Diagnosing Winding and Core Condition of Power Transformer by Vibration Signal Analysis'

被引:0
|
作者
Munir, Buyung Sofiarto [1 ]
Smit, Johan J. [2 ]
Rinaldi, I. G. M. Rama [1 ]
机构
[1] PT PLN Persero, Jakarta, Indonesia
[2] Delft Univ Technol, Delft, Netherlands
关键词
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The ability to diagnose the integrity of the transformer windings and core through online diagnostic method would be useful for electric utilities who are concerned about the availability and reliability of power transformer. This paper presents results of a study to identify the condition of power transformer windings and core by measuring the vibration signal of outdoor transformer in normal operating conditions. The obtained vibration signal which is recorded from various places on the transformer tank is analyzed by matching the signal frequency spectrum with transformer load. From this study, mechanical integrity of windings and core inside the transformer is determined by comparing the correlation between each main frequency of vibration signal and the load among similar transformer.
引用
收藏
页码:429 / 432
页数:4
相关论文
共 50 条
  • [1] Vibration measuring system for monitoring core and winding condition of power transformer
    Ji, Shengchang
    Liu, Weiguo
    Shan, Ping
    Li, Yanming
    Xu, Dake
    [J]. Gaodianya Jishu/High Voltage Engineering, 2000, 26 (06): : 1 - 3
  • [2] Study on Diagnosis of Power Transformer Winding Deformation through Vibration Signal
    Zhang, Fan
    Ji, Shengchang
    Shi, Yuhang
    Cui, Yanjie
    Zhu, Lingyu
    Zhu, Yeye
    [J]. 2016 IEEE INTERNATIONAL POWER MODULATOR AND HIGH VOLTAGE CONFERENCE (IPMHVC), 2016, : 654 - 658
  • [3] Application of Multi-fractal Spectrum to Analysis the Vibration Signal of Power Transformer for the Detection of Winding Deformation
    Wang, Feng-hua
    Zhang, Jun
    Jin, Zhi-jian
    Li, Qing
    [J]. MANUFACTURING SYSTEMS AND INDUSTRY APPLICATIONS, 2011, 267 : 584 - 589
  • [4] Analysis of Vibration Signal for Power Transformer On-Load Tap Changer (OLTC) Condition Monitoring
    Seo, Junhyuck
    Ma, Hui
    Saha, Tapan K.
    [J]. 2018 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM), 2018,
  • [5] The axial vibration of transformer winding under short circuit condition
    Wang, ZQ
    Wang, M
    Ge, YQ
    [J]. POWERCON 2002: INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY, VOLS 1-4, PROCEEDINGS, 2002, : 1630 - 1634
  • [6] An Analysis of Transformer Core Vibration and Noise under DC Bias Condition
    Xu, Yongming
    Dai, Meng
    Wang, Wenyi
    [J]. 2017 INTERNATIONAL CONFERENCE ON COMPUTER SYSTEMS, ELECTRONICS AND CONTROL (ICCSEC), 2017, : 1612 - 1615
  • [7] Transformer Winding Deformation Analysis Based on Short-circuit Reactance and Vibration Signal Analysis
    Xu J.
    Chen Y.
    Li H.
    E S.
    Chen J.
    Cai S.
    [J]. Xu, Jianyuan (intxjy@163.com), 2001, Science Press (43): : 2001 - 2006
  • [8] Feature extraction for vibration signal of transformer winding with multiple faults
    Li, Li
    Zhu, Yongli
    Song, Yaqi
    [J]. Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2014, 34 (08): : 140 - 146
  • [9] Analysis of Transformer Vibration Signal
    Ma, Keqi
    [J]. PROCEEDINGS OF THE 2017 5TH INTERNATIONAL CONFERENCE ON FRONTIERS OF MANUFACTURING SCIENCE AND MEASURING TECHNOLOGY (FMSMT 2017), 2017, 130 : 1044 - 1049
  • [10] Analysis of the Measuring Points Selection of Power Transformer Winding Deformation though Vibration Test
    Li, Xuebin
    Huang, Xu
    Zhou, Zhiqiang
    Zhao, Yisong
    Chen, Yanwen
    Song, Xuebin
    [J]. 2016 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2016,