Aging Degree Evaluation for Paper-oil Insulation using the Recovery Voltage Method

被引:34
|
作者
Wolny, Stefan [1 ]
机构
[1] Opole Univ Technol, Fac Elect Engn Automat Control & Comp Sci, Chair Elect Power Engn & Renewable Energy, PL-45758 Opole, Poland
关键词
Power transformer insulation testing; paper insulation; dielectric polarization; relaxation methods; aging; moisture; COLE-COLE MODEL; DIELECTRIC RESPONSE; TRANSFORMERS INSULATION; DOMAIN; POLARIZATION; PARAMETERS; MOISTURE;
D O I
10.1109/TDEI.2015.004796
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The paper presents new diagnostic method applied to assess aging degree for paper-oil insulation used in professional electrical power device, primarily including medium and high power transformers. The described method is based on modified diagnostics using the recovery voltage effect occurring in dielectrics (RVM - Recovery Voltage Methods). Modification of the RVM method applied so far, which is now used only to assess moistening degree for paper-oil insulation in power transformers, consists in a new parametric analysis of recovery voltage time characteristics. Simulation and experimental tests carried out in laboratory conditions for adequately prepared insulation samples have proven that the time-constant of recovery voltage decay (tau(R)_(MIN)) is the most susceptible parameter as regards quantitative change in the function of aging of the examined insulation. This conclusion is also confirmed by statistical studies, in which a multi-parameter variance analysis method has been applied. An original equivalent circuit diagram of the insulation has been used to simulate aging degree of paper-oil insulation samples in numerical tests. The diagram is based on the Cole-Cole type dielectric response model.
引用
收藏
页码:2455 / 2462
页数:8
相关论文
共 50 条