Performance analysis and evaluation of a triple-effect ammonia-water absorption-refrigeration system

被引:18
|
作者
Ratlamwala, T. A. H. [1 ]
Dincer, I. [1 ]
Gadalla, M. A. [2 ]
机构
[1] Univ Ontario Inst Technol, Fac Engn & Appl Sci, Oshawa, ON L1H 7K4, Canada
[2] Univ City Sharjah, Amer Univ Sharjah, Sharjah, U Arab Emirates
关键词
energy; exergy; efficiency; absorption system; refrigeration; THERMODYNAMIC ANALYSIS; ENERGY;
D O I
10.1002/er.2998
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In this paper, a comprehensive thermodynamic analysis of the triple-effect absorption-refrigeration system using ammonia-water solution is carried out in order to investigate the effect of different operating conditions on the coefficient of performance (COPs) and rate of heat input to the system. It is found that both energetic and exergetic COPs vary from 0.31 to 1.867 and 0.165 to 0.964, respectively, as the inlet temperature to the high-temperature generator (HTG), cooling load, and concentration of the strong solution are increased, while the rate of heat input varies from 65.5 to 71.5%. Moreover, increase in the mixture exit temperature from the HTG, concentration of the weak solution, and mass flow rate result in the variation of energetic and exergetic COPs from 2.49 to 0.68 and 1.0 to 0.23, respectively, which results in the change of rate of heat input from 7.1 to 28.5 kW. When the outdoor temperature is increased, the exergetic COP varies from 0.43 to 1.23. Copyright (c) 2013 John Wiley & Sons, Ltd.
引用
收藏
页码:475 / 483
页数:9
相关论文
共 50 条
  • [1] Performance analysis and evaluation of a commercial absorption-refrigeration water-ammonia (ARWA) system
    Darwish, N. A.
    Al-Hashimi, S. H.
    Al-Mansoori, A. S.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (07): : 1214 - 1223
  • [2] Energy analysis of an ammonia-water absorption refrigeration system
    Dincer, I
    Dost, S
    [J]. ENERGY SOURCES, 1996, 18 (06): : 727 - 733
  • [3] Performance analysis of ammonia-water absorption refrigeration Gax cycle
    Liao, JM
    Du, K
    [J]. ENERGY AND ENVIRONMENT, VOLS 1 AND 2, 2003, : 1408 - 1412
  • [4] Modelling and performance evaluation of a low-temperature ammonia-water absorption refrigeration system
    Ge, Y. T.
    Tassou, S. A.
    Chaer, I.
    [J]. INTERNATIONAL JOURNAL OF LOW-CARBON TECHNOLOGIES, 2009, 4 (02) : 68 - 77
  • [5] Performance analysis of ammonia-water absorption/compression combined refrigeration cycle
    Bao, Shuaiyang
    Du, Kai
    Cai, Xingchen
    Niu, Xiaofeng
    Wu, Yunlong
    [J]. Journal of Southeast University (English Edition), 2014, 30 (01) : 60 - 67
  • [6] THERMAL PERFORMANCE OF AN AMMONIA-WATER REFRIGERATION SYSTEM
    MANRIQUE, JA
    [J]. INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 1991, 18 (06) : 779 - 789
  • [7] THERMODYNAMIC SIMULATION OF AMMONIA-WATER ABSORPTION REFRIGERATION SYSTEM
    Sathyabhama, A.
    Babu, T. P. Ashok
    [J]. THERMAL SCIENCE, 2008, 12 (03): : 45 - 53
  • [8] A computational model of ammonia-water absorption refrigeration system
    Al-Shemmeri, T
    Wang, YD
    [J]. CRYOGENICS AND REFRIGERATION - PROCEEDINGS OF ICCR'2003, 2003, : 393 - 396
  • [9] Dynamic Simulation of an Ammonia-water Absorption Refrigeration System
    Cai, Weihua
    Sen, Mihir
    Paolucci, Samuel
    [J]. INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2012, 51 (04) : 2070 - 2076
  • [10] Thermodnamic analysis on an adsorption-absorption cascading triple-effect refrigeration system
    Jiangzhou, S
    Wang, RZ
    Lu, YZ
    Wang, ZG
    [J]. PROCEEDINGS OF THE INTERNATIONAL SORPTION HEAT PUMP CONFERENCE, 2002, : 561 - 566