Effects of inlet relative humidity and inlet temperature on the performance of counterflow wet cooling tower based on exergy analysis

被引:62
|
作者
Muangnoi, Thirapong [2 ]
Asvapoositkul, Wanchai [1 ]
Wongwises, Somchai [1 ]
机构
[1] King Mongkuts Univ Technol Thonburi, Dept Mech Engn, Bangkok 10140, Thailand
[2] King Mongkuts Univ Technol Thonburi, Joint Grad Sch Energy & Environm, Bangkok 10140, Thailand
关键词
exergy analysis; wet cooling tower; exergy change; second law efficiency;
D O I
10.1016/j.enconman.2008.03.019
中图分类号
O414.1 [热力学];
学科分类号
摘要
The purpose of this study is to analyze the influence of the ambient temperature and humidity on the performance of a counterflow wet cooling tower according to the second law, exergy analysis, of thermodynamics. First, the properties of water and air flow through the tower were predicted and validated by the experiment. Exergy analysis then has been carried out for investigating the cooling tower performance with various inlet air conditions, relative humidity and dry bulb temperature, while the water side condition is kept constant. According to the analysis in this paper, the similar result in terms of required dry air flow rate, exergy change of water and that of air, exergy destruction and second law efficiency were obtained for the various inlet air conditions. The exergy change of water Delta x(w) is higher than that of air Delta X-air, since Delta x(w) is the available energy of water to supply to air throughout the tower while Delta x(air), is the available energy of air to recover or utilize that supplied by water. It reveals that Delta x(air) is dominated by the exergy change of air due to evaporative heat transfer. In addition, it,gives a clearer explanation of the cooling tower performance and gives clear trends for optimization. (c) 2008 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2795 / 2800
页数:6
相关论文
共 50 条
  • [1] An exergy analysis on the performance of a counterflow wet cooling tower
    Muangnoi, Thirapong
    Asvapoositkul, Wanchai
    Wongwises, Somchai
    [J]. APPLIED THERMAL ENGINEERING, 2007, 27 (5-6) : 910 - 917
  • [2] Inlet losses in counterflow wet-cooling towers
    de Villiers, E
    Kröger, DG
    [J]. JOURNAL OF ENGINEERING FOR GAS TURBINES AND POWER-TRANSACTIONS OF THE ASME, 2001, 123 (02): : 460 - 464
  • [3] Influence factor analysis of inlet spray on a natural draft wet cooling tower
    Cheng, W.
    Hou, C.
    [J]. BULGARIAN CHEMICAL COMMUNICATIONS, 2016, 48 : 177 - 184
  • [4] Effects of Inlet Gas Temperature and Relative Humidity on Performance Characteristics of PEM Fuel Cell
    Chang, Guofeng
    Xu, Yiming
    Fan, Ruijia
    [J]. Tongji Daxue Xuebao/Journal of Tongji University, 2021, 49 : 231 - 237
  • [5] Effects of Inlet Water Temperature and Heat Load on Fan Power of Counter-Flow Wet Cooling Tower
    Nguyen, Minh Phu
    Lee, Geun Sik
    [J]. TRANSACTIONS OF THE KOREAN SOCIETY OF MECHANICAL ENGINEERS B, 2013, 37 (03) : 267 - 273
  • [6] Improved Quantification of Exergy Destruction in Mechanical Cooling Tower Considering All Tower Inlet Parameters
    Singh, Kuljeet
    Das, Ranjan
    [J]. JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 2018, 140 (05):
  • [7] HEAT AND MASS TRANSFER PERFORMANCE AND EXERGY PERFORMANCE EVALUATION OF SEAWATER COOLING TOWER CONSIDERING DIFFERENT INLET PARAMETERS
    Yu, Yang
    Qi, Xiaoni
    Hou, Xiaochen
    Qu, Xiaohang
    Guo, Qianjian
    Zhu, Hegang
    [J]. THERMAL SCIENCE, 2022, 26 (05): : 3715 - 3728
  • [8] The effect of elevated inlet air temperature and relative humidity on Gas Turbine cogeneration system: exergy assessment
    Alasfour, F. N.
    Al-Fahed, S. F.
    Abdulrahim, H. K.
    [J]. INTERNATIONAL JOURNAL OF EXERGY, 2011, 8 (03) : 247 - 264
  • [9] Asymptotic analysis for the inlet relative humidity effects on the performance of proton exchange membrane fuel cell
    Liu, Yongfeng
    Fan, Lei
    Pei, Pucheng
    Yao, Shengzhuo
    Wang, Fang
    [J]. APPLIED ENERGY, 2018, 213 : 573 - 584
  • [10] Energy and performance analysis of multi droplets shower cooling tower at different inlet water temperature for air cooling application
    Zunaid, Mohammad
    Murtaza, Qasim
    Gautam, Samsher
    [J]. APPLIED THERMAL ENGINEERING, 2017, 121 : 1070 - 1079