Derating of a distribution transformer for non-linear loads

被引:10
|
作者
Sharifian, MBB
Faiz, J
机构
[1] Univ Tehran, Fac Engn, Dept Elect & Comp Engn, Tehran, Iran
[2] Univ Tabriz, Fac Elect & Comp Engn, Power Engn Dept, Tabriz, Iran
来源
关键词
non-linear loads; distribution transformer; finite element method;
D O I
10.1002/etep.75
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper deals with an important problem related to power quality that has been tackled in the literature quite often. The three-phase distribution transformer in electrical power systems is generally installed for supplying loads with rated frequency. Non-linear loads introduce harmonics to the supply and result in a different performance compared with that of the designed transformer. In this paper a three-phase 50kVA distribution transformer is modeled using the finite element (FE) method in order to evaluate its losses under non-linear loads. Comparison of the FE computation results with the analytical standard method results shows that the latter method leads to a more conservative estimate of the transformer derating. Copyright (c) 2005 John Wiley & Sons, Ltd.
引用
收藏
页码:189 / 203
页数:15
相关论文
共 50 条
  • [1] Derating of distribution transformers under non-linear loads using a combined analytical-finite elements approach
    Ghazizadeh, Milad
    Faiz, Jawad
    Oraee, Hashem
    [J]. IET ELECTRIC POWER APPLICATIONS, 2016, 10 (08) : 779 - 787
  • [2] Temperature Prediction in Cast-Resin Transformer Due to Non-Linear Loads
    Azizian, Davood
    [J]. JOURNAL OF ELECTRICAL SYSTEMS, 2014, 10 (03) : 238 - 249
  • [3] Role of DSTATCOM in Distribution Network with Non-Linear and Active Loads
    Kaur, Savreet
    Nijhawan, Parag
    [J]. 2016 7TH INDIA INTERNATIONAL CONFERENCE ON POWER ELECTRONICS (IICPE), 2016,
  • [4] Simulation of large numbers of non-linear loads in distribution systems
    Van den Keybus, J
    Driesen, J
    Bartolive, D
    Belmans, R
    [J]. NINTH INTERNATIONAL CONFERENCE ON HARMONICS AND QUALITY OF POWER PROCEEDINGS, VOLS I - III, 2000, : 515 - 519
  • [5] Analysis of Transformer Derating in the presence of EV Charging and Nonlinear loads in a Radial Distribution System
    Hareesh, Muddamalla
    Bhattacharya, Aniruddha
    Ahmed, Irfan
    [J]. 2022 IEEE 6TH INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS, CATCON, 2022, : 364 - 368
  • [6] Thermal analysis and derating of a power transformer with harmonic loads
    Mikhak-Beyranvand, Morteza
    Faiz, Jawad
    Rezaeealam, Behrooz
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2020, 14 (07) : 1233 - 1241
  • [7] Linear and non-linear wave loads on FPSOs
    Blandeau, F
    François, M
    Malenica, S
    Chen, XB
    [J]. PROCEEDINGS OF THE NINTH (1999) INTERNATIONAL OFFSHORE AND POLAR ENGINEERING CONFERENCE, VOL 1, 1999, 1999, : 252 - 258
  • [8] The measurement and evaluation of distribution transformer losses under non-linear loading
    Damnjanovic, A
    Ferguson, G
    [J]. 2004 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1 AND 2, 2004, : 1416 - 1419
  • [9] Investigation of Harmonic Distortion and Losses in Distribution Systems with Non-Linear Loads
    Wang Kui
    Guan Shuhua
    Hou Qian
    Hou Yuanhong
    Wu Qinfang
    [J]. 2008 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION, VOLS 1 AND 2, 2009, : 30 - +
  • [10] Performance evaluation of digital filters in distribution static compensator for non-linear loads
    Chittora, Prakash
    Singh, Alka
    Singh, Madhusudan
    [J]. IET POWER ELECTRONICS, 2017, 10 (14) : 1915 - 1923