A subsynchronous resonance prevention for DFIG-based wind farms

被引:4
|
作者
Fateh, Davood [1 ]
Birjandi, Ali Akbar Moti [1 ]
Guerrero, Josep M. [2 ]
机构
[1] Shahid Rajaee Teacher Training Univ, Fac Engn, Dept Elect Engn, Tehran, Iran
[2] Aalborg Univ, Villum Ctr Res Microgrids CROM, Dept Energy Technol, Aalborg, Denmark
关键词
SSR; DFIG-based wind farm; SSR prevention controller; line series capacitor voltage; FED INDUCTION GENERATOR; SYNCHRONOUS CONTROL INTERACTION; POWER-CONTROL; MITIGATION;
D O I
10.3906/elk-1912-177
中图分类号
TP18 [人工智能理论];
学科分类号
081104 ; 0812 ; 0835 ; 1405 ;
摘要
In this paper, subsynchronous resonance (SSR) instability was accurately analyzed in doubly fed induction generator (DFIG)-based wind farms by the linearization of equations and modal analysis. In addition, the possibility of high compensation for the transmission lines connected to DFIG-based wind farms was provided using a SSR prevention controller (SSRPC). For this purpose, an SSRPC was connected to the output voltage of the grid side converter (GSC) of the DFIG. The GSC output voltage was selected as the connection point of the SSRPC because it directly affects the induction generator effect (IGE) and can be an inhibitor factor in its occurrence. Furthermore, using system dynamic equations and the participation factor, it was shown that the effective factor on subsynchronous mode was the capacitor series voltage of the line, considered an input signal to the SSRPC. To validate the performance of the proposed method, a simulation was performed based on the IEEE SSR first benchmark model using the software MATLAB/Simulink.
引用
收藏
页码:2670 / 2685
页数:16
相关论文
共 50 条
  • [1] Utilizing DFIG-Based Wind Farms for Damping Subsynchronous Resonance in Nearby Turbine-Generators
    Faried, Sherif Omar
    Unal, Irfan
    Rai, Dipendra
    Mahseredjian, Jean
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2013, 28 (01) : 452 - 459
  • [2] Subsynchronous interactions in power networks with multiple DFIG-based wind farms
    Revel, Gustavo
    Alonso, Diego M.
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2018, 165 : 179 - 190
  • [3] Robust subsynchronous interaction damping controller for DFIG-based wind farms
    Mohsen GHAFOURI
    Ulas KARAAGAC
    Houshang KARIMI
    Jean MAHSEREDJIAN
    [J]. Journal of Modern Power Systems and Clean Energy, 2019, 7 (06) : 1663 - 1674
  • [4] An LQR Controller for Damping of Subsynchronous Interaction in DFIG-Based Wind Farms
    Ghafouri, Mohsen
    Karaagac, Ulas
    Karimi, Houshang
    Jensen, Simon
    Mahseredjian, Jean
    Faried, Sherif O.
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2017, 32 (06) : 4934 - 4942
  • [5] Probabilistic Stability Analysis of Subsynchronous Resonance for Series-Compensated DFIG-Based Wind Farms
    Chen, Wuhui
    Xie, Xiaorong
    Wang, Danhui
    Liu, Huakun
    Liu, Hui
    [J]. IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2018, 9 (01) : 400 - 409
  • [6] Robust subsynchronous interaction damping controller for DFIG-based wind farms
    Ghafouri, Mohsen
    Karaagac, Ulas
    Karimi, Houshang
    Mahseredjian, Jean
    [J]. JOURNAL OF MODERN POWER SYSTEMS AND CLEAN ENERGY, 2019, 7 (06) : 1663 - 1674
  • [7] Understanding Subsynchronous Oscillations in DFIG-Based Wind Farms Without Series Compensation
    Xu, Yanhui
    Zhao, Shimeng
    Cao, Yuping
    Sun, Kai
    [J]. IEEE ACCESS, 2019, 7 : 107201 - 107210
  • [8] Multi-parameter bifurcation analysis of subsynchronous interactions in DFIG-based wind farms
    Revel, Gustavo
    Leon, Andres E.
    Alonso, Diego M.
    Moiola, Jorge L.
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2016, 140 : 643 - 652
  • [9] Analysis of Subsynchronous Control Interactions in DFIG-based Wind Farms: ERCOT Case Study
    Mohammadpour, Hossein Ali
    Santi, Enrico
    [J]. 2015 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2015, : 500 - 505
  • [10] Coordinated Control of Wind Energy Conversion Systems for Mitigating Subsynchronous Interaction in DFIG-Based Wind Farms
    Karaagac, Ulas
    Faried, Sherif O.
    Mahseredjian, Jean
    Edris, Abdel-Aty
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2014, 5 (05) : 2440 - 2449