Impact of an internal heat exchanger on a transcritical CO2 heat pump under optimal pressure conditions Optimal-pressure performance of CO2 heat pump with IHX

被引:15
|
作者
Oton-Martinez, Ramon A. [2 ]
Illan-Gomez, Fernando [1 ]
Garcia-Cascales, Jose R. [1 ]
Velasco, F. J. S. [1 ]
Haddouche, M. Reda [1 ]
机构
[1] Univ Politecn Cartagena, Dept Thermal & Fluid Engn, Cartagena 30202, Spain
[2] Univ Politecn Cartagena, Ctr Univ Defensa, C Coronel Lopez Pena S-N, Murcia 30720, Spain
关键词
CO < sub > 2 <; sub > heat hump; R744; Space heating; Internal heat exchanger; Hot water generation; Optimal pressure; CARBON-DIOXIDE; SYSTEMS; EQUATION; CYCLE;
D O I
10.1016/j.applthermaleng.2022.118991
中图分类号
O414.1 [热力学];
学科分类号
摘要
Transcritical R744 (CO2) heat pumps are a low-GWP high-efficiency alternative for domestic hot water gener-ation and space heating. For high set-point temperatures, however, the COP drops and the optimum operating pressure increases. For this reason, the effect on system performance achieved by the inclusion of an Intermediate Heat Exchanger (IHX) is analyzed in depth. This is carried out by means of a numerical-experimental approach in which the effectiveness of the IHX and other characteristic parameters of the heat pump cycle are studied as a function of the IHX heat transfer area. The numerical modeling of the heat pump components is implemented for transient simulations of system heating-up process. Experimental tests with and without IHX are carried out with a water-to-water heat pump that feeds an accumulator tank, to assess its influence on the system's COP and the electrical consumption. Simulations reveal that improving the efficiency of the IHX, by increasing the exchange area, improves the system's performance. For the cases with higher IHX exchange area, the optimum pressure in the system is lower. For the heating experiments, the resulting thermodynamic COP is 7.55 % higher in the case with IHX, while the effective COP increases by 4.26 %. In consequence, the use of the IHX is recommended for the conditions analyzed.
引用
收藏
页数:12
相关论文
共 50 条
  • [1] Optimal discharge pressure in transcritical CO2 heat pump water heater with internal heat exchanger based on pinch point analysis
    Ye, Zuliang
    Wang, Yikai
    Song, Yulong
    Yin, Xiang
    Cao, Feng
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2020, 118 : 12 - 20
  • [2] Experimental investigation of the optimal heat rejection pressure for a transcritical CO2 heat pump water heater
    Qi, Peng-Cheng
    He, Ya-Ling
    Wang, Xiao-Lin
    Meng, Xiang-Zhao
    [J]. APPLIED THERMAL ENGINEERING, 2013, 56 (1-2) : 120 - 125
  • [3] A study on the compressor frequency and optimal discharge pressure of the transcritical CO2 heat pump system
    Qin, Xiang
    Liu, Huadong
    Meng, Xiangrui
    Wei, Xinli
    Zhao, Linghua
    Yang, Lingxiao
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 99 : 101 - 113
  • [4] Optimal compressor discharge pressure and performance characteristics of transcritical CO2 heat pump for crude oil heating
    Li, Conghui
    Jiang, Peixue
    Zhu, Yinhai
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2022, 144 : 99 - 107
  • [5] Experimental and theoretical analysis of the optimal high pressure and peak performance coefficient in transcritical CO2 heat pump
    Qin, Xiang
    Zhang, Fan
    Zhang, Dongwei
    Gao, Zhao
    Tang, Songzhen
    [J]. APPLIED THERMAL ENGINEERING, 2022, 210
  • [6] Optimal compressor discharge pressure and performance characteristics of transcritical CO2 heat pump for crude oil heating
    Li, Conghui
    Jiang, Peixue
    Zhu, Yinhai
    [J]. International Journal of Refrigeration, 2022, 144 : 99 - 107
  • [7] The Influence of Internal Heat Exchanger on the Performance of Transcritical CO2 Water Source Heat Pump Water Heater
    Feng, Fan
    Zhang, Ze
    Liu, Xiufang
    Liu, Changhai
    Hou, Yu
    [J]. ENERGIES, 2020, 13 (07)
  • [8] Experimental investigation on the influence of internal heat exchanger in a transcritical CO2 heat pump water heater
    Cao, Feng
    Ye, Zuliang
    Wang, Yikai
    [J]. APPLIED THERMAL ENGINEERING, 2020, 168 (168)
  • [9] The evaluation of optimal discharge pressure in a water-precooler-based transcritical CO2 heat pump system
    Song, Yulong
    Cao, Feng
    [J]. APPLIED THERMAL ENGINEERING, 2018, 131 : 8 - 18
  • [10] Analysis of internal heat exchanger for heat pump system using CO2
    Kim, OJ
    Kim, YY
    Hong, YJ
    Lee, KH
    [J]. 2ND ASIAN CONFERENCE ON REFRIGERATION AND AIR-CONDITIONING, PROCEEDINGS: NEW CONTRIBUTION TO ASIAN SUSTAINABLE DEVELOPMENT, 2004, : 229 - 237