Water Level Control of Steam Generator in Nuclear Power Plant Based on Intelligent MFAC-PID

被引:0
|
作者
Du, Yonglu [1 ]
Li, Haotian [1 ]
Fei, Minrui [1 ]
Wang, Ling [1 ]
Zhang, Pinggai [1 ]
Zhao, Wanqing [2 ]
机构
[1] Shanghai Univ, Shanghai Key Lab Power Stn Automat Technol, Sch Mechatron Engn & Automat, Shanghai 200072, Peoples R China
[2] Univ East Anglia, Sch Comp Sci, Norwich NR4 7TJ, Norfolk, England
关键词
Steam generator; Water level control; Human learning optimization; Model-free adaptive control; Data-driven;
D O I
暂无
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
As an indispensable key equipment in nuclear power plants, the water level control of steam generators directly affects the quality of exported steam, which is critical to the safe operation of nuclear power plant units. The controlled object, water level control system often has the characteristics of time lag, inertia and time-varying, and it is difficult to achieve the desired control effect using the classical control method. To solve the above problem, this paper proposes an intelligent model-free adaptive control and PID (IMFAC-PIDA) approach, in which an improved MFAC controller is designed to enhance the performance of the system, and the adaptive simplified human learning optimization (ASHLO) algorithm is used to optimize the parameter of the designed controller. Finally, the simulation experiments show that the proposed IMFAC-PIDA significantly outperforms other four control approaches.
引用
收藏
页码:2549 / 2554
页数:6
相关论文
共 50 条
  • [1] Water Level Control of Nuclear Power Plant Steam Generator Based on Intelligent Virtual Reference Feedback Tuning
    Han, Zhi
    Qi, Hu
    Wang, Ling
    Menhas, Muhammad Ilyas
    Fei, Minrui
    [J]. ADVANCES IN GREEN ENERGY SYSTEMS AND SMART GRID, PART III, 2018, 925 : 14 - 23
  • [2] Level control in the steam generator of a nuclear power plant
    Kothare, MV
    Mettler, B
    Morari, M
    Bendotti, P
    Falinower, CM
    [J]. IEEE TRANSACTIONS ON CONTROL SYSTEMS TECHNOLOGY, 2000, 8 (01) : 55 - 69
  • [3] PID control for nuclear steam generator water level based on genetic algorithm
    Li, Feng-Yu
    Zhang, Da-Fa
    Wang, Shao-Ming
    Cui, Chang-Ling
    Liu, Ying
    [J]. Yuanzineng Kexue Jishu/Atomic Energy Science and Technology, 2008, 42 (SUPPL.): : 137 - 141
  • [4] Level control in the steam generator of a nuclear power plant
    Kothare, MV
    Mettler, B
    Morari, M
    Bendotti, P
    Falinower, CM
    [J]. PROCEEDINGS OF THE 35TH IEEE CONFERENCE ON DECISION AND CONTROL, VOLS 1-4, 1996, : 4851 - 4856
  • [5] Research on Steam Generator Water Level Control System Based on Nuclear Power Plant Simulator
    Guo, Jianghua
    [J]. LIFE SYSTEM MODELING AND INTELLIGENT COMPUTING, PT I, 2010, 97 : 1 - 7
  • [6] Soft Constrained MPC on Water Level Control in Steam Generator of a Nuclear Power Plant
    Jiang, Di
    Liu, Xiang-Jie
    Kong, Xiao-Bing
    [J]. Zidonghua Xuebao/Acta Automatica Sinica, 2019, 45 (06): : 1111 - 1121
  • [7] Performance Assessment for the Water Level Control System in Steam Generator of the Nuclear Power Plant
    Zhang Zhi
    Hu Lisheng
    [J]. 2011 30TH CHINESE CONTROL CONFERENCE (CCC), 2011, : 5842 - 5847
  • [8] Performance assessment for the water level control system in steam generator of the nuclear power plant
    Zhang, Zhi
    Hu, Li-Sheng
    [J]. ANNALS OF NUCLEAR ENERGY, 2012, 45 : 94 - 105
  • [9] Fractional order PID control of steam generator water level for nuclear steam supply systems
    Salehi, Ahmad
    Safarzadeh, Omid
    Kazemi, Mohammad Hossein
    [J]. NUCLEAR ENGINEERING AND DESIGN, 2019, 342 : 45 - 59
  • [10] Evolutionary optimization of fuzzy systems for water level control in the steam generator of nuclear power plant
    Kim, MS
    Kim, CH
    Rohan, M
    Lee, JJ