Characterization and comprehension of corona partial discharge in air under power frequency to very low frequency voltage

被引:10
|
作者
Zhou, Yuanxiang [1 ]
Zhou, Zhongliu [1 ]
Zhang, Ling [1 ]
Zhang, Yunxiao [1 ]
Mo, Yajun [1 ]
Sun, Jiantao [2 ]
机构
[1] Tsinghua Univ, Dept Elect Engn, State Key Lab Elect Power Syst, Beijing 100084, Peoples R China
[2] China Elect Power Res Inst, Beijing 100192, Peoples R China
来源
PLASMA SCIENCE & TECHNOLOGY | 2018年 / 20卷 / 05期
关键词
corona; partial discharge; low frequency voltage; impulse current method; statistical parameters; 0.1; HZ; ELECTRIC-FIELD; RECOGNITION; INSULATION;
D O I
10.1088/2058-6272/aaa479
中图分类号
O35 [流体力学]; O53 [等离子体物理学];
学科分类号
070204 ; 080103 ; 080704 ;
摘要
For the partial discharge test of electrical equipment with large capacitance, the use of low-frequency voltage instead of power frequency voltage can effectively reduce the capacity requirements of test power supply. However, the validity of PD test under low frequency voltage needs to be evaluated. In order to investigate the influence of voltage frequency on corona discharge in the air, the discharge test of the tip-plate electrode under the frequency from 50 to 0.1 Hz is carried out based on the impulse current method. The results show that some of the main features of corona under low frequency do not change. The magnitude of discharge in a positive half cycle is obviously larger than that in a negative cycle. The magnitude of discharge and interval in positive cycle are random, while that in negative cycle are regular. With the decrease of frequency, the inception voltage increases. The variation trend of maximum and average magnitude and repetition rate of the discharge in positive and negative half cycle with the variation of voltage frequency and magnitude is demonstrated, with discussion and interpretation from the aspects of space charge transportation, effective discharge time and transition of discharge modes. There is an obvious difference in the phase resolved pattern of partial discharge and characteristic parameters of discharge patterns between power and low frequency. The experimental results can be the reference for mode identification of partial discharge under low frequency tests. The trend of the measured parameters with the variation of frequency provides more information about the insulation defect than traditional measurements under a single frequency (usually 50 Hz). Also it helps to understand the mechanism of corona discharge with an explanation of the characteristics under different frequencies.
引用
收藏
页数:9
相关论文
共 50 条
  • [1] Characterization and comprehension of corona partial discharge in air under power frequency to very low frequency voltage
    周远翔
    周仲柳
    张灵
    张云霄
    莫雅俊
    孙建涛
    [J]. Plasma Science and Technology, 2018, 20 (05) : 121 - 129
  • [2] Characterization and comprehension of corona partial discharge in air under power frequency to very low frequency voltage
    周远翔
    周仲柳
    张灵
    张云霄
    莫雅俊
    孙建涛
    [J]. Plasma Science and Technology, 2018, (05) - 129
  • [3] Corona Discharge under Non-Sinusoidal Voltage Excitation at Very Low Frequency
    Morsalin, S.
    Phung, B. T.
    [J]. 2018 12TH INTERNATIONAL CONFERENCE ON THE PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS (ICPADM 2018), 2018, : 653 - 656
  • [4] Partial Discharge Behaviors in Cavities under Square Voltage Excitation at Very Low Frequency
    Nguyen, H. V. P.
    Phung, B. T.
    Blackburn, T.
    [J]. 2016 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD), 2016, : 866 - 869
  • [5] A Comparative Study of Partial Discharges Under Power and Very Low Frequency Voltage Excitation
    Dao, Thinh
    Phung, B. T.
    Blackburn, T.
    Nguyen, H. V. P.
    [J]. 2014 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2014, : 164 - 167
  • [6] Investigation of Corona Partial Discharge Characteristics under Variable Frequency and Air Pressure
    Esfahani, Ali Nasr
    Shahabi, Saeed
    Stone, Greg
    Kordi, Behzad
    [J]. 2018 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2018, : 31 - 34
  • [7] Partial Discharge Characterization of Cross-Linked Polyethylene Medium Voltage Power Cable Termination Defects at Very Low Frequency (0.1 Hz) and Power Frequency Test Voltages
    Fynes-Clinton, Daniel
    Nyamupangedengu, Cuthbert
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2016, 32 (04) : 15 - 23
  • [8] Comparison of the Characteristics of Corona Discharge in the Oil under Low and Power Frequency Voltage by Impulse-Current Method
    Zhou, Yuanxiang
    Zhou, Zhongliu
    Guo, Shaowei
    Niu, Zheng
    Zhang, Ling
    [J]. Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2019, 34 (01): : 160 - 169
  • [9] Feature Extraction and Comprehension of Partial Discharge Characteristics in Transformer Oil from Rated AC Frequency to Very Low Frequency
    Zhou, Zhongliu
    Zhou, Yuanxiang
    Huang, Xin
    Zhang, Yunxiao
    Wang, Mingyuan
    Guo, Shaowei
    [J]. ENERGIES, 2018, 11 (07)
  • [10] Comparison of Air Corona PD Characteristics under Low and Power Frequency Voltage by Impulse-Current Method
    Zhou, Yuanxiang
    Zhou, Zhongliu
    Guo, Shaowei
    Niu, Zheng
    Huang, Meng
    Li, Shaohua
    [J]. 2017 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENON (CEIDP), 2017, : 339 - 342