Patient Warming Excess Heat: The Effects on Orthopedic Operating Room Ventilation Performance

被引:29
|
作者
Belani, Kumar G. [1 ]
Albrecht, Mark [3 ]
McGovern, Paul D. [4 ]
Reed, Mike [5 ]
Nachtsheim, Christopher [2 ]
机构
[1] Univ Minnesota, Dept Anesthesiol, Minneapolis, MN 55455 USA
[2] Univ Minnesota, Carlson Sch Management, Minneapolis, MN 55455 USA
[3] Natl Marrow Donor Program, Minneapolis, MN 55413 USA
[4] Medway Maritime Hosp, Gillingham, Kent, England
[5] Northumbria Healthcare NHS Fdn Trust, Ashington, Northd, England
来源
ANESTHESIA AND ANALGESIA | 2013年 / 117卷 / 02期
关键词
SURGICAL SITE INFECTION; FORCED-AIR; LAMINAR-FLOW; KNEE REPLACEMENT; DEEP INFECTION; JOINT; ANTIBIOTICS; PREVENTION; SYSTEMS; SEPSIS;
D O I
10.1213/ANE.0b013e31825f81e2
中图分类号
R614 [麻醉学];
学科分类号
100217 ;
摘要
BACKGROUND: Patient warming has become a standard of care for the prevention of unintentional hypothermia based on benefits established in general surgery. However, these benefits may not fully translate to contamination-sensitive surgery (i.e., implants), because patient warming devices release excess heat that may disrupt the intended ceiling-to-floor ventilation airflows and expose the surgical site to added contamination. Therefore, we studied the effects of 2 popular patient warming technologies, forced air and conductive fabric, versus control conditions on ventilation performance in an orthopedic operating room with a mannequin draped for total knee replacement. METHODS: Ventilation performance was assessed by releasing neutrally buoyant detergent bubbles (bubbles) into the nonsterile region under the head-side of the anesthesia drape. We then tracked whether the excess heat from upper body patient warming mobilized the bubbles into the surgical site. Formally, a randomized replicated design assessed the effect of device (forced air, conductive fabric, control) and anesthesia drape height (low-drape, high-drape) on the number of bubbles photographed over the surgical site. RESULTS: The direct mass-flow exhaust from forced air warming generated hot air convection currents that mobilized bubbles over the anesthesia drape and into the surgical site, resulting in a significant increase in bubble counts for the factor of patient warming device (P < 0.001). Forced air had an average count of 132.5 versus 0.48 for conductive fabric (P = 0.003) and 0.01 for control conditions (P = 0.008) across both drape heights. Differences in average bubble counts across both drape heights were insignificant between conductive fabric and control conditions (P = 0.87). The factor of drape height had no significant effect (P = 0.94) on bubble counts. CONCLUSIONS: Excess heat from forced air warming resulted in the disruption of ventilation airflows over the surgical site, whereas conductive patient warming devices had no noticeable effect on ventilation airflows. These findings warrant future research into the effects of forced air warming excess heat on clinical outcomes during contamination-sensitive surgery.
引用
收藏
页码:406 / 411
页数:6
相关论文
共 48 条
  • [1] Numerical investigation of the impact of warming blankets on the performance of ventilation systems in the operating room
    Sadeghian, Parastoo
    Duwig, Christophe
    Skoldenberg, Olof
    Tammelin, Ann
    Hosseini, Ardalan Rahimi
    Sadrizadeh, Sasan
    [J]. ADVANCES IN BUILDING ENERGY RESEARCH, 2022, 16 (05) : 589 - 611
  • [2] Performance evaluation of operating room schedules in orthopedic surgery
    Zexian Zeng
    Xiaolei Xie
    Heidi Menaker
    Susan G. Sanford-Ring
    Jingshan Li
    [J]. Flexible Services and Manufacturing Journal, 2018, 30 : 198 - 223
  • [3] Performance evaluation of operating room schedules in orthopedic surgery
    Zeng, Zexian
    Xie, Xiaolei
    Menaker, Heidi
    Sanford-Ring, Susan G.
    Li, Jingshan
    [J]. FLEXIBLE SERVICES AND MANUFACTURING JOURNAL, 2018, 30 (1-2) : 198 - 223
  • [4] Study on Ventilation Performance in Operating Room with Variation Ventilation Design
    Wu, Yan-Lin
    Wu, Yu-Lieh
    Hanifan, Azka Hasya
    [J]. 3RD FORUM IN RESEARCH, SCIENCE, AND TECHNOLOGY (FIRST 2019) INTERNATIONAL CONFERENCE, 2020, 1500
  • [5] Laminar airflow and mixing ventilation: Which is better for operating room airflow distribution near an orthopedic surgical patient?
    Cao, Guangyu
    Nilssen, Anders M.
    Cheng, Zhu
    Stenstad, Liv-Inger
    Radtke, Andreas
    Skogas, Jan Gunnar
    [J]. AMERICAN JOURNAL OF INFECTION CONTROL, 2019, 47 (07) : 737 - 743
  • [6] Performance of ventilation system in a non-standard operating room
    Chow, TT
    Yang, XY
    [J]. BUILDING AND ENVIRONMENT, 2003, 38 (12) : 1401 - 1411
  • [7] Interaction between a local and a general ventilation system for an operating room with patient
    Tacutu, Laurentiu
    Nastase, Ilinca
    Bode, Florin
    Dogeanu, Angel
    Croitoru, Cristiana
    [J]. 2019 INTERNATIONAL CONFERENCE ON ENERGY AND ENVIRONMENT (CIEM), 2019, : 348 - 353
  • [8] Numerical evaluation of the operating room ventilation performance: Ultra-Clean Ventilation (UCV) systems
    Sajadi, B.
    Saidi, M. H.
    Ahmadi, G.
    [J]. SCIENTIA IRANICA, 2019, 26 (04) : 2394 - 2406
  • [9] Effect of forced-air warming on the performance of operating theatre laminar flow ventilation
    Dasari, K. B.
    Albrecht, M.
    Harper, M.
    [J]. ANAESTHESIA, 2012, 67 (03) : 244 - 249
  • [10] Computer modeling of the operating room ventilation performance in connection with surgical site infection
    Sajadi, B.
    Saidi, M. H.
    Ahmadi, G.
    [J]. SCIENTIA IRANICA, 2020, 27 (02) : 704 - 714