A fast time-frequency transform based differential relaying scheme for UPFC based double-circuit transmission line

被引:21
|
作者
Tripathy, L. N. [1 ]
Samantaray, S. R. [1 ]
Dash, P. K. [2 ]
机构
[1] Indian Inst Technol Bhubaneswar, Sch Elect Sci, Bhubaneswar, Orissa, India
[2] Siksha O Anusandhan Univ, Bhubaneswar 751030, Odisha, India
关键词
Double-circuit transmission line; Fast Discrete S-Transform (FDST); Time-frequency transform; Spectral energy (SE); Unified Power Flow Controller (UPFC); FUZZY COMBINED APPROACH; S-TRANSFORM; PROTECTION; CLASSIFICATION; FAULTS; SVC;
D O I
10.1016/j.ijepes.2015.11.032
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a new differential relaying scheme for a mutually coupled, double circuit transmission line in presence of Unified Power Flow Controller (UPFC) in the line. The process starts at retrieving the three phase current signals at both ends of the transmission line synchronously and processing it though the time-frequency transform such as Fast Discrete S-Transform to derive the spectral energy content of the current signals. The differential spectral energy of current signals (difference between the spectral energy of the current signal at the sending and receiving ends, respectively) of the respective phases of transmission line is used to register the fault pattern. The proposed approach includes fault detection and classification along with identification of the fault section with respect to UPFC location in one of the double-circuit transmission line. The extensive test results indicate that the proposed differential relaying scheme is highly reliable in registering fault patterns in UPFC based transmission line including wide variations in operating parameters of the power network. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:404 / 417
页数:14
相关论文
共 50 条
  • [1] Fast Discrete S-transform based Differential Relaying Scheme for UPFC Compensated Parallel Line
    Tripathy, L. N.
    Samantaray, S. R.
    Jena, Manas Kumar
    Mishra, S. K.
    2015 INTERNATIONAL CONFERENCE ON ELECTRICAL, ELECTRONICS, SIGNALS, COMMUNICATION AND OPTIMIZATION (EESCO), 2015,
  • [2] DWT approach based differential relaying scheme for single circuit and double circuit transmission line protection including STATCOM
    Mishra, S. K.
    Tripathy, L. N.
    Swain, S. C.
    AIN SHAMS ENGINEERING JOURNAL, 2019, 10 (01) : 93 - 102
  • [3] Time-frequency transform-based differential scheme for microgrid protection
    Kar, Susmita
    Samantaray, Subhransu Rajan
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2014, 8 (02) : 310 - 320
  • [4] Double-circuit transmission line based on interconnection of sequence networks
    Li, Botong
    Li, Yongli
    Li, Hongbo
    Su, Bin
    Li, Youyi
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2010, 34 (09): : 53 - 58
  • [5] Differential relaying scheme for tapped transmission line connecting UPFC and wind farm
    Tripathy, L. N.
    Jena, Manas Kumar
    Samantaray, S. R.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2014, 60 : 245 - 257
  • [6] A single-end directional relaying scheme for double-circuit transmission line using fuzzy expert system
    Kumar, A. Naresh
    Sanjay, Ch.
    Chakravarthy, M.
    COMPLEX & INTELLIGENT SYSTEMS, 2020, 6 (02) : 335 - 346
  • [7] A single-end directional relaying scheme for double-circuit transmission line using fuzzy expert system
    A. Naresh Kumar
    Ch. Sanjay
    M. Chakravarthy
    Complex & Intelligent Systems, 2020, 6 : 335 - 346
  • [8] Percentage differential protection of double-circuit line using wavelet transform
    Bhalja, Bhavesh
    Maheshwari, R. P.
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2007, 35 (08) : 945 - 954
  • [9] Fast S-transform based distance relaying in transmission line
    Samantaray, S. R.
    ELECTRIC POWER SYSTEMS RESEARCH, 2013, 95 : 268 - 274
  • [10] Current-traveling-wave-based protection of double-circuit transmission line
    Li, You-Yi
    Dong, Xin-Zhou
    Sun, Yuan-Zhang
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2002, 22 (11): : 6 - 10