An analysis of the performance of an ejector refrigeration cycle working with R134a

被引:4
|
作者
Memet, F. [1 ]
Preda, A. [1 ]
机构
[1] Constanta Maritime Univ, Fac Naval Electromech, Constanta 900663, Romania
关键词
SYSTEM;
D O I
10.1088/1757-899X/95/1/012035
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
In the context of recent developments in the field of energy, the aspect related to energy consumption is of great importance for specialists. Many industries rely on refrigeration technologies, a great challenge being expressed by attempts in energy savings in this sector. In this respect, efforts oriented towards efficient industrial refrigeration systems have revealed the necessity of a proper design. The most commonly used method of cooling is based on vapor compression cycles. Compared to vapor compression refrigeration systems, an ejector refrigeration system shows an inferior performance, indicated by the Coefficient of Performance of the cycle, but it is more attractive from energy saving point of view. In this respect, the present study deals with a theoretically analysis of an Ejector Refrigeration System, started with the presentation of the typical ejector design. It is stated that ejector refrigeration is a thermally driven system which requires low grade thermal energy for its working. After a short description of the analyzed system, are given equations for thermal loads and Coefficient of Performance calculation, on First Law basis. The working fluid considered in this research is Freon R134a. The developed study is focused on the effect of generating temperature variation on the Coefficient of Performance ( COP) and on the work input to the pump when the cooling effect, the condensation temperature, the evaporation temperature and the reference state temperature are kept constant. Are obtained results in the following conditions: the condensation temperature is t(c) = 33 degrees C, the evaporation temperature is t(e) = 3 degrees C, the reference state temperature is t(o) = 23 degrees C. The generating temperature varies in the range 82 divided by 92 degrees C and the cooling effect is 1 kW. Also, are known the isentropic efficiencies of the ejector, which are 0.90, and the isentropic efficiency of the pump, which is 0.75. Calculation will reveal that the Coefficient of Performance is increasing together with the increase of the generating temperature values, the best COP value being 0.178, in the considered range for the mentioned temperature. In the same time, the generating temperature increase leads to the increase of the work input to the pump.
引用
收藏
页数:5
相关论文
共 50 条
  • [1] Ejector design and theoretical study of R134a ejector refrigeration cycle
    Khalil, A.
    Fatouh, M.
    Elgendy, E.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2011, 34 (07) : 1684 - 1698
  • [2] Performance investigation of an ejector expansion refrigeration system working on different alternative refrigerants to R134a
    Al-Chlaihawi, Kadhim K. Idan
    Al-Rubaye, Ahmed
    Kadhim, Hakim T.
    [J]. AUSTRALIAN JOURNAL OF MECHANICAL ENGINEERING, 2023, 21 (05) : 1806 - 1817
  • [3] Area ratio effects to the performance of air-cooled ejector refrigeration cycle with R134a refrigerant
    Yan Jia
    Cai Wenjian
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2012, 53 (01) : 240 - 246
  • [4] Exergy Analysis of the Combined Ejector - Vapor Compression Refrigeration System Using R134a as Working Fluid
    Kien-Trung Nguyen
    Quoc-An Hoang
    Hiep-Chi Le
    [J]. PROCEEDINGS OF 2018 4TH INTERNATIONAL CONFERENCE ON GREEN TECHNOLOGY AND SUSTAINABLE DEVELOPMENT (GTSD), 2018, : 442 - 447
  • [5] Performance Analysis of Refrigerants R1234yf, R1234ze and R134a in Ejector-Based Refrigeration Cycle
    Yadav, Ajay Kumar
    Neeraj
    [J]. INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2018, 26 (03)
  • [6] Experimental investigation on R134a vapour ejector refrigeration system
    Selvaraju, A.
    Mani, A.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2006, 29 (07): : 1160 - 1166
  • [7] Experimental investigations on a R134a ejector applied in a refrigeration system
    Yan, Jiwei
    Chen, Guangming
    Liu, Chengyan
    Tang, Liming
    Chen, Qi
    [J]. APPLIED THERMAL ENGINEERING, 2017, 110 : 1061 - 1065
  • [8] Study of a solar booster assisted ejector refrigeration system with R134a
    Hernández, JI
    Best, R
    Dorantes, RJ
    Estrada, CA
    [J]. JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 2005, 127 (01): : 53 - 59
  • [9] Seasonal performance optimisation of thermally driven ejector cooling cycles working with R134a
    Exposit Carrillo, J. A.
    Sanchez de La Flor, F. J.
    Salmeron Lissen, J. M.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 104 : 356 - 366
  • [10] Performance of a four-intersecting-vane expander in a R134a refrigeration cycle
    Murthy, Anarghya Ananda
    Norris, Stuart
    Subiantoro, Alison
    [J]. APPLIED THERMAL ENGINEERING, 2022, 209