Multiple Features Based Anti-Islanding Protection Relay for Distributed Generations

被引:0
|
作者
Kar, Susmita [1 ]
Samantaray, S. R. [1 ]
机构
[1] Indian Inst Technol, Sch Elect Sci, Bhubaneswar 751013, Orissa, India
关键词
Distributed generation; islanding detection; S-transform; decision tree; Rate of Change of Frequency; Rate of change of Voltage; HARMONIC DISTORTION;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A multiple features based passive islanding detection technique using S-transform and decision tree is proposed in this paper. It consider synchronous as well as inverter based distributed generations interfaced to micro-grid. The technique involves extraction of different statistical features of frequency contour obtain by performing S-transform with the current signal retrieved at target distributed generation location and builds the decision tree for islanding and non-islanding classification. Extensive simulations are carried out for wide variations in system loading and power mis-match during islanding, and a decision tree is built for effective islanding detection for both synchronous and inverter based distributed generations in microgrid. Performance of the proposed anti-islanding technique is compared with existing rate of change of frequency and rate of change of voltage relay. It provides improved performance at lower end power mis-match.
引用
收藏
页数:6
相关论文
共 50 条
  • [1] Data-mining-based intelligent anti-islanding protection relay for distributed generations
    Kar, Susmita
    Samantaray, Subhransu R.
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2014, 8 (04) : 629 - 639
  • [2] Data-Mining-based Intelligent Anti-Islanding Protection Relay for Distributed Generations
    Pardeshi, Chaitanya P.
    Jadhav, Ganesh N.
    [J]. 2017 IEEE INTERNATIONAL CONFERENCE ON POWER, CONTROL, SIGNALS AND INSTRUMENTATION ENGINEERING (ICPCSI), 2017, : 2496 - 2501
  • [3] Intelligent Anti-Islanding Protection Scheme for Distributed Generations
    Kar, Susmita
    Samantaray, S. R.
    [J]. 2013 ANNUAL IEEE INDIA CONFERENCE (INDICON), 2013,
  • [4] Anti-Islanding Protection Relay for Medium Voltage Feeder With Multiple Distributed Generators
    Xiao, Hua F.
    Fang, Zhijian
    Xu, Dewei
    Venkatesh, Bala
    Singh, Birendra
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2017, 64 (10) : 7874 - 7885
  • [5] Anti-Islanding Protection Relay for Medium Voltage Feeder with Distributed Generator
    Xiao, Huafeng
    Fang, Zhijian
    Li, Chushan
    Xu, David
    Venkatesh, Bala
    Singh, Birendra N.
    [J]. 2016 IEEE ELECTRICAL POWER AND ENERGY CONFERENCE (EPEC), 2016,
  • [6] Comprehensive investigation of the voltage relay for anti-islanding protection of synchronous distributed generation
    Ahmadzadeh-Shooshtari, Babak
    Golshan, Mohamad Esmail Hamedani
    Sadeghkhani, Iman
    [J]. INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2017, 27 (11):
  • [7] An Anti-islanding Protection for Inverters in Distributed Generation
    Amin, Mohammad
    Zhong, Qing-Chang
    Lyu, Zijun
    Zhang, Liuxi
    Li, Zuyi
    Shahidehpour, Mohammad
    [J]. IECON 2018 - 44TH ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY, 2018, : 1669 - 1674
  • [8] Local Anti-Islanding Protection for Distributed Generators Based on Impedance Measurements
    Kliber, Jacek
    Wang, Wencong
    Xu, Wilsun
    [J]. 2008 IEEE ELECTRICAL POWER AND ENERGY CONFERENCE, 2008, : 519 - 523
  • [9] An Autoground System for Anti-Islanding Protection of Distributed Generation
    Abbey, Chad
    Brissette, Yves
    Venne, Philippe
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2014, 29 (02) : 873 - 880
  • [10] An Anti-Islanding Protection for VSM Inverters in Distributed Generation
    Amin, Mohammad
    Zhong, Qing-Chang
    Lyu, Zijun
    [J]. IEEE OPEN JOURNAL OF POWER ELECTRONICS, 2020, 1 : 372 - 382