Predicted vs. actual energy performance of non-domestic buildings: Using post-occupancy evaluation data to reduce the performance gap

被引:498
|
作者
Menezes, Anna Carolina [1 ,2 ]
Cripps, Andrew [1 ]
Bouchlaghem, Dino [2 ]
Buswell, Richard [2 ]
机构
[1] AECOM, London WC1V 6QS, England
[2] Univ Loughborough, Ctr Innovat & Collaborat Construct Engn, Loughborough LE11 3TU, Leics, England
关键词
Building energy modelling; Energy benchmarks; Energy performance; Performance gap; Post-occupancy evaluation;
D O I
10.1016/j.apenergy.2011.11.075
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
With the increasing demand for more energy efficient buildings, the construction industry is faced with the challenge to ensure that the energy performance predicted during the design stage is achieved once a building is in use. There is, however, significant evidence to suggest that buildings are not performing as well as expected and initiatives such as PROBE and CarbonBuzz aim to illustrate the extent of this so called 'performance gap'. This paper discusses the underlying causes of discrepancies between energy modelling predictions and in-use performance of occupied buildings (after the twelve month liability period). Many of the causal factors relate to the use of unrealistic input parameters regarding occupancy behaviour and facilities management in building energy models. In turn, this is associated with the lack of feedback to designers once a building has been constructed and occupied. The paper aims to demonstrate how knowledge acquired from Post-Occupancy Evaluation (POE) can be used to produce more accurate energy performance models. A case study focused specifically on lighting, small power and catering equipment in a high density office building is analysed and presented. Results show that by combining monitoring data with predictive energy modelling, it was possible to increase the accuracy of the model to within 3% of actual electricity consumption values. Future work will seek to use detailed POE data to develop a set of evidence based benchmarks for energy consumption in office buildings. It is envisioned that these benchmarks will inform designers on the impact of occupancy and management on the actual energy consumption of buildings. Moreover, it should enable the use of more realistic input parameters in energy models, bringing the predicted figures closer to reality. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:355 / 364
页数:10
相关论文
共 28 条
  • [1] Mind the Gap: Predicted vs. Actual Performance of Green Buildings
    Pollard, Brett
    [J]. ENVIRONMENT DESIGN GUIDE, 2011, (66)
  • [2] Managing the risk of the energy performance gap in non-domestic buildings
    Thompson, David
    Burman, Esfand
    Mumovic, Dejan
    Davies, Mike
    [J]. BUILDING SERVICES ENGINEERING RESEARCH & TECHNOLOGY, 2022, 43 (01): : 57 - 88
  • [3] Post-occupancy evaluation of non-domestic buildings using passive downdraught evaporative cooling in south-west USA
    Rosa Schiano-Phan
    [J]. ARCHITECTURAL SCIENCE REVIEW, 2012, 55 (04) : 320 - 340
  • [4] Evaluating energy performance in non-domestic buildings: A review
    Borgstein, E. H.
    Lamberts, R.
    Hensen, J. L. M.
    [J]. ENERGY AND BUILDINGS, 2016, 128 : 734 - 755
  • [6] Post-occupancy evaluation of the actual performance of a low-carbon building
    Qiao, Jun
    Zhang, Xian
    Hao, Cuicai
    Liu, Shaoliang
    Zhang, Yulong
    Xing, Kaijie
    Yang, Peiyuan
    [J]. ENERGY REPORTS, 2023, 10 : 228 - 243
  • [7] A Review of the Regulatory Energy Performance Gap and Its Underlying Causes in Non-domestic Buildings
    van Dronkelaar C.
    Dowson M.
    Spataru C.
    Mumovic D.
    [J]. Frontiers in Mechanical Engineering, 2016, 1
  • [8] THE POST-OCCUPANCY DILEMMA IN GREEN-RATED BUILDINGS: A PERFORMANCE GAP ANALYSIS
    Li, Hongyang
    Li, Chuting
    Skitmore, Martin
    He, Tingen
    Jiang, Tingting
    [J]. JOURNAL OF GREEN BUILDING, 2022, 17 (03): : 259 - 275
  • [9] Mind the Gap:Predicted vs.Actual Performance of Green Buildings
    Brett Pollard
    [J]. 施工技术(中英文), 2012, 41 (03) : 1 - 8
  • [10] Experimental monitoring and post-occupancy evaluation of a non-domestic solar building in the central region of Argentina
    Filippin, C.
    Flores Larsen, S.
    Marek, L.