Performance analysis of the ejector-vapour compression refrigeration cycle

被引:19
|
作者
Yari, M. [1 ]
Sirousazar, M. [2 ]
机构
[1] Univ Mohaghegh Ardabili, Dept Mech Engn, Fac Engn, Ardabil 179, Iran
[2] Univ Mohaghegh Ardabili, Dept Chem Engn, Fac Engn, Ardabil 179, Iran
关键词
ejector-vapour compression cycle; internal heat exchanger; intercooler; coefficient of performance; second law;
D O I
10.1243/09576509JPE484
中图分类号
O414.1 [热力学];
学科分类号
摘要
In the current paper, a new configuration of the ejector-vapour compression refrigeration cycle was presented, which uses an internal heat exchanger and intercooler to enhance the performance of the cycle. The theoretical analysis on the performance characteristics was carried out for this new cycle based on the first and second laws of thermodynamics. The effects of the evaporative and condenser temperatures on the coefficient of performance (COP), second law efficiency, exergy destruction rate and entrainment ratio were investigated. The exergy analysis is employed in order to identify the amounts and locations of the irreversibility within the cycles. It was found that the COP and second law efficiency values of the new ejector-vapour compression refrigeration cycle are on average 8.6 and 8.15 per cent higher than that of the conventional ejector-vapour compression refrigeration cycle with R125. It was also shown that the COP of the new ejector-vapour compression cycle is 21 per cent higher than that of the conventional vapour. compression.
引用
收藏
页码:1089 / 1098
页数:10
相关论文
共 50 条
  • [1] Performance evaluation of a solar ejector-vapour compression cycle for cooling application
    Megdouli, K.
    Elakhdar, M.
    Nahdi, E.
    Kairouani, L.
    Mhimid, A.
    [J]. TUNISIA-JAPAN SYMPOSIUM: R&D OF ENERGY AND MATERIAL SCIENCES FOR SUSTAINABLE SOCIETY, 2015, 596
  • [2] Thermodynamic analysis of an ejector-vapour compressor cascade refrigeration system
    Trung Kien Nguyen
    Chi Hiep Le
    [J]. JOURNAL OF THERMAL ANALYSIS AND CALORIMETRY, 2020, 141 (06) : 2189 - 2200
  • [3] Exergetic analysis of the vapour compression refrigeration cycle using ejector as an expander
    Yari, Mortaza
    [J]. INTERNATIONAL JOURNAL OF EXERGY, 2008, 5 (03) : 326 - 340
  • [4] Performance analysis of the vapour compression cycle using ejector as an expander
    Nehdi, E.
    Kairouani, L.
    Bouzaina, M.
    [J]. INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2007, 31 (04) : 364 - 375
  • [5] Performance analysis of a combined vapor compression cycle and ejector cycle for refrigeration cogeneration
    Megdouli, K.
    Tashtoush, B. M.
    Nahdi, E.
    Elakhdar, M.
    Mhimid, A.
    Kairouani, L.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2017, 74 : 517 - 527
  • [6] Performance improvement of the vapour compression refrigeration cycle by a two-phase constant area ejector
    Bilir, Nagihan
    Ersoy, H. Kursad
    [J]. INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2009, 33 (05) : 469 - 480
  • [7] ANALYSIS OF REFRIGERATION CYCLE PERFORMANCE WITH AN EJECTOR
    Wani, J. R.
    Baheta, Aklilu T.
    Woldeyohannes, Abraham D.
    Hassan, Suhaimi
    [J]. 3RD INTERNATIONAL CONFERENCE ON MECHANICAL ENGINEERING RESEARCH (ICMER 2015), 2016, 74
  • [8] Solar powered combined ejector vapour compression cycle for air conditioning and refrigeration
    Sun, DW
    [J]. ENERGY CONVERSION AND MANAGEMENT, 1997, 38 (05) : 479 - 491
  • [9] Performance assessment of a low-grade heat driven dual ejector vapour compression refrigeration cycle
    Mondal, Subha
    De, Sudipta
    [J]. APPLIED THERMAL ENGINEERING, 2020, 179
  • [10] Performance evaluation of an ejector subcooled vapor-compression refrigeration cycle
    Xing, Meibo
    Yan, Gang
    Yu, Jianlin
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2015, 92 : 431 - 436