005, Vol 111, Pt 1, 2005, 111 : 71 - 82
  • [2] Performance analysis of a ductless personalized ventilation combined with radiant floor cooling system and displacement ventilation
    Jiying Liu
    Daniel Alejandro Dalgo
    Shengwei Zhu
    Hui Li
    Linhua Zhang
    Jelena Srebric
    [J]. Building Simulation, 2019, 12 : 905 - 919
  • [3] An Experimental Study on Operating Characteristic of Radiant Floor Cooling Integrated with Underfloor Ventilation System
    Cai, Ning
    Zhang, Dongliang
    [J]. INTERNATIONAL JOURNAL OF HEAT AND TECHNOLOGY, 2021, 39 (04) : 1207 - 1212
  • [4] Performance analysis of a ductless personalized ventilation combined with radiant floor cooling system and displacement ventilation
    Liu, Jiying
    Dalgo, Daniel Alejandro
    Zhu, Shengwei
    Li, Hui
    Zhang, Linhua
    Srebric, Jelena
    [J]. BUILDING SIMULATION, 2019, 12 (05) : 905 - 919
  • [5] Performance Evaluation of Hybrid Radiant Cooling System Integrated with Decentralized Ventilation System in Hot and Humid Climates
    Cui, Shixin
    Kim, Moon Keun
    Papadikis, Konstantinos
    [J]. 10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 1245 - 1252
  • [6] Experimental Study on Performance of Lightweight Radiant Floor Cooling Combined with Underfloor Ventilation System
    Xia, Xue-ying
    Zhang, Xu
    [J]. LOW-CARBON CITY AND NEW-TYPE URBANIZATION, 2015, : 307 - 315
  • [7] Radiant Cooling with Dehumidified Air Ventilation for Thermal Comfort in Buildings in Tropical Climate
    Nutprasert, Nipaporn
    Chaiwiwatworakul, Pipat
    [J]. 2013 INTERNATIONAL CONFERENCE ON ALTERNATIVE ENERGY IN DEVELOPING COUNTRIES AND EMERGING ECONOMIES (2013 AEDCEE), 2014, 52 : 250 - 259
  • [8] Analysis of feasibility of floor radiant cooling system combined with displacement ventilation
    Li, DY
    Ren, YL
    Wang, ZJ
    [J]. 2ND ASIAN CONFERENCE ON REFRIGERATION AND AIR-CONDITIONING, PROCEEDINGS: NEW CONTRIBUTION TO ASIAN SUSTAINABLE DEVELOPMENT, 2004, : 634 - 637
  • [9] Performance of radiant cooling system integrated with ice storage
    Matsuki, N
    Nakano, Y
    Miyanaga, T
    Yokoo, N
    Oka, T
    [J]. ENERGY AND BUILDINGS, 1999, 30 (02) : 177 - 183
  • [10] Numerical evaluation of the thermal performance of a ceiling radiant cooling panel integrated with radiation shields and ventilation air
    Rasti, Fatemeh
    Salmanzadeh, Mazyar
    [J]. Journal of Building Engineering, 2025, 99