PRESSURE DROP IN R-245FA CONDENSATION IN TUBES FITTED WITH COILED-WIRE INSERTS

被引:1
|
作者
Khatua, Ajit Kumar [1 ]
Kumar, Parmanand [1 ]
Singh, Hari Narayan [1 ]
机构
[1] Natl Inst Technol, Dept Mech Engn, Jamshedpur, Bihar, India
关键词
rough surface; two-phase flow; structured roughness and condensation enhancement hydrodynamics; HEAT-TRANSFER; PREDICTION;
D O I
10.1615/JEnhHeatTransf.2015012442
中图分类号
O414.1 [热力学];
学科分类号
摘要
This study examines pressure drop during condensation of R-245fa pure vapor inside two separate horizontal coaxial double-pipe test sections with coiled-wire inserts assembled in series. For each inserted tube and the plain tube, data were collected for mass fluxes in the range of 100 to 250 kg/m(2)s in increments of 50 kg/m(2)s for vapor qualities ranging from 0.1 to 0.9. It was observed that the pressure drop inside a horizontal tube is a complex function of vapor quality, mass velocity, and coil pitch, and in a low vapor quality region. The highest pressure drop ratio was 13.33 for a coil pitch of 3.0 mm at a refrigerant mass flux of 150 kg/m(2)s.
引用
收藏
页码:425 / 438
页数:14