Multiple Harmonic Current Injection System for Audible Noise Analysis of AC Filter Capacitors in Converter Stations

被引:2
|
作者
Han, Jingang [1 ]
Zheng, Shouzhi [1 ]
Yao, Gang [1 ]
Chen, Hao [1 ]
Wang, Yide [1 ,2 ]
Tang, Tianhao [1 ]
机构
[1] Shanghai Maritime Univ, Inst Elect Drives & Control Syst, Shanghai 201306, Peoples R China
[2] Univ Nantes, IETR, UMR CNRS 6164, F-44300 Nantes, France
来源
IEEE ACCESS | 2020年 / 8卷
基金
中国国家自然科学基金;
关键词
Power harmonic filters; Harmonic analysis; Filtering theory; Delays; Power capacitors; AC filter capacitor; current control; harmonic current; synchronous rotating frame; VOLTAGE; COMPENSATION;
D O I
10.1109/ACCESS.2020.2993458
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The audible noise of AC filter capacitors is one of the major noise sources in High Voltage Direct Current (HVDC) converter stations. In order to avoid the sharp noise of AC filter capacitors, it is necessary to design a Multiple Harmonic Current Injection System (MHCIS) for power capacitors to analyze their audible noise characteristics. Simulating effectively the noise of AC filter capacitors under their actual working conditions in converter stations is the primary target of this proposed MHCIS. To ensure the accuracy of the harmonic currents injected into the power capacitors, each harmonic current is detected and controlled separately. On the basis of the instantaneous reactive power theory, a selective harmonic current detection algorithm is proposed in this paper for the single-phase MHCIS. The amplitude of the selected harmonic current can be tracked timely and exactly in d-q synchronous rotational coordinate system, such that a Proportional Integral (PI) controller can be directly operated to eliminate the steady-state errors. The experimental parameters are usually invariable in this system, the phase deviation of the selected harmonic current is also fixed. Thus the phase angle offset of the corresponding harmonic current can be detected and calculated to compensate the system inherent delay. Owing to the accurate detection and control of multiple harmonic currents, the actual working conditions of AC filter capacitors can be accurately simulated, and the reliable noise analysis results of power capacitors can be obtained. Finally, the proposed selective harmonic current detection and control algorithm is verified by the theoretical analysis, simulation and experimental results.
引用
收藏
页码:94024 / 94032
页数:9
相关论文
共 42 条
  • [1] FFT-based selective harmonic current control of AC filter capacitors for audible noise analysis
    Han, Jingang
    Sun, Shuoshuo
    Zheng, Shouzhi
    Gao, Yang
    Wang, Yide
    Tang, TianHao
    MEASUREMENT & CONTROL, 2021, 54 (3-4): : 408 - 416
  • [2] Audible Noise Characteristics of Filter Capacitors Used in HVDC Converter Stations
    Zhu, Lingyu
    Li, Jinyu
    Shi, Yuhang
    Rehman, Habibur
    Ji, Shengchang
    IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (05) : 2263 - 2271
  • [3] Study on Audible Noise Characteristics of Filter Capacitors and Reactors in HVDC Converter Stations by Using Sound Signal Processing Array Technique
    Wang, Lv
    Wu, Jian
    Wei, Jingyi
    Zhou, Haihong
    Geng, Mingxin
    Bai, Xiaochun
    2020 5TH ASIA CONFERENCE ON POWER AND ELECTRICAL ENGINEERING (ACPEE 2020), 2020, : 1281 - 1285
  • [4] Study on an Audible Noise Reduction Measure for the Filter Capacitors in the HVDC Converter Station Based on the MPP Absorber
    Wu Peng
    Ji Shengchang
    Cao Tao
    Li Yanming
    Li Xiaolin
    Li Yan
    IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (04) : 1756 - 1762
  • [5] Test Study on Noise of Filter Capacitors Based on Different Harmonic Injection Conditions
    Wang Lulu
    Lei Xiaoyan
    Chen Li
    Qian Qingchun
    Xiong Yi
    2018 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2018, : 937 - 944
  • [6] Noise and Vibration Survey of ac Filter Capacitors in Feng Xian HVdc Converter Station
    Zhu Lingyu
    Ji Shengchang
    Shen Qi
    PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), 2012, : 886 - 889
  • [7] Control Scheme for Reducing Second Harmonic Current in AC-DC-AC Converter System
    Liu, Fei
    Ruan, Xinbo
    Huang, Xinze
    Qiu, Yang
    Jiang, Yuyang
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2022, 37 (03) : 2593 - 2605
  • [8] Research on harmonic impedance model and harmonic interaction of multiple converter station system with AC filters
    Guo C.
    Xu X.
    Zhang C.
    Yang L.
    Ma K.
    Jiang W.
    1600, Electric Power Automation Equipment Press (40): : 187 - 193
  • [9] Modeling of a multiple grid-connected-converter system considering harmonic coupling and analysis of AC/DC harmonic interaction characteristics
    Lin S.
    Li Y.
    Dai Y.
    Yang F.
    Bian X.
    Li D.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2023, 51 (10): : 65 - 77
  • [10] Analysis of the impact of AC system faults on filter commutated converter in HVDC
    Xu, Jiazhu
    Luo, Longfu
    Li, Ji
    Zhao, Zhiyu
    Shao, Pengfei
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2010, 25 (01): : 144 - 150