Reduction of the step voltages of MV/LV substation grounding system based on shaping electric field

被引:3
|
作者
Sikorao, Roman [1 ]
Markiewiczo, Przemyslaw [1 ]
机构
[1] Lodz Univ Technol, Inst Elect Power Engn, Stefanowski Str 18-22, PL-90924 Lodz, Poland
关键词
grounding system; step voltage; touch voltage; IEEE; 80-2013; standard; RESISTANCE; SOILS; MODEL;
D O I
10.24425/aee.2021.137576
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The article presents the analysis results of the effectiveness limitation of the step voltage by forming an electric field on the ground surface. For shaping the electric field, a method consisting of screens placed around the point of the earth current flow was used. The analysis was performed using an example of an MV/LV substation grounding system. This research was conducted applying a mathematical model of the grounding system and screens by means of the finite element method. The influence of metal, insulating screens and surface material on the step/touch voltage values for the considered grounding system was estimated. Most of the methods described can be applied in practice. In the opinion of the authors, the method of using screens made of insulating and conductive materials has not been sufficiently described in the literature. Moreover, in the available literature there is no in-depth analysis of the described electric field shaping methods.
引用
收藏
页码:601 / 613
页数:13
相关论文
共 50 条
  • [1] Performance Evaluation of Grounding System of MV/LV Outdoor Compact Substation
    Merentitis, Konstantinos D.
    Ellinas, Emmanouil D.
    Christodoulou, Christos A.
    Christoforos, Spyridon
    Pyrgioti, Eleftheria C.
    Gonos, Ioannis F.
    [J]. 2022 57TH INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE (UPEC 2022): BIG DATA AND SMART GRIDS, 2022,
  • [2] Field Area Network in a MV/LV Substation: a Technical and Economical Analysis
    Feliciano, Sara
    Sarmento, Helena
    de Oliverira, Joao Zambujal
    [J]. 2014 IEEE INTERNATIONAL CONFERENCE ON INTELLIGENT ENERGY AND POWER SYSTEMS (IEPS), 2014, : 192 - 197
  • [3] Design of active loops for magnetic field mitigation in MV/LV substation surroundings
    Carlos del-Pino-Lopez, Juan
    Giaccone, Luca
    Canova, Aldo
    Cruz-Romero, Pedro
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2015, 119 : 337 - 344
  • [4] Thevenin source resistances of the touch, transferred and step voltages of a grounding system
    Chow, YL
    Salama, MMA
    Djogo, G
    [J]. IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1999, 146 (02) : 107 - 114
  • [5] Research on Measures of Grounding Resistance Reduction for Substation Based on CDEGS
    Chen, Sigeng
    Shen, Wei
    Cao, Wen
    Miao, Haoming
    Du, Siqi
    Fan, Yicheng
    [J]. 2022 9TH INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD), 2022, : 722 - 726
  • [6] Research of the Grounding Measurement System based on LabVIEW in Substation
    Liu, Zhishen
    Gao, Jingge
    Zhang, Shuqiang
    [J]. ICICTA: 2009 SECOND INTERNATIONAL CONFERENCE ON INTELLIGENT COMPUTATION TECHNOLOGY AND AUTOMATION, VOL II, PROCEEDINGS, 2009, : 328 - +
  • [7] Gas Insulated Substation Grounding System Design Using the Electromagnetic Field Method
    Liu, Jie
    Dawalibi, Farid P.
    Majerowicz, Brian F.
    [J]. 2012 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2012,
  • [8] Reduction of low voltage power cables electromagnetic field emission in MV/LV substations
    Segundo, Hector Beltran San
    Roig, Vicente Fuster
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2008, 78 (06) : 1080 - 1088
  • [9] Analytical Study on Improvement of Traction Substation's Grounding System for lightning overvoltage reduction
    Yasui, Shinji
    Nakao, Yasutomo
    Ogihara, Masaki
    Yamamoto, Yusuke
    Kobayashi, Shinichi
    Hayashiya, Hitoshi
    [J]. 2018 34TH INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP 2018), 2018,
  • [10] IEC61850-based Protection System for MV/LV Substations
    Suarez, Fernando A. Fuentes
    Ragaini, Enrico
    [J]. 2017 IEEE WORKSHOP ON POWER ELECTRONICS AND POWER QUALITY APPLICATIONS (PEPQA), 2017, : 48 - 52