INFLUENCES OF THE PLUGGING IN CONDENSER COILS AND EVAPORATOR FILTERS ON THE PERFORMANCE OF WALL TYPE SPLIT AIR CONDITIONING SYSTEM

被引:0
|
作者
Simsek, Erdogan [1 ]
Bilgili, Mehmet [2 ]
Yasar, Abdulkadir [1 ]
Sahin, Besir [3 ]
机构
[1] Cukurova Univ, Adana Meslek Yuksekokulu, Elekt & Enerji Bolumu, Adana, Turkey
[2] Cukurova Univ, Ceyhan Muhendislik Fak, Makine Muhendisligi Bolumu, Adana, Turkey
[3] Cukurova Univ, Muhendislik Mimarlik Fak, Makine Muhendisligi Bolumu, Adana, Turkey
关键词
Air flow; Split air conditioner; Periodic maintenance; Evaporator plugging; Condenser plugging;
D O I
暂无
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
In this study, influences of the plugging in the evaporator filters and condenser coils on the system performance were examined in a wall type split air conditioning system. In an original air conditioning system designed for digital experimental measurements, the changes in operating parameters such as temperature, pressure, thermal capacity, compressor power, coefficients performance for heating and cooling were investigated by creating plugging on the evaporator filters and condenser coil, proportionally. According to the obtained results, in the case of restricting the evaporator coil performance with 50% and 100% due to the air filters plugging, the COP of air conditioning system decreased as 3.32% and 11.19%, respectively. Furthermore, in the event of 50% and 100% plugging caused by bending, crushing and contamination of condenser coil, the COP of air conditioning system decreased as 12.07% and 47.38%. The results indicate that surface maintenance of evaporator filters, condenser and evaporator coils need to be done, regularly. Therein, performing heating and cooling processes of wall type split air conditioning with less energy will be provided to operate without any problems during a long period of time.
引用
收藏
页码:375 / 383
页数:9
相关论文
共 50 条
  • [1] DESIGN CONSIDERATIONS FOR AIR-CONDITIONING EVAPORATOR AND CONDENSER COILS
    PATE, MB
    [J]. TWO-PHASE FLOW HEAT EXCHANGES: THERMAL-HYDRAULIC FUNDAMENTALS AND DESIGN, 1988, 143 : 849 - 884
  • [2] ANALYSIS OF THE PERFORMANCE OF THE EVAPORATOR OF AUTOMOTIVE AIR CONDITIONING SYSTEM
    Shen, C. C.
    Lu, J. H.
    [J]. INTERNATIONAL JOURNAL OF AUTOMOTIVE TECHNOLOGY, 2014, 15 (01) : 19 - 38
  • [3] Improvement of Performance of Air Conditioning System with Modification in Condenser
    Mani, Purusothaman
    Madhubalan, G.
    Parameswaran, T.
    Ponnappan, Venkatesan Sorakka
    Gnanamani, Senthilkumar
    Natesan, Valarmathi Thirumalai
    [J]. 3RD INTERNATIONAL CONFERENCE ON FRONTIERS IN AUTOMOBILE AND MECHANICAL ENGINEERING (FAME 2020), 2020, 2311
  • [4] Analysis of the performance of the evaporator of automotive air conditioning system
    C. C. Shen
    J. H. Lu
    [J]. International Journal of Automotive Technology, 2014, 15 : 19 - 38
  • [5] An experimental study on the effect of room setpoint temperature, and evaporator/condenser fouling on performance of a ductless split type air conditioner
    Niknami, Mohammad
    Maniee, Siavash
    Rad, Ali Asghar Farokhi
    Mansoori, Shabnam
    Yahaghi, Masoud
    [J]. ENERGY AND BUILDINGS, 2024, 322
  • [6] The performance of a mobile air conditioning system with a water cooled condenser
    Di Battista, Davide
    Cipollone, Roberto
    [J]. 33RD UIT (ITALIAN UNION OF THERMO-FLUID DYNAMICS) HEAT TRANSFER CONFERENCE, 2015, 655
  • [7] The performance study of a split type air conditioning system in the tropics, as affected by weather
    Yau, Y. H.
    Pean, H. L.
    [J]. ENERGY AND BUILDINGS, 2014, 72 : 1 - 7
  • [8] Experimental Investigation on the Performance of Condenser for Charge Reduction of HC-290 in a Split Air-Conditioning System
    Saravanan, Ayyamperumal Lalitha
    Lal, Dhasan Mohan
    Selvam, Chandrasekaran
    [J]. HEAT TRANSFER ENGINEERING, 2020, 41 (17) : 1499 - 1511
  • [9] Experimental Investigations on the Performance Enhancement Using Minichannel Evaporator with Integrated Receiver-Dryer Condenser in an Automotive Air Conditioning System
    Prabakaran, Rajendran
    Lal, Dhasan Mohan
    Prabhakaran, Arumugam
    Kumar, Jha Kaushal
    [J]. HEAT TRANSFER ENGINEERING, 2019, 40 (08) : 667 - 678
  • [10] Experimental study on the performance of evaporator and condenser heat exchangers in a train-used air conditioning group
    Xia, JJ
    Teodorese, V
    Georges, B
    Mazy, C
    Lebrun, J
    [J]. PROCEEDINGS OF THE 4TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS 1 AND 2, 2003, : 750 - 759